FT2A Commands Supported
The FT2A supports the following commands:
1)
Command 03: Read holding registers
2)
Command 04: Read input register.
3)
Command 06: Preset single register
Read Holding Registers (command 03)
This command reads the basic variable from the FT2A and has the following format:
Request:
<Meter Address> <Command code=03> <Register start address high> <Register start
address low> <Register count high> <Register count low> <CRC high> <CRC low>
Response:
<Meter Address> <Command code=03> <Byte count> <Data high><Data low> ... <Data
high><Data low> <CRC high> <CRC low>
Example:
Request data register at starting address 0x0000 and specifying only 1 register
<0x01> <0x03> <0x00> <0x00> <0x00> <0x01> <0x0a> <0x84>
Response:
<0x01> <0x03> <0x02> <xx> <xx> <CRC high> <CRC low>
Where xx xx is the data register value.
Table 4.1: FT2A Modbus Holding Registers
Register
Address
Modbus
Address
Data Type
Scaling
Comment
0x00
40001
Flow in Eng units (low)
No
Mass flow in selected units
0x01
40002
Flow in Eng units (high)
No
0x02
40003
Total (low)
No
Total in selected units
0x03
40004
Total (High)
No
0x04
40005
Temperature (low)
*10
Temperature in selected units
* 10
0x05
40006
Temperature (high)
*10
0x06
40007
Elapsed time (low)
*10
Elapsed time in hours * 10
0x07
40008
Elapsed time (high)
*10
0x08
40009
Velocity (Low)
No
Velocity in nm/hr
Modbus/BACnet
6
FT2A Commands Supported by Modbus
MODBUS - F
T2A C
OMMANDS