RS485 Wiring: BACnet MS/TP
Wiring connections are made to terminal block TS2 for BACnet MS/TP communication.
The Tx/Rx+ signal connects to pin 7, Tx/Rx- connects to pin 8 and communication common to
pin 9 as shown in Figure 8.1.
Termination Resistor
Connect a termination resistor across the receive/transmit signals of the last device on the
BACnet MS/TP communication line. To connect the 121 ohm termination resistor on the FT2A,
set jumper W1 to the TERM position.
Disconnect the termination resistor on all other external BACnet MS/TP devices. The
termination resistor of the FT2A is disconnected by setting jumper W1 to the NC (Not
Connected) position.
Fig. 8.1: BACnet MS/TP Wiring
i
Note: W1 jumper will either be in the NC or TERM position. It should be in the TERM
position on the last meter in the BACnet MS/TP daisy chain.