Communication Protocol and Parameters
To program the communication parameters, press I/O (F1) key from the base menu.
F1 F2 F3 F4
Then press I/O (F1) again:
F1 F2 F3 F4
Then press COM (F1) to select communication parameters.
Set Bus protocol for BACnet:
F1 F2 F3 F4
Press NXT (F1) repeatedly until BACnet is selected as shown and then press OK (F4) to accept
the setting.
F1 F2 F3 F4
Press NXT (F1) repeatedly until the correct selection is shown and then press OK (F4) to accept
the setting.
Selections are:
“9600”
“19200”
“38400”
“57600”
“76800”
“115200"
Next select the MS/TP Mac address. The selection is from 0-127. Please note that only one
device can be on a MS/TP Mac address.
SET I/O
I/O FEQ 420 EXIT
SET I/O
COM CTC EXIT
Bus=BACnet
NXT OK
Baud=9600
NXT OK
Model FT2A
Modbus/BACnet
21
BACnet
BA
CNE
T PR
OGRAMMING
BACnet Programming