12
Before the ignition the “
System of Motor Protection from Overload
” has to be calibrated
setting the
Current Protection
on the internal regulator of the Board.
The
Protection Delay
is set at a fix time of
4 seconds
.
During the calibration close the “ESC.TIN.TA” JUMPER to disable the delay
protection;
The
Regulator of Current Protection
depends on the value of calibration set on the
board
(MOTORS 2-22A, MOTORS 20-44A );
Trimmer “CORRENTE”
Trimmer “CORRENTE”
N.B.: When the setting is complete, reset the protection tripping current delay time
by removing the “ESC.TIM.TA” JUMPER;
9a. REGULATION AND CALIBRATION
EXAMPLE OF CALIBRATION FOR MOTORS FROM 2 to 22A
- Current Protection Regulator
Set the current protection of the motor at
a value superior of about 10-20% of the
nominal current.
Example: for a motor with nominal
electrical input of 10A set it at about 12A
22A
2A
19A
3A
12A
6A
5A
15A
9A
EXAMPLE OF CALIBRATION FOR MOTORS FROM 20 to 44A
-
Current Protection Regulator
Set the current protection of the motor at
a value superior of about 10-20% of the
nominal current.
Example: for a motor with nominal
electrical input of 30A set it at about 36A
44A
20A
39A
23A
32A
26A
25A
35A
29A
Содержание Simplex-Up
Страница 17: ...17 CONFIGURATION 1 CONFIGURATION 2 NOT USE WITH DIRTY WATER 17a CONNECTION DIAGRAMS FOR SIMPLEX UP M...
Страница 18: ...18 CONFIGURATION 3 CONFIGURATION 4 17b CONNECTION DIAGRAMS FOR SIMPLEX UP M...
Страница 19: ...19 CONFIGURATION 1 CONFIGURATION 2 NOT USE WITH DIRTY WATER 17c CONNECTION DIAGRAMS FOR SIMPLEX UP T...
Страница 20: ...20 CONFIGURATION 3 CONFIGURATION 4 17d CONNECTION DIAGRAMS FOR SIMPLEX UP T...