BACTNET
MSTP MAC:
the address of the device that needs to be accessed. (0~255).
Device Number:
Indicate the number of the device.
The IEC power agreement
Link Addr:
Used for equipment addressing.
Common address:
The same as the link address, as the terminal address.
Reson Byte Length:
The 101 protocol is generally 1 bytes, and the 104 protocol is generally 2
bytes.
ASDU Common Addr Length:
The 101 protocol is generally 1 bytes, and the 104 protocol is
generally 2 bytes.
Infomation Addr Length:
The 101 protocol is generally 2 bytes, and the 104 protocol is generally
3 bytes.
Time period:
The period of clock synchronization between the main station and the sub station.
Fullcall cycle:
After the call control station is initialized, the control station must obtain all the
state signals of the field equipment and all the analog data.