Access to the second level
To access the parameters the controller must be in the stand-by mode.
To place the controller in ‘stand–by’ press
for 2 seconds, whilst in stand-by the cabinet internal air
temperature will be displayed intermittently.
Press
and
for 4 seconds the display will show ‘
PA
’.
Press ‘
0
’ will be displayed, press
to change the setting to ‘
-19
’
Press ‘
PA
’ will be displayed.
Press
and
for 4 seconds the display will show ‘
CA1
’ the first parameter in the second level.
Press
to display the value followed by
to decrease the value or
to increase the value.
Press
to return to the followed by
to move to the next parameter.
On completion of the changes press
plus
to exit or wait 60 seconds
Second Level Configuration Parameters
Mnem.
Definition
Min.
Max
Default
Dim.
Default
CA1
Air probe offset
-25
25
0
°K
0
CA2
Food probe offset
-25
25
0
°K
0
P0
Probe type (0 = PTC, 1 = NTC)
0
1
0
flag
0
P1
Decimal point active (0 = No, 1 = Yes)
0
1
1
flag
0
P2
Temperature unit (0 =
o
C, 1 =
o
F) 0
1
0
flag
0
P3
Food probe activation (0 = No, 1 = Yes)
0
1
1
flag
1
r0
Differential of parameters r7, r8, r9 and rA
0.1
15.0
2.0
°K
2.0
r1
Timed positive blast chilling duration
1
600
90
min.
90
r2
Timed negative blast chilling duration
1
600
240
min.
240
r3
Positive blast chill end point temperature (food probe)
-99.0 99.0 3.0
°C
3.0
r4
Negative blast chill end point temperature (food probe)
-99.0
99.0 -18.0 °C -18.0
r5
Set temperature positive blast chilling duration
1
600
90
min.
90
r6
Set temperature negative blast chilling duration
1
600
240
min.
240
r7
Positive blast chilling setpoint (air temp.)
-99.0
99.0
0.0
°C
0.0
r8
Negative blast chilling setpoint (air
temp.)
-99.0
99.0 -40.0 °C -25.0
r9
Post positive blast chilling storage setpoint
-99.0 99.0 2.0
°C
2.0
rA
Post negative blast chilling storage setpoint -99.0
99.0
-20.0 °C -20.0
rb
Negative blast chilling and storage enabling
0 (NO)
1
(YES)
1 flag 0
rc
Test for food probe insertion differential (0 = no test)
0.0
99.0
5
°K
5
rd
Duration of probe insertion test
1
99
60
sec.
60
C0
Compressor start delay
0
240
0
min.
0
C1
Compressor interval between starts
0
240
5
min.
5
C2
Minimum compressor shut down time
0
240
3
min.
3
C3
Minimum compressor run time
0
240
0
sec.
0
C4
Compressor shut down with air probe error in hold (if 'C11' = 0)
0
240
10
min.
10
C5
Compressor shut down with air probe error in positive chill cycle
(if 'C11' = 0)
0 240 10 min. 10
C6
Compressor shut down with air probe error in negative chill cycle
(if 'C11' = 0)
0 240 20 min. 20
C11
Food probe operation with air probe failure
0
1
0
flag
0
5
Содержание FX Blast Chiller
Страница 1: ...FX BLAST CHILLER ISO 14001 ISO 9001 ...
Страница 9: ...FXBC 10 Wiring Diagram 8 ...
Страница 10: ...FXBC 10R Wiring Diagram 9 ...
Страница 11: ...FXBC 20R Wiring Diagram 10 ...
Страница 12: ...FXBC 20R Wiring Diagram 11 ...
Страница 13: ...FXBC 30 Wiring Diagram 12 ...
Страница 14: ...13 FXBC 30R Wiring Diagram ...
Страница 15: ...FXBC 40 Wiring Diagram 14 ...
Страница 16: ...FXBC 40R Wiring Diagram 15 ...
Страница 17: ...16 ...
Страница 18: ...17 ...
Страница 19: ...18 ...