background image

4.4 Operation 

·

·

·

·

·

·

Push down the power switch once on the top panel to start the UPS. The LCD display 

lights up.  

To turn off the unit, simply push down the power switch again.

When operating in AC mode and utility power is interrupted, the unit will beep twice 

every 8 seconds to indicate that it has gone into battery mode. 

When operating in battery mode, the unit will beep every time the battery voltage falls 

under or rises above the acceptable limits. 

This UPS is designed for "off-mode charging”, that is when it is switched off, it will 

automatically recharge the internal battery as long as it remains connected to utility 

power. 

The display turns off in battery mode when the unit is powered off. In AC mode, the 

display remains on, but no output will be provided to the outlets.

4.5 DC start function

· The DC start function enables UPS to be started up when AC utility power is not available 

and battery is fully charged. Simply push the power switch to turn it on.  

5. LCD display

· The UPS comes equipped with an easy to read LCD with blue backlight that displays the 

battery status, input voltage, output voltage, and operation mode of the UPS.

1. Turn off and unplug all connected equipment.

2. Unplug the unit from the AC power source.

3. Turn the UPS upside down.

4. Use a screwdriver to remove the compartment screw. Slide the cover towards the back

    in order to remove it completely from the unit. 

5. Using the tabs, carefully lift the battery from the compartment. 

8. Battery replacement 

Forza makes the replacing of batteries a simple and quick installation process.  

Simply follow the steps described below.

Simply connect mobile devices into a USB charger port. This will automatically start charging 

the connected device.

·

Operation and status indicators

 

Number

1.

2.

3.

4.

5.

6.

7.

8.

Indication

AC normal mode

Back-up mode

Overload

Fault mode

Load capacity

Battery level

Input voltage

Output voltage

Description

This icon is displayed when utility power is normal

This icon is displayed when the unit is operating in battery mode

This icon is displayed when the connected load is beyond the

accepted range 

The icon becomes illuminated and the alarm will sound continuously in the 

event of abnormal operation of the UPS 

Indicates current loads at increments of 25% of its capacity 

Indicates charging level at increments of 25%

Indicates input line voltage 

Indicates output voltage value

When the input voltage is within acceptable range, UPS will 

provide pure and stable AC power to the output. The UPS will 

also charge the battery in AC mode.

In case of an overload, the alarm will beep once every 0.5 second

The alarm will beep once every 10 seconds.

It will always show 0 on the output voltage indicator.

UPS mode

LCD

Description

When AVR is functioning, the        icon blinks 

once every second 

When battery level is low, the       icon will 

blink once every second. 

AC mode

Overload in AC mode

Battery mode

Off-charging mode

The            icons will blink  

6. Storage 

· All connected equipment should be turned off prior to disconnecting them from the UPS 

to avoid battery drain. Unplug the UPS from the wall outlet and then turn it off for 

storage. 

·

·

Store the UPS unit covered in environments where the ambient temperature ranges 

from 5 to 86 °F with its battery fully charged.  

During extended storage, charge the UPS battery for 6 hours at least once every 6 

months.

7. Troubleshooting guide

· If the UPS fails to operate normally, please refer to the following table to solve most 

common installation and operation problems.

If any other abnormal situation not listed above should occur, please call our service department for further assistance.

When an overload occurs, the alarm will beep once every 0.5 

second.

UPS mode

LCD

Description

The             icons will blink.

Overload in battery mode

When a fault event is detected, the UPS alarm will beep 

continuously.

Fault mode

Press the power switch again to turn on the UPS

Allow the battery to recharge for at least 6 hours.  

Replace the battery.

Problem

Possible cause

Solution

The UPS is not on

Battery voltage is too low 

Battery fault 

UPS fails to turn on and the LCD 

is not illuminated

Allow the battery to recharge for at least 6  hours 

Replace the battery when it is weak or its performance degraded

Verify that the load matches the UPS capability specified. 

Remove the least critical equipment until load levels are back to 

normal.     

Battery voltage is too low 

Defective battery

Overload 

Backup time shorter than 

expected

Plug the power cord again into the wall outlet.  

Power cord is loose

The UPS remains in battery mode 

Содержание HT-750LCD

Страница 1: ...y can present the risk of short circuit current and electrical shock The following precautions should be taken Attention Potentially hazardous voltages from the battery can still be present even after disconnecting the UPS from the AC mains Therefore the positive and negative terminals of the battery shall be disconnected prior to performing any maintenance or repair inside the unit The UPS contai...

Страница 2: ...in the event of abnormal operation of the UPS Indicates current loads at increments of 25 of its capacity Indicates charging level at increments of 25 Indicates input line voltage Indicates output voltage value When the input voltage is within acceptable range UPS will provide pure and stable AC power to the output The UPS will also charge the battery in AC mode In case of an overload the alarm wi...

Страница 3: ...ency AC plug style Nominal voltage Frequency Frequency stability Waveform Total outlets Full battery Surge protection outlets Surge protection outlets only Network protection Phone modem fax protection Sat Cable protection USB charger Battery type and quantity Backup time Recharge time Battery replacement design Voltage regulation Boost feature Buck feature Automatic frequency selection Typical tr...

Страница 4: ...por segundo Modo de CA Sobrecarga en el modo de CA Modo de la batería Modo de carga con el interruptor apagado Los íconos se iluminan en forma intermitente 6 Almacenamiento Debe apagar todo los dispositivos conectados antes de desenchufarlos de la UPS para evitar el consumo innecesario de energía de la batería Desenchufe la UPS del tomacorriente de la pared y a continuación apague el interruptor p...

Страница 5: ...batería interna de 12V DC sellada de plomo ácido Jamás incinere las baterías puesto que pueden explotar si se exponen a altas temperaturas Gracias por preferir el sistema de alimentación ininterrumpible HT 750LCD HT 1000LCD de Forza Con el objeto de aprovechar todas las características y ventajas que le ofrece esta unidad haga el favor de leer y observar todas las instrucciones relativas a su inst...

Отзывы: