Forza FDC-106KMR-ISO Скачать руководство пользователя страница 3

• It is not recommend the use of this UPS in life support applications where failure or malfunctions of the product can be reasonably  

   expected to cause failure of the life support device or to significantly affect its safety or effectiveness. Do not use this equipment      

   in the presence of a flammable anesthetic mixture with air, oxygen or nitrous oxide.

• Connect your UPS power module’s grounding terminal to a grounding electrode conductor. 

• The UPS is connected to a DC energy source (battery). The output terminals may be live when the UPS is not connected to an AC  

   supply.

• This is a product for commercial and industrial application in the second environment – installation restrictions or additional  

    

   measures may be needed to prevent disturbances.

• In accordance with safety standard EN-IEC 62040-1, installation has to be provided with a “Backfeed protection” system, as a       

   contactor for example, which will prevent the appearance of voltage or dangerous energy in the input mains during a mains fault.      

   There is no standard backfeed protection inside of the UPS. Please isolate the UPS before operating the product according to       

   Diagram 1. The isolation device must be able to carry the UPS input current. 

Diagram 1: External backfeed protection wiring

Warning labels should be placed on all primary power switches installed in places away from the device to alert the  electrical 
maintenance personnel of the presence of a UPS in the circuit. The label will bear the following or an equivalent text:            

 

Do not disconnect the earth conductor cable on the UPS or the building wiring terminals at any time since this would cancel the 

protective earth of the UPS system and of all connected loads.

The UPS system features its own, internal current source (batteries). The UPS output sockets or output terminals block may be 

electrically live even if the UPS system is not connected to the building wiring outlet.

In order to fully disconnect the UPS system, first press the 

OFF

 button and then disconnect the power from the AC mains.

Do not allow any kind of liquid or foreign object to enter this UPS unit. Do not place beverages or any other containers with liquid 

on or nearby the unit.

The UPS can be operated by any individual with no previous experience.

1-5. Standards

2. Installation and operation

The Forza Atlas series is offered in four different models, as shown in the table below.

* Safety

Safety conformance: IEC/EN 62040-1,UL1778 (5th Edition)

* EMI

Conducted emission..............................:IEC/EN 62040-2,FCC PART15 CLASS A

Radiated emission.................................:IEC/EN 62040-2,FCC PART15 CLASS A

* EMS

ESD.........................................................:IEC/EN 61000-4-2

RS...........................................................:IEC/EN 61000-4-3

EFT..........................................................:IEC/EN 61000-4-4

SURGE....................................................:IEC/EN 61000-4-5

CS............................................................:IEC/EN 61000-4-6

Power-frequency magnetic field...............:IEC/EN 61000-4-8

Low frequency signals..............................:IEC/EN 61000-2-2

Level 4

Level 3

Level 4

Level 4

Level 3

Level 4

Model

Capacity

FDC-106KMR with isolation transformer  

FDC-110KMR with isolation transformer  

FDC-206KMR

FDC-210KMR

6000VA /6000W 

10000VA/ 1000W

6000VA /6000W 

10000VA/ 10000W 

Q

T

L/L1
N/L2

L/L1

External Distribution Panel

UPS

N/L2

Coil Remote Switch

Magneto_Thermal Input Main Switch

AC Contactor as backfeed protection device

N/L2 

Neutral L/L2

L/L1 

L1 Line Input

Legend

There can be no derivation in the line that goes from the «Backfeed protection» to the UPS, as the 
standard safety would be infringed.

Before working on this circuit

- Isolate Uninterruptible Power System (UPS)

- Then check for Hazardous Voltage between all terminals 

including the protective earth

Risk of Voltage Backfeed

Содержание FDC-106KMR-ISO

Страница 1: ...2 y e a r W a r r a n t y Ajustes 07_14_2017 User manual Uninterruptible Power Supply System FDC 106KMR ISO FDC 110KMR ISO FDC 206KMR FDC 210KMR...

Страница 2: ...he UPS must be thoroughly dry before being installed Failure to do so may increase the risk of electric shock Do not install the UPS system near water or in moist environments To reduce the risk of ov...

Страница 3: ...f the UPS system and of all connected loads The UPS system features its own internal current source batteries The UPS output sockets or output terminals block may be electrically live even if the UPS...

Страница 4: ...ry ground for battery pack 22 Output breaker 23 Maintenance bypass switch 24 Output control signal slot 25 Maintenance bypass ground 26 Maintenance bypass output terminals 27 Maintenance bypass UPS ou...

Страница 5: ...battery pack breaker must also be set to OFF before installing the battery pack Pay close attention to the rated battery voltage marked on the rear panel If you want to change the number of batteries...

Страница 6: ...VA load max Connect X1 X3 via jumper wire Connect N N via jumper wire This will give you 120V output for 10KVA load The following connection will give you two sets of 120V outputs each output takes 5K...

Страница 7: ...m the selected settings of the configuration menu Turns off the UPS Press and hold this button for 0 5 second to turn off the UPS Esc key Press this button to return to the last setting of the configu...

Страница 8: ...e UPS will perform an automatic battery self test on a periodic basis The default setting for the battery self test is once per week 3 Battery self test interval can also be set through the monitoring...

Страница 9: ...ixed 11 Operation in fault mode 1 When the Fault LED illuminates and the buzzer beeps continuously it means that there is a fatal error in the UPS Fault codes are available via the LCD panel Refer to...

Страница 10: ...re connected correctly 4 Turn on each UPS one by one and make sure that AC mode LED or Battery mode LED display is lit in each UPS Using a multimeter measure the output voltage of each UPS to make sur...

Страница 11: ...he load and complete ly shut down the UPS system 2 Enable the Bypass setting in each UPS and then power off the running UPS All UPS units in the parallel system will transfer to Bypass mode Remove all...

Страница 12: ...ce Setting 03 Voltage range for bypass Parameter 3 Frequency mode Enables you to set the output frequency in either CVCF mode or no CVCF mode You may choose any of the following two options in paramet...

Страница 13: ...V to 5 7V the default value is 0V Interface Setting 13 Battery voltage adjustment Parameter 2 You may choose Add or Sub to adjust the charger voltage Parameter 3 The voltage ranges from 0V to 9 9V the...

Страница 14: ...ress This operation is used to check the battery status 3 9 Fault codes 3 10 Warning indicators Fault event Bus start failure Bus over Bus under Bus unbalanced Inverter soft start failure High inverte...

Страница 15: ...UPS is overloaded UPS is overloaded Devices connected to UPS are fed directly with utility power through Bypass After repetitive overloads the UPS is locked in Bypass mode Connected devices are fed di...

Страница 16: ...utput Nominal voltage AC voltage regulation battery mode Frequency synchronized range Frequency battery mode Power factor Efficiency AC mode Efficiency battery mode Overload Transfer time line to batt...

Страница 17: ......

Отзывы: