Output voltage
Output frequency
Voltage range for bypass
Frequency range for bypass
ECO mode enable/disable
Voltage range for ECO mode
ECO mode frequency range setting
Bypass mode setting
Battery backup time setting
Reserved  
Reserved  
Hot standby function enable/disable
Battery voltage adjustment
Charger voltage adjustment
Inverter voltage adjustment
Output voltage adjustment

Code

Description

Bypass

Y

AC

ECO CVCF Battery Battery

test

Parameter 3: Output voltage

You may choose the following output voltage in parameter 3: 208: The output 
voltage is 208VAC

220:

 The output voltage is 220VAC 230: The output voltage is 230VAC

240:

 The output voltage is 240VAC

Or

104:

 The output voltage is 104VAC

110:

 The output voltage is 110VAC 

115:

 The output voltage is 115VAC

120:

 The output voltage is 120VAC

Interface

Setting

01: Output voltage settings

4. Removing one unit from the parallel system

There are two methods that can be used to remove one UPS from the parallel system:

First method:

1) Press the 

OFF

 button twice for about 0.5 second each. The UPS will enter into bypass mode without output.

2) After turning off the output breaker, do the same with the input breaker of the UPS.
3) After the UPS shuts down, turn off the battery breaker. Then remove the parallel cable and share current cable. You can now      
    remove the unit out from the parallel system.

Second method:

1) If the bypass is abnormal, the UPS cannot be removed without interruption. You must first power down the load and complete 
    ly shut down the UPS system.
2) Enable the Bypass setting in each UPS and then power off the running UPS. All UPS units in the parallel system will transfer to  
    Bypass mode. Remove all maintenance bypass covers and change the maintenance switches from 

UPS

 to 

BPS

. Next, turn off  

    input breakers and battery breakers.
3) Remove the desired UPS.
4) Turn on the input breaker of the remaining UPS units and the system will transfer to Bypass mode.
5) Set the maintenance switches from 

BPS

 to 

UPS

 and replace the maintenance bypass covers. Turn on the remaining UPS units  

    and finish the parallel system connections.

Warning:

 (parallel system only)

• Before turning on the parallel system to activate the inverter, make sure that every maintenance switch on the UPS is in the same      
   position.
• When the parallel system is turned on to operate through the inverter, do not change the maintenance switch of any unit.

3-6. Abbreviations on the LCD display

ENA

DIS

ATO
BAT
NCF

CF

SUB
ADD

ON

OFF
FBD

OPN

RES

OP.V

PAR

Enable
Disable
Auto
Battery
Normal mode (not CVCF mode)
CVCF mode
Subtract
Add
On
Off
Not allowed
Allow
Reserved
Output voltage
Parallel

Abbreviation

Display content

Meaning

Parameter 1: 

it is used for the different configu-

ration options. There are 16 programs to set up. 
Refer to the table below.

Parameter 2 and parameter 3:

 they represent 

the setting options or values of each program.

Parameter 1

Parameter 2

Parameter 3

List of the programs for parameter 1:

*Y means that this program can be set in this mode.

Note:

 All parameter settings will be saved only when UPS shuts down normally with internal or external battery connection. 

(Normal UPS shutdown means turning off input breaker in bypass/no output mode).

3-7. UPS parameter settings

Three parameters need to be configured in order to set up the UPS. Refer to following diagram:

Содержание FDC-106KMR-ISO

Страница 1: ...2 y e a r W a r r a n t y Ajustes 07_14_2017 User manual Uninterruptible Power Supply System FDC 106KMR ISO FDC 110KMR ISO FDC 206KMR FDC 210KMR...

Страница 2: ...he UPS must be thoroughly dry before being installed Failure to do so may increase the risk of electric shock Do not install the UPS system near water or in moist environments To reduce the risk of ov...

Страница 3: ...f the UPS system and of all connected loads The UPS system features its own internal current source batteries The UPS output sockets or output terminals block may be electrically live even if the UPS...

Страница 4: ...ry ground for battery pack 22 Output breaker 23 Maintenance bypass switch 24 Output control signal slot 25 Maintenance bypass ground 26 Maintenance bypass output terminals 27 Maintenance bypass UPS ou...

Страница 5: ...battery pack breaker must also be set to OFF before installing the battery pack Pay close attention to the rated battery voltage marked on the rear panel If you want to change the number of batteries...

Страница 6: ...VA load max Connect X1 X3 via jumper wire Connect N N via jumper wire This will give you 120V output for 10KVA load The following connection will give you two sets of 120V outputs each output takes 5K...

Страница 7: ...m the selected settings of the configuration menu Turns off the UPS Press and hold this button for 0 5 second to turn off the UPS Esc key Press this button to return to the last setting of the configu...

Страница 8: ...e UPS will perform an automatic battery self test on a periodic basis The default setting for the battery self test is once per week 3 Battery self test interval can also be set through the monitoring...

Страница 9: ...ixed 11 Operation in fault mode 1 When the Fault LED illuminates and the buzzer beeps continuously it means that there is a fatal error in the UPS Fault codes are available via the LCD panel Refer to...

Страница 10: ...re connected correctly 4 Turn on each UPS one by one and make sure that AC mode LED or Battery mode LED display is lit in each UPS Using a multimeter measure the output voltage of each UPS to make sur...

Страница 11: ...he load and complete ly shut down the UPS system 2 Enable the Bypass setting in each UPS and then power off the running UPS All UPS units in the parallel system will transfer to Bypass mode Remove all...

Страница 12: ...ce Setting 03 Voltage range for bypass Parameter 3 Frequency mode Enables you to set the output frequency in either CVCF mode or no CVCF mode You may choose any of the following two options in paramet...

Страница 13: ...V to 5 7V the default value is 0V Interface Setting 13 Battery voltage adjustment Parameter 2 You may choose Add or Sub to adjust the charger voltage Parameter 3 The voltage ranges from 0V to 9 9V the...

Страница 14: ...ress This operation is used to check the battery status 3 9 Fault codes 3 10 Warning indicators Fault event Bus start failure Bus over Bus under Bus unbalanced Inverter soft start failure High inverte...

Страница 15: ...UPS is overloaded UPS is overloaded Devices connected to UPS are fed directly with utility power through Bypass After repetitive overloads the UPS is locked in Bypass mode Connected devices are fed di...

Страница 16: ...utput Nominal voltage AC voltage regulation battery mode Frequency synchronized range Frequency battery mode Power factor Efficiency AC mode Efficiency battery mode Overload Transfer time line to batt...

Страница 17: ......

Отзывы: