background image

L

N

L

N

Ground

L

N

L

N

Ground

Input neutral

Input line

Output neutral

Output line

Diagram 1: Power cable connection

Parallel communication port connection

Share current cable connection

Diagram 2: Wiring diagram of parallel system 

2. Parallel system connection 

NOTE: 

For parallel installation each UPS must have a maintenance bypass output breaker/switch connected. This device is offered 

separately. 

1) Once you have verified all wiring has been done properly, turn off the input, output and battery breakers of each UPS. 
2) Remove all the maintenance bypass covers and change the maintenance switches from 

UPS

 to 

BPS

, turn on the input breaker    

    of the each UPS and change the maintenance switches from 

BPS

 to 

UPS

. When done, replace the maintenance bypass cover.  

    With a multimeter, measure the L1-N1 and L2-N2 voltage difference between each UPS. If the voltage difference is less than        
    2V, it means all connections are correct. If the difference is higher than 2V, check if the wiring has been done correctly.
3) Turn on the input breakers of each UPS in the parallel system. Before turning on each UPS in turns, check if PAR001~PAR003  
    are displayed in each UPS sequentially. If no “PARXX exists in any UPS, please check if the parallel cables are connected  

   

    correctly.
4) Turn on each UPS one by one and make sure that AC mode LED or Battery mode LED display is lit in each UPS. Using a    

   

    multimeter, measure the output voltage of each UPS to make sure the voltage difference is less than 2V (typical 1V). If the  

    

    difference is above 2V, check that parallel cables and/ or parallel current cables are connected properly. If all connections are     
    done properly, it may be a UPS internal issue. In this case, contact your local distributor or service center for help.
5) Turn off each UPS in sequence. After all of the UPS are transferred to Bypass mode, turn on the output breaker of each unit.
6) Finish by turning on the UPS units in AC mode. Now the system is ready for operation in parallel mode. 

3. Adding one new unit into the parallel system

1) You cannot add one new unit into the parallel system while the whole system is running. First, all loads and each UPS in the        
    system must be shutdown.
2) Make sure all of the UPS are parallel models, and follow the wiring scheme shown earlier in this manual.
3) Install the new UPS and follow instructions in the previous section for proper connection, testing and startup.

Full installation with maintenance bypass and isolation transformer (110V or 220V operation)

MAINTENANCE

BYPASS

UPS

BATTERY PACK

ISO (Output to load)

Full installation with maintenance bypass (220V operation only)

MAINTENANCE

BYPASS

(Output to load)

UPS

BATTERY PACK

Output load

Ground

Содержание FDC-106KMR-ISO

Страница 1: ...2 y e a r W a r r a n t y Ajustes 07_14_2017 User manual Uninterruptible Power Supply System FDC 106KMR ISO FDC 110KMR ISO FDC 206KMR FDC 210KMR...

Страница 2: ...he UPS must be thoroughly dry before being installed Failure to do so may increase the risk of electric shock Do not install the UPS system near water or in moist environments To reduce the risk of ov...

Страница 3: ...f the UPS system and of all connected loads The UPS system features its own internal current source batteries The UPS output sockets or output terminals block may be electrically live even if the UPS...

Страница 4: ...ry ground for battery pack 22 Output breaker 23 Maintenance bypass switch 24 Output control signal slot 25 Maintenance bypass ground 26 Maintenance bypass output terminals 27 Maintenance bypass UPS ou...

Страница 5: ...battery pack breaker must also be set to OFF before installing the battery pack Pay close attention to the rated battery voltage marked on the rear panel If you want to change the number of batteries...

Страница 6: ...VA load max Connect X1 X3 via jumper wire Connect N N via jumper wire This will give you 120V output for 10KVA load The following connection will give you two sets of 120V outputs each output takes 5K...

Страница 7: ...m the selected settings of the configuration menu Turns off the UPS Press and hold this button for 0 5 second to turn off the UPS Esc key Press this button to return to the last setting of the configu...

Страница 8: ...e UPS will perform an automatic battery self test on a periodic basis The default setting for the battery self test is once per week 3 Battery self test interval can also be set through the monitoring...

Страница 9: ...ixed 11 Operation in fault mode 1 When the Fault LED illuminates and the buzzer beeps continuously it means that there is a fatal error in the UPS Fault codes are available via the LCD panel Refer to...

Страница 10: ...re connected correctly 4 Turn on each UPS one by one and make sure that AC mode LED or Battery mode LED display is lit in each UPS Using a multimeter measure the output voltage of each UPS to make sur...

Страница 11: ...he load and complete ly shut down the UPS system 2 Enable the Bypass setting in each UPS and then power off the running UPS All UPS units in the parallel system will transfer to Bypass mode Remove all...

Страница 12: ...ce Setting 03 Voltage range for bypass Parameter 3 Frequency mode Enables you to set the output frequency in either CVCF mode or no CVCF mode You may choose any of the following two options in paramet...

Страница 13: ...V to 5 7V the default value is 0V Interface Setting 13 Battery voltage adjustment Parameter 2 You may choose Add or Sub to adjust the charger voltage Parameter 3 The voltage ranges from 0V to 9 9V the...

Страница 14: ...ress This operation is used to check the battery status 3 9 Fault codes 3 10 Warning indicators Fault event Bus start failure Bus over Bus under Bus unbalanced Inverter soft start failure High inverte...

Страница 15: ...UPS is overloaded UPS is overloaded Devices connected to UPS are fed directly with utility power through Bypass After repetitive overloads the UPS is locked in Bypass mode Connected devices are fed di...

Страница 16: ...utput Nominal voltage AC voltage regulation battery mode Frequency synchronized range Frequency battery mode Power factor Efficiency AC mode Efficiency battery mode Overload Transfer time line to batt...

Страница 17: ......

Отзывы: