EN-

US

4

Ford Connected Charge Station Installation manual

SKML9J-10C823-BA

3.2.2

Wi-Fi

You can use Wi-Fi communication to connect the charge
station to the charging backend. This enables you to config-
ure the charger remotely through the FordPass™ app.

4

Power supply interface
connections

The terminals on the right, marked GND, X2, X1, must be con-
nected to the charging cable.

Fig. 1

The terminals on the left, marked L2, L1, GND, must be con-
nected to the mains.

Fig. 2

CAUTION

The wire colors shown in the illustrations
are for example purposes only.

Please follow the National Electrical Code (NEC) for the
appropriate wire color-coding.

5

Installation

Observe the safety information provided in section Impor-
tant Safety Information.

NOTICE

In addition to the user manual and installation manual,
follow and comply with the local regulations relating to
operation, installation, and environmental protection.

5.1

Product location considerations

When choosing the installation location for the Ford Con-
nected Charge Station, make sure that the location allows
the charging cable to reach the vehicle charge port without
straining the cable.
See Fig.19 on the inside of the back page.
You must also make sure that:

– If you are installing more than one Ford Connected

Charge Station, then you must minimally leave 200 mm
(7.9 inches) in between.

– The Ford Connected Charge Station is installed at least

900 mm (35.5 inches) above floor level.

– The mounting surface is solid and strong.
– The mounting surface is completely flat.

– The mounting surface does not have any flammable sub-

stances.

– The pavements and escape routes are not obstructed.
– You have fault-free Wi-Fi reception if you want to remote

control the charger through the Ford backend.

– The Ford Connected Charge Station is outdoor-rated;

however, for locations in intense climates, you may want
to shield the unit from intense direct sunlight and spray
to extend its useful life and fault-free operation.

5.2

Criteria for electrical connection

The Ford Connected Charge Station type label indicates the
maximum charging current that you can configure. The type
label on the Ford Connected Charge Station is located on
the right.
The power availability at the service connection determines
the maximum permitted charging current. A qualified elec-
trician must make the necessary settings in the configura-
tion. They must also verify the prerequisites for connection.
The installation must comply with the nationally applicable
regulations of authorities and power supply companies, such
as the registration of the installation of a charge station. All
protective devices specified must be designed in such a way
that every power supply pole of the Ford Connected Charge
Station is disconnected if a fault occurs. You must meet na-
tional installation regulations and standards when selecting
the protective device.

NOTICE

Do not install a GFCI (Ground Fault Circuit Interrupter).

5.2.1

DIP switch settings

WARNING

High voltages

Danger of fatal electric shock.

D1

D2 D3 D4 [A]

Comment

0

0

0

0

Invalid, default
48A, 60A CB

0

0

0

1

Invalid, default
48A, 60A CB

0

0

1

0

12 A, 15A CB

D1

D2 D3 D4 [A]

Comment

0

0

1

1

16 A, 20A CB

0

1

0

0

20 A, 25A CB

0

1

0

1

24 A, 30A CB

0

1

1

0

32 A, 40A CB

0

1

1

1

40 A, 50A CB

1

0

0

0

48 A, 60A CB

1

0

0

1

48 A, 60A CB

1

0

1

0

48 A, 60A CB

1

0

1

1

48 A, 60A CB

1

1

0

0

48 A, 60A CB

1

1

0

1

48 A, 60A CB

1

1

1

0

48 A, 60A CB

1

1

1

1

48 A, 60A CB

D5

Comment

0

1

Invalid, default
48A, 60A CB

5.2.2

Power supply isolation device

The Ford Connected Charge Station does not have its own
power ON/OFF switch. The protective devices installed in
the power supply system are therefore also used to discon-
nect the Ford Connected Charge Station.

5.2.3

Dimensioning the lead’s cross-
section

A qualified electrician must determine the conductor’s
cross-section / wire gauge size.
The conductor cross-section of the lead depends on:

– The maximum power availability from the service con-

nection

– The cable length

Содержание Connected Charge Station

Страница 1: ...Installation manual 48A Single Phase Ford Connected Charge Station ...

Страница 2: ...GND X2 X1 1 L2 L1 GND 2 3 4 5 1 6 ...

Страница 3: ...7 8 9 10 11 12 ...

Страница 4: ...13 14 15 16 17 18 ...

Страница 5: ...A B C D E F G H AA AB AC AD AE AF AG 0 5 x 3 5 mm 29 mm 36 mm 40 mm T x 6 T x 20 T x 25 3 mm 1 8 Inch 8 mm 3 8 Inch 19 ...

Страница 6: ...DIP switch settings 4 5 2 2 Power supply isolation device 4 5 2 3 Dimensioning the lead s cross section 4 5 3 Step by step installation 5 5 3 1 Required tools 5 5 3 2 Installing the mounting bracket 5 5 3 3 Removing the front cover 5 5 3 4 Installing the blind plugs and conduit fitting 5 5 3 5 Installing the charging cable 6 5 3 6 Mounting the rear housing 6 5 3 7 Connecting the grid cable 6 5 3 8...

Страница 7: ... Station has been developed produced tested and documented according to the rele vant safety regulations and environmental requirements that apply to your geographical area You must only use the charge station in a technically fault less condition Any malfunctions that adversely affect the safety of persons or of the device must be immediately rec tified by a qualified electrician in accordance wi...

Страница 8: ...ageways Do not install the charge station in areas subject to am monia or air containing ammonia Do not install the charge station in a location where falling objects may damage it The charge station is suitable for indoor and outdoor use Do not install the charge station in the vicinity of water jets such as car wash installations high pressure clean ers or garden hoses Protect the charge station...

Страница 9: ... kg Installation height Minimally 35 inches above floor level regarding to the bottom of the de vice Minimally 900 mm above floor level regarding to the bottom of the de vice IP protection class NEMA Type 3S IP65 Protection against mechanical impact UL2994 Ambient conditions Operating tempera ture range 40 F to 140 F 40 C to 60 C Storage tempera ture range C 40 F to 185 F 40 C to 85 C Altitude m M...

Страница 10: ...ct sunlight and spray to extend its useful life and fault free operation 5 2 Criteria for electrical connection The Ford Connected Charge Station type label indicates the maximum charging current that you can configure The type label on the Ford Connected Charge Station is located on the right The power availability at the service connection determines the maximum permitted charging current A qual...

Страница 11: ...rx T25 screwdriver and two screws 6 x 90 mm x 3 inch to mount the bracket on the pole 5 3 3 Removing the front cover Use a Torx T25 screwdriver to remove the three transport safety screws M4 x 16 mm inch from the front cover as shown in Fig 4 and make sure to keep these for later in stallation Fig 4 5 3 4 Installing the blind plugs and conduit fitting 1 Choose the appropriate conduit in accordance...

Страница 12: ...grip The upper part has larger screw holes and recesses in which the screws can move freely 5 3 6 Mounting the rear housing Use a Torx T20 screwdriver and two screws M4 x 16 mm to mount the rear housing onto the mount bracket torque 4Nm 3 ft lb Fig 10 5 3 7 Connecting the grid cable To connect the grid cable to the Ford Connected Charge Sta tion 1 Remove any debris such as insulation trimmings fro...

Страница 13: ...older out of the box 2 Mark the drill holes by using the rear part of the dock holder as a template 3 Drill two holes 8 mm 5 16 inch in the marked posi tions 4 Push the two dowels 8 x 50 mm 5 16 x 2 Inches firmly into the drill holes 5 Use a Torx T20 screwdriver and two screws 6 x 90 mm x 3 5 inches to mount the dock s rear holder on the wall Fig 16 6 Carefully clip the dock front cover onto dock ...

Страница 14: ...tibility To download the User Manual Installation Manual for the Ford Connected Charge Station browse to https owner ford com or www ford ca owners Published October 20 2020 5110776 CL1 WALLBOX FORD INSTALLATION MANUAL SAE 10 Installation checklist Please complete the Ford Connected Charge Station instal lation checklist Variant 1 phase Serial number Material number General preconditions Installat...

Отзывы: