AST 14 C 258/00
Jumper
Dip
switch
RS connection and settings
Regardless of the number of boards
used, each board must be connected to
the boiler board in cascade via an RS485
connection, as shown in the diagram on
the right:
The boiler boar dand the additional board are provided with a jumper that closes the 485
communication line in case of difficulty in transmitting data between the boards, due to
very long connection lines or electromagnetic interferences.
This jumper must only be left on the last board in cascade; all the others, including
the one on the boiler board, must be removed.
Each 0SCHEZON01 additional board with the
dip switches must be set in such a way as to
associate it to the zone to be controlled or to
the solar system.
Only the first two of the three dip switches are
used for the setting (the third one must be left
in the “down” position, i.e. OFF).
BOILER
CARD
BOILER
BOARD
ZONE2
ZONE3
ZONE4
SOLAR
MIXED ZONE2
MIXED ZONE3
MIXED ZONE4
COMPLEX SOLAR