INSTALLATION INSTRUCTIONS

Preliminary Notes Before Installation

This appliance is a high efficiency, flueless, flame effect gas fire.  It provides radiant and con-
vected warmth both efficiently and safely utilising the latest type catalytic convertor burner
technology.

The appliance incorporates a combustion monitoring system (Oxygen Depletion System). It
must not be adjusted or put out of operation. If replaced then manufacturers original parts
must be used.

The appliance is designed to fit various types of situations as listed in the Installation
Requirements.  

This appliance must be installed in accordance with the rules in force and only used in a suf-
ficiently ventilated space.  A minimum of 100cm

(15.5in

2

) purpose provided ventilation is

required for this appliance. An openable window or louvre is also required. This appliance is
factory set for operation on the gas type, and at the pressure stated on the appliance data
plate.

The room size should be a minimum of 23m

3

(812ft

3

) to allow adequate circulation of air

and ensure the correct operation of the fire. This volume may include adjacent spaces but
these spaces must not be separated by a door. In order to convert from cubic feet (ft

3

) to

cubic metres (m

3

) divide the room volume (in ft

3

) by 35.3. This appliance is intended as a

secondary source of heat only and should not be used in a room without some form of
background heating present.

The appliance must not be installed in a bedroom, bathroom or any sleeping area.  The
appliance does not require a flue system of any type as the catalytic converter cleans the
flue products to provide a complete combustion system, which is intrinsically safe.

The appliance must be installed by a competent person in accordance with Gas Safety
(Installation and Use) Regulations 1998 or rules in force. It is strongly recommended that a
CORGI registered engineer is used for this purpose, as they are the only persons approved
by the HSE under the above regulations.

On initial lightup of a new appliance, the ‘newness’ will burn off within the first few hours of
operation. During this period some smoke may be emitted from outlet grille, this should be
no cause for concern.  Accordingly, the room should be well ventilated with all windows
and doors open during this period.

Read all these instructions before commencing installation.

Содержание L23 BLACK

Страница 1: ...ser for safekeeping Revision A 03 08 Country s of destination GB IE L23 CHESHIRE P23 MONET TRIO P23 ENIGMA FLUELESS GAS FIRE Focal Point Fires plc Christchurch Dorset BH23 2BT Tel 01202 499330 Fax 012...

Страница 2: ...L23 Cheshire P23 Monet trio P23 Enigma silver glass...

Страница 3: ...fire This volume may include adjacent spaces but these spaces must not be separated by a door In order to convert from cubic feet ft3 to cubic metres m3 divide the room volume in ft3 by 35 3 This app...

Страница 4: ...only in a sufficiently ventilated space A minimum of 100cm2 15 5 in2 purpose provided ventilation is required for this appliance an openable window or louvre is also required To reduce the possibility...

Страница 5: ...is common however other rooms such as kitchens dining rooms and hallways are permitted providing a suitable natural gas supply is available and rooms sizing and ventilation requirements are strictly a...

Страница 6: ...s etc be positioned on the wall above the appliance The appliance is designed to be wall mounted alone and not in conjunction with any type of combustible fire surround No combustible shelves should b...

Страница 7: ...met 1 Fitting template GAS SUPPLY ROUTES There are four possible entry points for the gas supply pipework to enter the appliance firebox These entry points are knock out type holes Non concealed gas c...

Страница 8: ...p wall plugs taking care to leave the screws protruding approximately 5mm from the wall Now hang the appliance onto these screws through the two key hole shaped holes in the back panel of the applianc...

Страница 9: ...If under any circumstances the piezo electric spark fails the pilot cannot be lit man ually SETTING PRESSURE The pressure test point is located on the left hand side of the appliance on the main burne...

Страница 10: ...ve packaging The glass facia panel is supported by four M6 screws which protrude from the front of the outer casing Ensure each screw is unscrewed approxi mately one turn from the fully screwed in pos...

Страница 11: ...detailed in section 8 4 13 Check the purpose provided ventilation is un obstructed 14 Light the fire and test setting pressures 15 Check safe operation of the appliance For specific servicing instruct...

Страница 12: ...ed by the analyser also noting the units in which the values are expressed Most analysers display carbon dioxide CO2 concentrations in percentage terms and carbon monoxide concentration in parts per m...

Страница 13: ...tray realign HT lead Fire runs for a time and then cuts off Loose or faulty thermocouple rectify Blocked pilot clean out Dirt or lint in pilot aeration hole or on the lint gauze clean thoroughly If th...

Страница 14: ...dicator bracket Combustible items such as flooring and furniture and soft wall coverings such as blown vinyl or embossed paper low temperature surrounds etc may discolour if fitted too close to the fi...

Страница 15: ...dis colouration may occur over time The appliance must not be positioned vertically within 100 mm of a carpeted floor rugs or fabric materials of any kind This dimension is measured vertically to the...

Страница 16: ...y device ODS If the appliance shuts down during use for no apparent reason then several reasons may be suspected If a door or window has been opened creating a draught then pilot disturbance could be...