INSTALLATION REQUIREMENTS
If the appliance is to be sited near a disused or unserviceable fireplace served by a natural draught flue then the
old flue must be sealed off. It will be necessary to ventilate the old flue to prevent condensation and dampness
forming, however any air vent used to ventilate the old flue must not be sited within 500mm of this appliance.
If the flue can be ventilated to the outside of the building then this is usually the best solution. If in doubt then
advice should be sought from a local building control officer. The appliance is designed to be wall mounted. If
the appliance is to be mounted on a newly fabricated area of wall that also serves the purpose of sealing off the
old flue then it is very important that there are no holes, gaps or otherwise in this wall that will allow draughts
from the old flue to enter the room, especially directly behind the appliance. Such draughts could affect the per-
formance of the ODS system and result in nuisance cutting out, for example. If the gas supply pipe is to enter
the appliance from the rear, i.e. emerge from the wall behind the appliance, then any hole in the wall from which
the pipe emerges must be tightly sealed. Propane/LPG models must not be installed in cellars, basements or any
room which is completely below ground level.
ROOM SIZING
The room size should be a minimum of 40m
3
(e.g. 13’4” x 13’4” x 8’). to allow adequate circulation of air and
ensure the correct operation of the fire. This volume may include adjacent spaces but these spaces must not
be separated by a door. To calculate a room size in cubic metres (m
3
) divide the room volume in cubic feet
(ft
3
) by 35.3. This appliance is intended as a secondary source of heat only and should not be used in a room
without some form of background heating present.
SITE REQUIREMENTS
This appliance is designed to be wall-hung. Do not recess any part of the appliance into the wall.
This appliance may be installed in any room in the home except bathrooms or bedrooms. Installation in living
rooms is common, however other rooms such as kitchens, dining rooms and hallways are permitted, providing
a suitable natural gas supply is available, and rooms sizing and ventilation requirements are strictly adhered to
(see sections 3.1 and 4.1).
The appliance is designed to be versatile, and as such will operate correctly when exposed to normal gentle
draughts experienced within the home. It is not recommended, however that the appliance be installed in areas
where it is likely to be directly exposed to persistent strong draughts, that may be generated by outside doors,
windows, air vents, air conditioning units, extractor fans, ceiling fans etc. See section 4.1 for more information
on ventilation.
2
2.0
3.0
3.1
4.0
APPLIANCE DATA
Gas Group
G20 Natural Gas CAT I2H
Inlet Pressure
20 mbar (+/- 2.0mbar)
Regulator Pressure
N/A
Max Energy Input - Gross
3.5 kW
Max Energy Input - Net
3.15 kW
Max Gas Rate
0.34 m3/h
Min Energy Input - Gross
2.0 kW
Min Energy Input - Net
1.8 kW
Pilot Energy Input - Gross
166 W
Pilot Energy Input - Net
150 W
Burner Pressure High (Hot)
18.0 mbar (+/-1.5 mbar)
High (Cold)
17.5 mbar (+/-1.5 mbar)
Low (Hot)
5.8 mbar (+/-0.75 mbar)
Low (Cold)
5.3 mbar (+/-0.75 mbar)
Main burner flow restrictor
Stereo 1.45mm (1/4” BSP)
Injector
N/A
Oxypilot
SIT/Bray 9082
Gas Inlet Connection
8mm inlet restrictor elbow
Ignition
Piezo spark
Gas Valve
BM733/NGC6802A
Spark Gap
4.0 mm (± 1.0mm)
Please see Data Badge affixed to appliance for current data.
This appliance is for use only with the gas type, and at the pressure stated on the appliance Data Badge.
©
2008 Focal Point Fires plc.
G31 Propane CAT I3P
37 mbar (± 2.0mbar)
24.5 mbar
3.0 kW
2.75 kW
0.115 m3/h
2.0 kW
1.85 kW
166 W
152 W
14.0 mbar (+/-1.5 mbar)
13.7 mbar (+/-1.5 mbar)
6.0 mbar (+/-0.75 mbar)
5.9 mbar (+/-0.75 mbar)
Stereo 1.45mm (1/4” BSP)
1.30 mm (single)
Seagas P5-19 /SIT/Bray 9286
8mm inlet restrictor elbow
Piezo spark
BM733/NGC6802A
4.0 mm (± 1.0mm)