Operation Manual EMGZ490A
30.08.2019
7
3
Quick Installation Guide
The set-up of the EMGZ490A and force sensors is limited to only the installation procedure,
offset compensation and the calibration.
3.1
Preparations for Set-up
1.
Read the Operation Manual of your force measuring sensors
2.
Check your requirements such as:
– required measuring units in the system
–Used outputs (0…10V and Bus)
–Filter settings for analogue output
3.
Draw the wiring diagram for your configuration (ref. to 3.5 “Wiring the Amplifier“)
3.2
Installation Procedure
1.
Mount the force maesuring sensors to the machine frame (ref. to chapter 3.4)
2.
Wire the Force Measuring Sensor(s) (ref. to Fig. 2)
3.
Connect the amplifier to the power supply.
4.
The supply voltage must in the range between 18 and 36V DC.
5.
Perform offset compensation and calibration (ref. to chapters 4.1 to 4.3)
4.
If required, do additional settings (chapter 8.2)
5.
In tegrate the amplifier in the PROFINET-network (chapter 5)
3.3
Installation and Wiring
Caution
In order to improve the natural convection and keep the temperature of the amplifiers
that are mounted in a cabinet, to a minimum, a distance of at least 15mm (0.6”)
between the devices must be kept.
.
Caution
Proper function of the Tension Measuring Amplifier is only guaranteed with the
recommended application of the components. In case of other arrangement, heavy
malfunction can be the result. Therefore, the installation instructions on the following
pages must be followed strictly.
Caution
Local installation regulations are to preserve safety of electric equipment. They are not
taken into consideration by this operating manual. However, they have to be followed
strictly.
3.4
Mounting the Force Sensors
Mounting of the force sensors is done according to the FMS Installation manual which is
delivered together with the force sensors.