Operation Manual EMGZ490A
30.08.2019
17
Tension at Max. Output
Use:
This parameter defines what force value (N, kN, lb, g, kg) corresponds to
the maximum output of the amplifier (10V).
Note:
By changing the units to
lb
the whole unit system will change from
metric to imperial units.
Unit
Parameter Range
Selection
Default
Min
Max
N, kN, g,
kg, lb
(1
0 200’000.000
-
1000.000
1)
The display shows the unit of measure that was previously selected.
Offset
Use:
The value determined with the adjustment procedure
Offset
Compensation
is stored as a Digit value in the parameter
Offset
. The
offset value is used to compensate the weight of the measuring roller.
Unit
Parameter Range
Selection
Default
Min
Max
- -8000 8000
-
0
Gain
Use:
This parameter stores the value determined with the Procedure
Calibration
in the parameter
Gain
.
Unit
Parameter Range
Selection
Default
Min
Max
0.100
20.000
-
1.000
System Force
Use:
The System Force determines the measuring capability of your
measuring roller. E.g. if two 500 N sensors are installed in your
measuring roller, enter 1000N. If only one 500N sensor is used, enter
500N. If sensors with sheaves are used (e.g. RMGZ-Series), 500N must
be entered.
Unit
Parameter Range
Selection
Default
Min
Max
N, kN, g,
kg, lb
(1
0 200’000.000
-
1000.000
1)
The display shows the unit of measure that was previously selected..