Configuration
The configuration of the EMGZ490A can be performed either over a web interface or
over PROFINET. In both case the same parameters are configured.
6.1
Description of Parameters
PROFINET Filter
Use:
The amplifier provides a low-pass filter for PROFINET data to prevent
noise and interferences being overlaid to the PROFINET output. This
parameter determines the cut off frequency of the filter. The lower the
cut off frequency, the more sluggish the output will be. The PROFINET
Filter is independent of the analogue output filter.
Unit
Parameter Range
Selection
Default
Min
Max
Hz 0.1 200.0
-
10.0
Analog Output Filter
Use:
The amplifier provides a low-pass filter to prevent noise and
interferences being overlaid to the analogue output signal. This
parameter determines the cut off frequency of the filter. The lower the
cut off frequency, the more sluggish the signal at the analogue output
will be. The Analogue Output Filter is independent of the PROFINET Filter.
Unit
Parameter Range
Selection
Default
Min
Max
Hz 0.1 200.0
-
10.0
Tension Unit
Use:
This parameter determines the unit used in the system. The label on the
sensor specifies the nominal force always in N.
Note:
By changing the units to
lb
the whole unit system will change from metric
to imperial units.
Unit
Parameter Range
Selection
Default
Min
Max
- -
N
kN
lb
g
kg
N