Operating Manual CMGZ432
38
Output limit
Use:
This parameter defines the range for the output signal. „80%“ refers to
„±8V“ resp. „0...8V“ resp. „0...16mA“ resp. „4...16.8mA“, depending
on parameter
Output configuration
.
Range:
0.1
to
100.0
Default:
100.0
Increment:
0.1
Unit:
[%]
Output configuration
Use:
With this parameter, you can choose the output signal. With setting
„±10V“, the drive unit can run and brake both in forward and reverse
direction. With the other settings, the drive unit can only run and
brake in forward direction.
FMS recommends setting to „±10V“ if the used drive unit supports
this signal.
Range:
±10V, 0...10V, 0...20mA, 4...20mA
Default:
±10V
Ramp diameter
Use:
To optimize the controller against disturbances, the diameter should
not change too fast. For this, the diameter signal is led internally to a
ramp. Its rate of rise is defined using this parameter. The length of the
ramp defines the time the diameter will take for a changement of
1mm.
Range:
0.1
to
60.0
Default:
1.0
Increment:
0.1
Unit:
[s]
Ramp reference
Use:
To optimize the controller against disturbances, the reference value
should not change too fast. For this, the reference value signal is led
internally to a ramp. Its rate of rise is defined using this parameter.
The length of the ramp defines the settling time the reference will take
to set to the new value.
Range:
0.1
to
20.0
Default:
1.0
Increment:
0.1
Unit:
[s]
Reference Internal / External
Use:
If the reference value will be set using the operating panel or the
interface, this parameter has to be set to
internal
. If the reference value
will be set using a 0...10V signal led to the analog input, this
parameter has to be set to
external
.
Range:
Internal,
External
Default:
Internal