UV32C and RUV32 UNVENTED 32" FIREBOX

FIREPLACE MANUFACTURERS INC.

AIR FOR
COMBUSTION AND
VENTILATION

Continued

VENTILATION AIR

Ventilation Air From Inside
Building

This fresh air would come from an adjoining
unconfined space. When ventilating to an
adjoining unconfined space, you must pro-
vide two permanent openings: one within
12" of the ceiling and one within 12" of the
floor on the wall connecting the two spaces
(see options 1 and 2, Figure 4). You can also
remove door into adjoining room (see op-
tion 3, Figure 4). Follow the National Fuel
Gas Code NFPA 54/ANS Z223.1, Section
5.3, Air for Combustion and Ventilation
 for
required size of ventilation grills or ducts.

 WARNING: Rework work-

sheet, adding the space of the
adjoining unconfined space. The
combined spaces must have
enough fresh air to supply all
appliances in both spaces.

Figure 5 - Ventilation Air from Outdoors

Ventilation Air From Outdoors

Provide extra fresh air by using ventilation
grills or ducts. You must provide two per-
manent openings: one within 12" of the
ceiling and one within 12" of the floor.
Connect these items directly to the outdoors
or spaces open to the outdoors. These spaces
include attics and crawl spaces.

IMPORTANT:

 Do not provide openings for

inlet or outlet air into attic if attic has a
thermostat-controlled power vent. Heated air
entering the attic will activate the power vent.

Figure 4 - Ventilation Air from Inside Building

,,,,

,,,,

,,,,

,,,,

,,,,

,,,,

,,,,

,,,,

,,,,

,,,,,

,,,,,

,,,,,

,,,,,

,,,,,

,,,,,

,,,,,

,,,,,

,,,,,

,,,,,

,

,

,

,

,

,

,

,

,

,

,

,

,

,

,

,

,

,

,

,

,

,

,

,

,

,

,

,

,

,

,

,

,

,

,

,

,

,

,

,

,

,

,

,

,

,

,

,

,

,

,

,

,

,

,

Or

Remove

Door into

Adjoining

Room,
Option

3

Ventilation Grills 

Into Adjoining Room,

Option 2

Ventilation

Grills 

Into Adjoining 

Room,

Option 1

12"

12"

Outlet
Air

Ventilated
Attic 

Outlet
Air

Inlet
Air

Inlet Air

Ventilated 

Crawl Space

To 

Crawl

Space

To Attic

,,,,,,,

,,,,,,,

,,,,,,,

,,,,,,,

,,,,,,,

,,,,,,,

,,,,,,,

,,,,,,,

Содержание RUV32

Страница 1: ...tion adjustment alteration ser vice or maintenance can cause injury or property damage Re fer to this manual for correct installation and operational pro cedures For assistance or addi tionalinformati...

Страница 2: ...r for Com bustion and Ventilation pages 4 through 6 9 Do not run firebox where flammable liquids or vapors are used or stored under dusty conditions 10 Do not use this firebox to cook food or burn pap...

Страница 3: ...8 19 3 8 Figure 1 Firebox Front View Built in Nailing Flanges Standoffs Model RUV32 only Louvers Model UV32C only 12 1 2 2 3 4 1 1 2 9 3 4 4 5 8 2 1 2 6 32 3 16 33 11 16 Standoffs Model RUV32 only El...

Страница 4: ...irebox will be located Al low for wall and ceiling clearances see Installation Clearances page 7 2 Everything needed to complete instal lation 3 These models CANNOT be installed in a bedroom or bathro...

Страница 5: ...e outdoors and vents to the outdoors 4 Compare the maximum Btu Hr the space can support with the actual amount of Btu Hr used _____________________Btu Hr maximum the space can support ________________...

Страница 6: ...ng unconfined space The combined spaces must have enough fresh air to supply all appliances in both spaces Figure 5 Ventilation Air from Outdoors Ventilation Air From Outdoors Provide extra fresh air...

Страница 7: ...ional vehicle where curtains furniture clothing or other flammable objects are less than 42 inches from the front top or sides of the firebox in high traffic areas in windy or drafty areas Figure6 Min...

Страница 8: ...binet mantel installation or with built in installation page 10 with model UV32C only To install blower accessory see instruction sheet included with the kit Cabinet Mantel Installation of Blower Acce...

Страница 9: ...pick up log base assembly by burners This could damage burners Only handle base by grates INSTALLING FIREPLACE SCREEN 1 Insert each rod through nine rings lo cated at top of screen 2 Insert first rod...

Страница 10: ...installation includes an approved flexible gas line if allowed by local codes after the manual shutoff valve The flexible gas line must be the last item installed on the gas piping See Connecting to...

Страница 11: ...iginal replacement part s call Fireplace Manufacturers Incorporated s Technical Service Depart ment at 1 888 427 8322 When calling Fireplace Manufacturers Inc have ready your name your address model n...

Страница 12: ...12 105383 UV32C and RUV32 UNVENTED 32 FIREBOX FIREPLACE MANUFACTURERS INC ILLUSTRATED PARTS BREAKDOWN RUV32 5 14 16 16 16 13 15 17 17 17 16 6 1 16 7 16 8 20 12 18 10 19 9 4 2 3 2 16 11 18 18...

Страница 13: ...1 4 101932 02 Side Firebrick 2 5 103207 01 Outer Casing 1 6 103208 01 Outer Shell Base 1 7 103245 01 Firebox Wrapper 1 8 103297 01 Assembly Screen 2 9 103217 01CK Hood 1 10 103773 02CK Front Assembly...

Страница 14: ...14 105383 UV32C and RUV32 UNVENTED 32 FIREBOX FIREPLACE MANUFACTURERS INC ILLUSTRATED PARTS BREAKDOWN UV32C 5 16 16 15 16 17 22 6 1 16 7 16 14 21 13 8 20 12 18 10 19 9 4 2 3 2 16 11 18 18...

Страница 15: ...3207 01 Outer Casing 1 6 103208 01 Outer Shell Base 1 7 103245 01 Firebox Wrapper 1 8 103297 01 Assembly Screen 2 9 103217 01CK Hood 1 10 103773 01CK Front Assembly 1 11 103250 01CK Firebox Bottom 1 1...

Страница 16: ...be installed by a qualified installer in accordance with all local codes and instructions furnished with the unit This warranty does not apply to parts that are not in original condition because of no...

Отзывы: