www.fmiproducts.com
56131L
22
FIREPLACE INSTALLATION
CAUTION: Due to high tem
-
peratures, make sure wires are
not touching upper firebox.
Figure 36 - Removing Louver
Glass
Locating
Holes
Spring
Latch
Figure 35 - Wall Switch Wiring Diagram,
Millivolt Units
Note: If any of the original wire supplied must
be replaced, use type 18 AWG-105 degree C
(25 feet length maximum) or equivalent.
OFF
P
IL
O
T
ON
LO
HI
PI
LOT
E
A
16AI
7
TPTH
TP
TH
Wall Switch
(Supplied)
Route Millivolt Wires
(Supplied) Through Gas
Line Conduit Sleeve
To
Thermopile
V1
SW
SI
TS
IND
V2
L1
D
N
G
P.
Figure 34 - Wall Switch Wiring Diagram,
Electronic Units
Route 24V (Supplied)
Through Electrical Conduit
Bushing
Electrode
Transformer
Plug 120V AC
To Receptacle
18 AWG
Red Wire T
o Gas V
alve
Wall Switch
(Supplied)
Make Connections
with Wirenuts
(Supplied)
Ignition
Control
Module
(Back
View)
(Back
View)
ELECTRICAL HOOKUP FOR
OPTIONAL BLOWER ACCESSORY
Before blower accessory can be operated, ap-
pliance outlet box must be properly connected
to a standard 120 VAC power source. This
must be done when appliance is originally in-
stalled. Refer to
Wiring Diagrams
on page 34.
An outlet box with two receptacles has been
supplied for your convenience and is located
on the lower right side of appliance (see
Figure 37, page 23). The variable speed
controller is mounted on a magnetic base
and may be positioned anywhere within an
accessible distance behind louvered opening
(see Figure 36).
Recommended
Blower Speed
Control Location
OFF
P
IL
O
T
ON
LO
HI
PI
LOT
E
A
16AI
7
TPTH
TP
TH
V1
SW
SI
TS
IND
V2
L1
D
N
G
P.
WALL SWITCH INSTALLATION
Since the (V)DVF36TPNEA/TSTEA series
uses a 24 VAC current supplied from a
transformer mounted on the ignition module
and is prewired for easy connection to a wall
switch (see Figure 34). The (V)DVF36TPNA/
TSTA models use a self generated millivolt
current that allows you to activate the gas
control valve directly without the use of normal
household electricity (see Figure 35). Both
versions are supplied with a wall switch kit
for ready connection and mounting.
WARNING: Do not wire re-
mote wall switch to main power
supply (Standard 120v house
-
hold current).
1. To remove louvers, simultaneously pull
both top end spring latches towards center
of appliance until they are disengaged
from locating holes. Repeat for bottom
spring latches and pull louvers outward.
Reverse procedure to install louvers back
onto appliance (see Figure 36).
2. Connect 18 gauge wires from wall switch
to gas control valve terminals marked
TH and TPTH or to ignition module using
pigtails and wire nut connectors supplied
with appliance.