DETERMINING FRESH-AIR FLOW FOR APPLIANCE LOCATION

Determining if You Have a Confined or Unconfined Space

Use this work sheet to determine if you have a confined or unconfined space.

Space:

  Includes the room in which you will install appliance plus any adjoining rooms with doorless passageways or ventilation grills

between the rooms.

1.

Determine the volume of the space (length x width x height).

Length x Width x Height = _________________ cu. ft. (volume of space)

Example:

 Space size 20 ft. (length) x 16 ft. (width) x 8 ft. (ceiling height) = 2560 cu. ft. (volume of space)

If additional ventilation to adjoining room is supplied with grills or openings, add the volume of these rooms to the total volume of
the space.

2.

Divide the space volume by 50 cubic feet to determine the maximum Btu/Hr the space can support.

_____________ (volume of space) 

÷

 50 cu. ft. = (maximum Btu/Hr the space can support)

Example:

 2560 cu. ft. (volume of space) 

÷

 50 cu. ft. = 51.2 or 51,200 (maximum Btu/Hr the space can support)

3.

Add the Btu/Hr of all fuel burning appliances in the space.

Gas fireplace logs

_____________ Btu/Hr

Gas water heater*

_____________ Btu/Hr

Gas furnace

_____________ Btu/Hr

Vented gas heater

_____________ Btu/Hr

Vent-free heater

_____________ Btu/Hr

Other gas appliances* + _____________ Btu/Hr
Total                            = _____________ Btu/Hr

* Do not include direct-vent gas appliances. Direct-vent draws combustion air from the outdoors and vents to the outdoors.

4.

Compare the maximum Btu/Hr the space can support with the actual amount of Btu/Hr used.

_____________ Btu/Hr (maximum the space can support)

_____________ Btu/Hr (actual amount of Btu/Hr used)

Example:

51,200 Btu/Hr (maximum the space can support)

95,000 Btu/Hr (actual amount of Btu/Hr used)

The space in the above example is a confined space because the actual Btu/Hr used is more than the maximum Btu/Hr the space can support.
You must provide additional fresh air. Your options are as follows:

A. Rework worksheet, adding the space of an adjoining room. If the extra space provides an unconfined space, remove door to adjoin-

ing room or add ventilation grills between rooms. See Ventilation Air From Inside Building, page 6.

B. Vent room directly to the outdoors. See Ventilation Air From Outdoors, page 6.

C. Install a lower Btu/Hr heater, if lower Btu/Hr size makes room unconfined.

If the actual Btu/Hr used is less than the maximum Btu/Hr the space can support, the space is an unconfined space. You will need no
additional fresh air ventilation.

AIR FOR
COMBUSTION AND
VENTILATION

Continued

Example:

Gas water heater

40,000 Btu/Hr

Gas fireplace logs +

55,000 Btu/Hr

Total

=

95,000 Btu/Hr

Continued

 WARNING: If the area in which the appliance may be operated is smaller than that defined as an unconfined

space or if the building is of unusually tight construction, provide adequate combustion and ventilation air by one
of the methods described in the 

National Fuel Gas Code, ANS Z223.1, Section 5.3 or applicable local codes.

Содержание FMLR18

Страница 1: ...onal procedures For assistance or additional information consult a qualified installer service agency or the gas supplier WARNING This appliance is for installation only in a solid fuelburningmasonryo...

Страница 2: ...nd fire box must be cleaned of soot creosote ashes and loose paint by a qualified chimney cleaner Creosote will ignite if highly heated Inspect chimney flue for damage 5 You must operate this log set...

Страница 3: ...s appliance See Acces sories page 19 A wall switch is also available for this appliance Youmustusethemillivoltvalve safety pilot kit to use the wall switch with this appliance See Accessories page 19...

Страница 4: ...helpreduceheatlossinhomes Homeowners weather strip and caulk around windows and doorstokeepthecoldairoutandthewarmair in During heating months home owners want their homes as airtight as possible Whi...

Страница 5: ...aws combustion air from the outdoors and vents to the outdoors 4 Compare the maximum Btu Hr the space can support with the actual amount of Btu Hr used _____________ Btu Hr maximum the space can suppo...

Страница 6: ...adjoining room see op tion 3 Figure 2 Follow the National Fuel Gas Code NFPA 54 ANS Z223 1 Section 5 3 Air for Combustion and Ventilation for required size of ventilation grills or ducts WARNING Rewo...

Страница 7: ...ATIONS Note This vented appliance must be in stalled only in a solid fuel burning fireplace with a working flue and constructed of non combustible material The charts in Figure 4 indicate technical in...

Страница 8: ...items listed below piping check local codes sealant resistant to propane LP gas equipment shutoff valve test gauge connection adjustable crescent wrench or pliers sediment trap tee joint pipe wrench C...

Страница 9: ...all adapter fitting onto the burner inlet fitting using thread sealant on male threads of burner inlet fitting see Figure 9 Adjust to most conve nient position 4 Install the gas connector tube to the...

Страница 10: ...ver ControlKnob and Piezo Ignitor Propane LP Gas Conversion To convert to propane LP gas the burner inlet fitting and pilot orifice must be re placed Thepropane LPburnerinletfittingis supplied with th...

Страница 11: ...igure 17 Installing Grate Pan Material Not Shown Figure 18 Placement of Bottom Logs Changing Pilot Orifice The pilot is provided with a natural gas orifice installed For propane LP gas you must remove...

Страница 12: ...If the burner doesn t ignite within 10 seconds with the match burning turn the shutoff valve OFF and repeat steps 1 through 4 again Note OperationinstructionsforGA9100 Remote Ready Valve Pilot Kit wi...

Страница 13: ...ooting excessively Note It is natural and unavoidable for vented gas log sets to produce moderate levels of carbon soot where flames contact the logs This is especially true with propane LP gas Burner...

Страница 14: ...nd tighten until snug then tighten 1 4 turn more 6 Replace thermocouple 7 Replace control valve 1 Clean burner orifice 2 Contact local natural or propane LP gas company 3 Replace burner orifice 4 Reco...

Страница 15: ...page OBSERVED PROBLEM Log Set produces a clicking ticking noise just after burner is lit or shut off Log Set produces unwanted odors Gas odor even when control knob is in OFF position Gas odor during...

Страница 16: ...16 901261 VENTED NATURAL GAS LOGS ILLUSTRATED PARTS BREAKDOWN FVMR18 FVMR24 3 1 8 6 12 10 11 10 4 2 7 9 5...

Страница 17: ...3 Natural Gas Injector 1 5 901763 02 901763 01 Burner Manifold 1 6 901767 02 901767 01 Burner Pan 1 7 901242 01 901242 01 Damper Clamp Std Assembly 1 8 901232 01 901232 01 Gas Line 12 Aluminum 1 9 901...

Страница 18: ...d under Replacement Parts on page 19 of this manual KEY PART NUMBER FOR NO FMLR18 FMLR24 DESCRIPTION QTY 1 901656 01 901657 01 Bottom Front 1 2 2 901666 01 901667 01 Bottom Front 2 2 3 901619 01 90161...

Страница 19: ...l models Carton of 6 GLOWING EMBERS GA9900 Not Shown For all models Use for firebox decoration only SILICA SAND GA9800 Not Shown For all models Use for firebox decoration only Carton of 6 LAVA ROCK GA...

Страница 20: ...ted to repairing a defective log set will be the responsibility of the owner TOTHEFULLEXTENTALLOWEDBYTHELAWOFTHEJURISDICTIONTHATGOVERNSTHESALEOFTHEPRODUCT THIS EXPRESS WARRANTY EXCLUDES ANY AND ALL OT...

Отзывы: