12
106394
DIRECT-VENT FIREPLACE (NATURAL/PROPANE/LP)
DVFH34, DVFH34P
4.
Connect a section of pipe and extend
up through the hole.
Note:
If an offset is needed to avoid
obstructions, you must support the vent
pipe every 3 feet. Use wall straps for
this purpose (see Figure 20). Whenever
possible, use 45
°
elbows instead of 90
°
elbows. The 45
°
elbow offers less re-
striction to the flow of the flue gases
and intake air.
5.
Place the flashing over the pipe
section(s) extending through the roof.
Secure the base of the flashing to the
roof and framing with roofing nails. Be
sure roofing material overlaps the top
edge of the flashing as shown in Figure
20. There must be a 1" clearance from
the vent pipe to combustible materials.
6.
Continue to add pipe sections until the
height of the vent cap meets the mini-
mum building code requirements de-
scribed in Figure 8 on page 6.
Note
: You
must increase vent height for steep roof
pitches. Nearby trees, adjoining rooflines,
steep pitched roofs, and other similar fac-
tors may cause poor draft or down-draft-
ing in high winds. Increasing the vent
height may solve this problem.
7.
Twist-lock the vent cap onto the last
section of vent pipe and seal outer pipe
connection with high temperature sili-
cone sealant as specified in the second
warning statement on page 7.
Note:
If the vent pipe passes through any
occupied areas above the first floor, including
storage spaces and closets, you must enclose
pipe. You may frame and sheetrock the enclo-
sure with standard construction material. Make
sure and meet the minimum allowable clear-
ances to combustibles. Do not fill any of the
required air spaces with insulation.
Cathedral Ceiling Installation
1.
Remove shingles or other roof cover-
ing as necessary to cut the rectangular
hole for the support box. Mark the out-
line of the cathedral ceiling support box
on the roof sheathing using the locat-
ing hole as a center point.
2.
Cut the hole 1/8" larger than the sup-
port box outline (see Figure 22, page 13).
INSTALLATION FOR
VERTICAL TERMINATION
Note:
Vertical restrictors must be installed
in all vertical installations.
1.
Determine the route your vertical vent-
ing will take. If ceiling joists, roof
rafters, or other framing will obstruct
the venting system, consider an offset
(see Figure 20) to avoid cutting load
bearing members.
Note:
Pay special
attention to these installation instruc-
tions for required clearances (air space)
to combustibles when passing through
ceilings, walls, roofs, enclosures, attic
rafters, etc. Do not pack air spaces with
insulation. Also note maximum verti-
cal rise of the venting system and any
maximum horizontal offset limitations.
Offsets must fall within the parameters
shown in Figure 8 on page 6.
2.
Set the fireplace in desired location.
Drop a plumb line down from the ceil-
ing to the position of the fireplace exit
flue. Mark the center point where the
vent will penetrate the ceiling. Drill a
small locating hole at this point.
Drop a plumb line from the inside of
the roof to the locating hole in the ceil-
ing. Mark the center point where the
vent will penetrate the roof. Drill a
small locating hole at this point.
Flat Ceiling Installation
1.
Cut a 10" square hole in the ceiling us-
ing the locating hole as a center point.
The opening should be framed to
10"x10" (254mm x 254mm) inside di-
mensions, as shown in Figure 12 on
page 9 using framing lumber the same
size as the ceiling joists. If the area
above the ceiling is an insulated ceil-
ing or a room, nail firestop from the
top side. This prevents loose insulation
from falling into the required clearance
space. Otherwise, install firestop below
the framed hole. The firestop should be
installed with no less than three nails
per side (see Figure 21).
2.
Assemble the desired lengths of pipe
and elbows necessary to reach from the
fireplace flue up through the firestop.
All connections must be sealed with
high temperature silicone sealant as
specified in the second warning state-
ment on page 7. Be sure all pipe and
elbow connections are fully twist-
locked (see Figure 11, page 9).
3.
Cut a hole in the roof using the locating
hole as a center point. (Cover any ex-
posed open vent pipes before cutting
hole in roof.) The 10"x10" hole must
be measured on the horizontal; actual
length may be larger depending on the
pitch of the roof. There must be a 1"
clearance from the vent pipe to combus-
tible materials. Frame the opening as
shown in Figure 12, page 9.
Figure 20 - Offset with Wall Strap and
45
°
Elbows
Figure 21 - Installing Firestop
If area above is not a room, install
firestop below framed hole.
If area above is a room, install firestop
above framed hole.
VENTING
INSTALLATION
Continued
45
°
Elbow
Wall Strap
Roof Flashing
Ceiling Firestop