background image

www.fmiproducts.com

125206-01B

10

REQUIREMENTS FOR THE COMMONWEALTH OF 

MASSACHUSETTS

For all side wall horizontally vented gas fueled 

equipment installed in every dwelling, building or 

structure used in whole or in part for residential 

purposes, including those owned or operated by 

the Commonwealth and where the side wall ex-

haust vent termination is less than seven (7) feet 

above finished grade in the area of the venting, 

including but not limited to decks and porches, 

the following requirements shall be satisfied:

INSTALLATION OF CARBON 

MONOXIDE DETECTORS

At the time of installation of the side wall horizon-

tal vented gas fueled equipment, the installing 

plumber or gas fitter shall observe that a hard 

wired carbon monoxide detector with an alarm 

and battery backup is installed on the floor level 

where the gas equipment is to be installed. In 

addition, the installing plumber or gas fitter shall 

observe that a battery operated or hard wired car-

bon monoxide detector with an alarm is installed 

on each additional level of the dwelling, building or 

structure served by the side wall horizontal vented 

gas fueled equipment. It shall be the responsibility 

of the property owner to secure the services of 

qualified licensed professionals for the installation 

of hard wired carbon monoxide detectors.

In the event that the side wall horizontally 

vented gas fueled equipment is installed 

in a crawl space or an attic, the hard wired 

carbon monoxide detector with alarm and 

battery back-up may be installed on the next 

adjacent floor level.

In the event that the requirements of this 

subdivision can not be met at the time of 

completion of installation, the owner shall 

have a period of thirty (30) days to comply with 

the above requirements; provided, however, 

that during said thirty (30) day period, a battery 

operated carbon monoxide detector with an 

alarm shall be installed.

Approved Carbon Monoxide Detectors

Each carbon monoxide detector as required 

in accordance with the above provisions shall 

comply with NFPA 720 and be ANSI/UL 2034 

listed and IAS certified.

SIGNAGE

A metal or plastic identification plate shall be 

permanently mounted to the exterior of the 

building at a minimum height of eight (8) feet 

above grade directly in line with the exhaust 

vent terminal for the horizontally vented gas 

fueled heating appliance or equipment. The 

sign shall read, in print size no less than 1/2" in 

size, "GAS VENT DIRECTLY BELOW. KEEP 

CLEAR OF ALL OBSTRUCTIONS".

INSPECTION

The state or local gas inspector of the side 

wall horizontally vented gas fueled equipment 

shall not approve the installation unless, upon 

inspection, the inspector observes carbon 

monoxide detectors and signage installed in 

accordance with the provisions of 248 CMR 

5.08(2)(a) 1 through 4.

EXEMPTIONS: The following equipment is 

exempt from 248 CMR 5.08(2)(a) 1 through 4:

•  The equipment listed in Chapter 10 entitled 

"Equipment Not Required To Be Vented" 

in the most current edition of NFPA 54 as 

adopted by the Board; and

•  Product Approved  side  wall  horizontally 

vented gas fueled equipment installed in a 

room or structure separate from the dwell-

ing, building or structure used in whole or 

in part for residential purposes.

MANUFACTURER REQUIREMENTS

Gas Equipment Venting System Provided 

When the manufacturer of Product Approved 

side wall horizontally vented gas equipment 

provides a venting system design or venting 

system components with the equipment, the 

instructions provided by the manufacturer for 

installation of the equipment and the venting 

system shall include:

•  Detailed instructions for the installation of 

the venting system design or the venting 

system components; and

•  A complete parts list for the venting system 

design or venting system.

Gas Equipment Venting System Not 

Provided

When the manufacturer of a Product Ap-

proved side wall horizontally vented gas fu-

eled equipment does not provide the parts for 

venting the flue gases, but identifies "special 

venting systems", the following requirements 

shall be satisfied by the manufacturer:

• 

The referenced "special venting system" in-

structions shall be included with the appliance 

or equipment installation instructions; and

•  The "special venting systems" shall be Prod

-

uct Approved by the Board, and the instruc-

tions for that system shall include a parts list 

and detailed installation instructions.

A copy of all installation instructions for all 

Product Approved side wall horizontally 

vented gas fueled equipment, all venting in-

structions, all parts lists for venting instruc-

tions, and/or all venting design instructions 

shall remain with the appliance or equipment 

at the completion of the installation.

f i r e - p a r t s . c o m

Содержание DVF32TMHPN-LS

Страница 1: ...ctrical switch do not use any phone in your building Immediatelycallyourgassupplierfromaneighbor s phone Follow the gas supplier s instructions If you cannot reach your gas supplier call the fire depa...

Страница 2: ...the rating plate A conversion kit is supplied with the fireplace State of Massachusetts The installation must be made by a licensed plumber or gas fitter in the Commonwealth of Massachusetts SAVE THI...

Страница 3: ...of any component part not manufac tured or approved byFMI PRODUCTS LLC in combination with a FMI PRODUCTS LLC fireplace system Proper installation is the most important step in ensuring safe and cont...

Страница 4: ...tural and propane LP gas are odorless An odor making agent is added to the gas The odor helps you detect a gas leak However the odor added to the gas can fade Gas may be present even though no odor ex...

Страница 5: ...fireplace in windy or drafty areas where curtains or other combustible flammable objects can make contact with the fireplace front in high traffic areas 4 Turn fireplace off and let cool before servi...

Страница 6: ...34 3 4 3 BACK VIEW TOP VIEW Left Side Right Side Front Back 24 1115 16 101 2 11 2 11 2 101 2 FRONT VIEW 30 Opening 24 25 RIGHT SIDE 22 5 8 43 1 8 32 Opening 1 7 8 1 7 8 BACK VIEW 39 3 4 26 3 8 3 1 2 3...

Страница 7: ...TS Determine the safest and most efficient loca tion for your FMI PRODUCTS LLC direct vent fireplace Make sure that rafters and wall studs are not in the way of the venting system Choose a location wh...

Страница 8: ...e 5 Minimum Clearances See Thru Shown Combustible Material Drywall 2 x 4 Stud Minimum 1 Clearance from Side Only for See Thru FRAMING Once final location has been determined observing clearances for v...

Страница 9: ...quare Min Figure 12 Rough Opening for Installing Exterior Vent Terminal Vertical Height Depends on Installation 26 3 8 Horizontal Length Depends on Installation 90o Elbow 45o Elbow Figure 13 Vent Open...

Страница 10: ...n line with the exhaust vent terminal for the horizontally vented gas fueled heating appliance or equipment The sign shall read in print size no less than 1 2 in size GAS VENT DIRECTLY BELOW KEEP CLEA...

Страница 11: ...al codes In the USA follow the current National Fuel Gas Fuel Gas Code ANS Z223 1 also known as NFPA 54 These models are approved for use with FMI PRODUCTS LLC Series rigid type direct vent pipe as su...

Страница 12: ...greater than 50 000 36 91 cm in Canada if greater than 100 000 K clearance to a mechanical air supply inlet In Canada 6 ft 1 83m minimum In US 3 ft 91 cm above if within 10 ft 3 m horizontally L clear...

Страница 13: ...ce from fireplace flue outlet to ceiling Add ceiling thickness vertical rise in an attic or second story and allow for sufficient vent height above roof line You may use one or two 90 elbows in this v...

Страница 14: ...des Note When installing in a chase you should insulate the chase as you would the outside walls of your home This is especially im portant in cold climates Minimum clearance between vent pipes and co...

Страница 15: ...bustible exterior wall 8 1 2 diameter hole if non combustible Frame as necessary Figure 17 Vent Pipe Connections Male Slots Female Locking Lugs Rigid Vent Pipe 4 Three types of vent caps are available...

Страница 16: ...unit is tight and does not come loose before unit is nailed to framing Square vent or long vent configuration Vent pipe must be manipulated at outer end to make final connection Manually secure pipe...

Страница 17: ...t to be used with a vertical termination 1 Determine route your vertical venting will take If ceiling joists roof rafters or other framing will obstruct venting system consider an offset see Figure 24...

Страница 18: ...er the same size as ceiling joists If area above ceiling is an insulated ceiling or an attic nail firestop from top side This prevents loose insulation from falling into required clearance space If ar...

Страница 19: ...vent pipe passes through any oc cupied areas above the first floor including storage spaces and closets you must enclose pipe You may frame and sheetrock enclosure with standard construction material...

Страница 20: ...Configuration Using Two 90 Elbows VENTING INSTALLATION Continued Vertical Termination Configurations Figures 29 through 32 show four different configurations for vertical termination These minimum ve...

Страница 21: ...0 feet USA you may need to decrease the input rating by changing the existing burner orifice to a smaller size Reduce input 4 for each 1 000 feet above sea level Check with your local gas company for...

Страница 22: ...ed P58 12 12 Section Double Wall Pipe Galvanized P58 6 6 Section Double Wall Pipe Galvanized VENTING INSTALLATION Continued Number Description PA58 712 Adjustable 7 12 Section Double Wall Pipe Galvani...

Страница 23: ...within an accessible distance behind louvered opening see Figure 35 You may test blower for operation by turning control knob clockwise just until it clicks on which is the full on position Adjust fa...

Страница 24: ...person An equipment shutoff valve has been included in the appliance s gas supply system You may consider installing an extra gas shutoff valve outside appliance s enclosure check with local codes whe...

Страница 25: ...a leak is detected WARNING Improper installa tion adjustment alteration service or maintenance can cause injury or propertydamage Refertothismanu al For assistance or additional infor mation consult a...

Страница 26: ...ght twig which is placed across top of logs B 5 Figure 44 shows the top view of burner and grate 6 Place logs A as shown in Figure 45 7 Place logs B as shown in Figure 46 page 27 Lift end of log A tha...

Страница 27: ...ued PILOT ELECTRODE ASSEMBLY ADJUSTMENT The pilot assembly is factory preset for the proper flame height Alteration to these set tings may have occurred during shipping and handling If this is the cas...

Страница 28: ...r s normal setting is fully open Do not forget to retighten the air shutter screw Figure 52 Burner Removal BURNER REMOVAL CAUTION Beforeproceeding toopenglassdoororhandlelogs make sure entire unit is...

Страница 29: ...s should be alerted to the hazards of high surface tem peratures andtostayawayfrom the appliance to avoid burns or clothingignition Youngchildren should be carefully supervised when they are in the sa...

Страница 30: ...n may result causing property damage per sonal injury or loss of life A This appliance has a pilot which must be lighted by hand When lighting the pi lot follow these instructions exactly B BEFORE LIG...

Страница 31: ...e technician or gas supplier 9 Turn on all electric power to fireplace 10 Turn gas control knob counterclockwise to ON 11 This valve is equipped with a HI LO fea ture Set fireplace input as desired O...

Страница 32: ...cian replace pilot line 7 Replace control valve see Replacement Parts and Ac cessories page 34 8 Tighten thermocouple or replace 1 Check wiring connection Refer to Wiring Diagram page 33 1 Check elect...

Страница 33: ...e pilot or misaligned electrode at pilot 3 No or low gas pressure OBSERVED PROBLEM Whenignitorbuttonispressed there is no spark at pilot TROUBLESHOOTING Continued 1 Checkelectricalconnections and repl...

Страница 34: ...have delayed ignition fireplace will not produce specified heat propane LP gas supply may be low You may feel your gas pressure is too low If so contact your local gas supplier TECHNICAL SERVICE You m...

Страница 35: ...Only Black 01645 REFRACTORY PIECES Front Bottom 25854 Left Right Bottom 25856 Rear 25855 See Thru Only Rear 27374 Peninsula Only Front Bottom Left Right Bottom Rear For Peninsula and See Thru PIEZO I...

Страница 36: ...t and or FMI PRODUCTS LLC who will provide original factory replacement parts Failure to use original factory replacement parts voids this warranty Travel handling transportation diagnostic material l...

Отзывы: