background image

www.fmiproducts.com

54010F

7

Figure 10 - Pipe Connection

LINEAL GAIN

PART NO.

DESCRIPTION

GAIN

36L/R

Fireplace

42"

12-8DM

Pipe Section

10 

5

/

8

"

18-8DM

Pipe Section

16 

5

/

8

"

24-8DM

Pipe Section

23 

5

/

8

"

36-8DM

Pipe Section

34 

5

/

8

"

48-8DM

Pipe Section

46 

5

/

8

"

RT-8DM

Round Termination

7

/

8

"*

RTL-8DM

Round Termination

3

/

4

"*

RTT-8DM

Round Termination 

with Slip Section

7

/

8

" to 

23 

1

/

8

"*

RTTL-8DM

Round Termination 

with Slip Section

3

/

4

" to 

21 

1

/

2

"*

ET-8DM

Square Chase 

Termination

12"*

ETL-8DM

Square Chase with 

Slip Section

7" to 15"*

ETO-8DM

Square Chase  

with Mesh

12"*

ETLO-8DM

Square Chase 

with Mesh and Slip 

Section

12" to 

21 

1

/

2

"*

Hemmed 
Ends 
(Female)

8" Stainless 
Inner Pipe

12 

3

/

8

Galvanized 
Outer Pipe

VENTING INSTALLATION

Continued

CHIMNEY SYSTEM

Chimney Height

Minimum chimney height measured fro 
bottom of fireplace to flue gas outlet-end of 
termination is:
Straight run 

 

14 feet

Run with one elbow set  

15 feet

Run with two elbow sets 

24 feet

An elbow set consists of one starter elbow 
and one return elbow. Uncommon circum-
stances such as neighboring hills, tall trees, 
or strong wind areas can cause downdrafts in 
chimney system. In such cases, going beyond 
minimum recommended height would be 
preferable to provide a better draw.
Maximum height approved for any chimney 
run with this fireplace system is 60 feet as 
measured from fireplace bottom to flue outlet 
end of termination.

Double Wall Chimney System

The FMI PRODUCTS, LLC chimney system 
consists of 12", 18", 24" 36" and 48" snap lock 
double wall pipe segments, planned for maxi-
mum adaptability to individual site require-
ments. Actual lineal gain for each is measured 
after each section is fully connected. Lineal 
gain is the actual measurable length of a part 
after two or more parts are connected. 
Each double wall chimney section consists 
of a galvanized outer pipe, a stainless steal 
inner  flue pipe and a wire spacer. Pipe sec-
tions must be assembled independently as 
chimney is installed. When connecting chim-
ney directly to fireplace, inner flue pipe section 
must be installed first with lanced (female) 
side up (see Figure 10). Outer pipe section 
can then be installed over flue pipe section 

with hemmed (male) end up. Press down on 
each pipe section until lances securely engage 
hem on fireplace starter. The wire will assure 
proper spacing between inner and outer pipe 
sections.
Continue to assemble chimney sections as 
outlined above, making sure both inner and 
outer pipe sections are locked together. 
When installing double wall snap-lock chim-
ney together, it is important to assure the 
joint between chimney sections is locked. 
Check by pulling chimney upward after lock-
ing. Chimney will not come apart if properly 
locked. It is not necessary to add screws to 
keep chimney together. However, if desired, 
use screws per directions provided on page 
8, Figure 11.

Lanced 
Ends 
(Male)

*Lineal Gain for Terminations is measured to 
Flue Gas Outlet Height.

Figure 9 - Air Kit Damper Rod

Air Kit 
Damper 
Rod- 
Closed 
Position

Open 
Position

Lower 
Left 
Side of 
Fireplace 
Opening

Содержание 36L Series

Страница 1: ...eater approved toANS Z21 11 2 standard AFMI PRODUCTS LLC hood must be installed when using a vent free gas log set see Accessories page 16 This wood burning fireplace complies with UL127 CAN ULS S610 M87 standard as a FACTORY BUILT APPLIANCE and is listed and tested by the PFS Cor poration INSTALLER Leave this manual with the appliance CONSUMER Retain this manual for future reference 36 OPEN CORNE...

Страница 2: ...mmablematerialsonornear the appliance Never leave children unat tended when a fire is burning in the fireplace IMPORTANT Check local codes before installing this fireplace This fireplace model is a wood burning fireplace intended and approved for installation in either residential homes or buildings of standard construction This fireplace system requires the utilization of FMI PRODUCTS LLC s 8 dou...

Страница 3: ...ey are burning Use only fire logs that have been evaluated for the application in fireplace and refer to fire log warnings and caution markings on packaging prior to use WARNING Alwaysleaveglass doorsfullyopenedorfullyclosed when operating fireplace WARNING Children and adults should be alerted to the hazardsofhighsurfacetempera tures and to stay away to avoid burns or clothing ignition Young chil...

Страница 4: ...e is even or level with wall Chase Installation type of installation where chimney is enclosed Perpendicular Side Wall applies to minimum clearance between side wall and fireplace opening Nailing Flange extended part on both sides of fireplace face that secures fireplace to wall Termination cap that is placed at end of chimney pipe SELECTING LOCATION To determine the safest and most efficient loca...

Страница 5: ...aterials can be obtained from manufacturer or supplier of noncombustible material The minimum required thickness ofr any material could be obtained by the following formula K factor at 1 thickness required 0 84 For example if the material selected has a K factor of 0 25 such as glass fiber the following formula would apply 0 25 x 1 0 0 30 thickness required 0 84 If hearth extension is to be covere...

Страница 6: ... Perpendicular Side Wall OPTIONAL OUTSIDE AIR KIT Models AK4 or AK4F The installation of an outside air kit should be performed during the rough framing of the fire place due to the nature of it s location Outside combustion air is accessed through and exterior wall AK4 or a vented crawl space AK4F See Figure 8 and Accessories on page 16 Avoid installing outside air eyebrow in areas where inlet op...

Страница 7: ... FMI PRODUCTS LLC chimney system consists of 12 18 24 36 and 48 snap lock double wall pipe segments planned for maxi mum adaptability to individual site require ments Actual lineal gain for each is measured after each section is fully connected Lineal gain is the actual measurable length of a part after two or more parts are connected Each double wall chimney section consists of a galvanized outer...

Страница 8: ...3 4 115 1 2 2 1 64 3 4 120 3 4 2 1 68 1 4 127 1 2 70 130 2 74 1 4 137 1 2 1 2 1 76 3 4 141 1 2 1 2 1 79 3 4 146 3 4 4 Figure 11 Rise and Offset B A Screws Figure 12 Typical Offset Installations WARNING The opening in the collar around the chimney at the top of the fireplace must not be obstructed Neveruseblowninsula tion to fill the chimney enclosure USING CHIMNEY OFFSET To achieve desired offset ...

Страница 9: ...uired clearance between the chimney and the combustible materials When the pipe passes through a framed open ing into a living space above the firestop must be placed onto the ceiling from below as shown in Figure 14 When the pipe passes through a framed opening into an attic space above the firestop must be placed on the attic floor as shown in Figure 15 SUPPORT SECTIONS 12S 8DM The chimney suppo...

Страница 10: ...ich pipe will penetrate roof 2 Determine center point of roof Pitch is the distance the roof drops over a given span usually 12 A 6 12 pitch means that the roof drops 6 for each 12 one measure horizontally down from roof rafters 3 Use roof opening chart Figure 18 to determine correct opening length and flashing required 4 Remove shingles around opening mea sured Cut out this section Figure 17 Typi...

Страница 11: ...n ingsontherooftopflashing Fol low the installation instructions provided with the termination being used RTL 8DM Collar Flashing Underlap Shingles Figure 21 Terminations Overlap Shingles Top and Sides Caulk Attach Bracket Tabs to Outer Pipe 3 places Secure with Screws 5 Add next sections of pipe until end penetrates roof line Check to see that proper clearances are maintained Extend chimney by ad...

Страница 12: ...s important that combustible materials do not overlap the face itself Brick glass tile or other noncombustible materials may overlap the front face provided they do not obstruct louvered slots or any other opening When overlapping with a noncombustible facing material use only noncombustible mortar or adhesive appropriate for the particular installation WARNING A qualified service person must conn...

Страница 13: ...ole with refractory cement or commercial furnace cement Install the gas appliance or cap off gas line if desired CAUTION All gas piping and connections must be tested for leaks after the installation is completed After ensuring that the gas valve is on apply soap and water solution to all connectionsandjoints Bubbles forming show a leak Correct all leaks at once DO NOT USE AN OPEN FLAME FOR LEAK T...

Страница 14: ...s log sets that comply with the Standard for Decorative Gas Appliance for Installa tion in Solid Fuel Burning Fireplace ANS Z21 1 60 can be installed in accordance with the National Fuel Gas Code ANS Z223 1 in this fireplace WARNING When using a decorative vented gas log the damper must be removed or per manently locked in the fully open positionandtheglassdoorsmust be in the fully open position C...

Страница 15: ...LLAR KEEP THIS AREA OPEN Figure 27 Fireplace Collar Opening GLASS DOORS Bi fold glass doors are optional with this fireplace Check with your local distributor for availability To install glass doors refer to installation instructions that are included with kit When fireplace is in operation doors must be fully open or fully closed position only or a fire haz ard may be created see Figure 28 A fire...

Страница 16: ... not overload grate or obstruct required air space beneath it Always keep ashes from building up under grate WARNING Risk of fire Re placegratemadeforusewiththis fireplace only See Replacement Parts CHIMNEY Have your chimney system cleaned and in spected regularly to ensure safe and efficient operation TECHNICAL SERVICE You may have further questions about instal lation operation or troubleshootin...

Страница 17: ...rass GA6052 Antique Brass GA6053 CHIMNEY SUPPORT 12S 10DM STORM COLLAR SC1 Used for RT 8DM and RTL 8DM SC2 Used for RTT 8DM and RTTL 8DM ROOF FLASHING V6F 8DM 0 to 6 12 Pitch V12F 8DM 6 12 to 12 12 Pitch FIRESTOP SPACER FS 8DM ANTI DRAFT SHIELD Round Top Termination Only ADS 8DM SQUARE TOP TERMINATION ET 8DM ETO 8DM SQUARE TOP TERMINATION WITH SLIP SECTION ETL 8DM ETLO 8DM ROUND TOP TERMINATION RT...

Страница 18: ...ts com 54010F 18 HIGHT TEMPERATURE TOUCH UP PAINT 106583 01 Not Shown ACCESSORIES Continued OUTSIDE AIR KIT FOR SIDE WALL INSTALLATION AK4F FAN KIT VCBK4C Left VCBK4R Right OUTSIDE AIR KIT FOR FLOOR INSTALLATION AK4 ...

Страница 19: ...___________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ __________________________________...

Страница 20: ...54010 Rev F 09 09 2701 S Harbor Blvd Santa Ana CA 92704 1 866 328 4537 www fmiproducts com ...

Отзывы: