![FLYGT FPC100 Скачать руководство пользователя страница 4](http://html1.mh-extra.com/html/flygt/fpc100/fpc100_installation-and-user-manual_2311481004.webp)
QUICK SET-UP OF FPC100
Quick set-up of FPC100
The purpose with the quick set-up is to initiate the stop function. FPC100 stops the pump
when the water level has dropped to such a low level that the pump begins to draw air
(snore). At air intake the pump motor power drops and below a manually set power-level
FPC100 stops the pump.
Pump power
Manually set power level
Full load power
Stop level
“Snore power”
Time
Stop at underpower
If FPC100 has been used previously, some parameters could have been changed and
locked. Then go to
Complete set-up
(page 11) that describes a complete set-up.
The prerequisite for quick set-up is that the pump is installed to a control panel including
FPC100. The control panel should preferably also include a Hand-0-Auto switch for the
pump.
In event of an alarm during the set-up, see
PROTECTION AND ALARM
(page 19).
Auto-set at normal pumping (pumping water without drawing air)
1. Check that the amount of water is enough for pumping about 30 seconds without
drawing air.
2. Turn on the supply voltage to FPC100 and set the Hand-0-Auto switch in the Auto-
position. The pump shall now be pumping water without drawing air. If the pump
doesn’t start, press START/RESET.
3. When the pump is working steadily, press AUTOSET until “SEt” is shown on the
display. The power level for stop is now set.
The stop function is now initiated and FPC100 controls the pump. Adjustments can be
made according to
DETAILED SETTINGS
(page 11).
Auto-set at snoring (pumping a mix of air and water)
1. Set the Hand-0-Auto switch in the 0-position and turn on the supply voltage to
FPC100.
2. Step with NEXT to window 13 and press “–“ so that the line is shown at the bottom of
the display ( _ ). Press ENTER to verify. FPC100 is now prepared for Auto-set at
snoring.
3. Set the Hand-0-Auto switch in the Auto-position to start the pump. If necessary, press
START/RESET.
4. Run the pump until it starts to snore.
5. Press AUTOSET until “SEt” is shown on the display. The power level for stop is now
set, hence stopping the pump due to the snoring.
The stop function is now initiated and FPC100 controls the pump. Adjustments can be
made according to
DETAILED SETTINGS
(page 11).