FLYGT FPC100 Скачать руководство пользователя страница 23

TROUBLESHOOTING

Troubleshooting

Window 00 shows F1-F5, LU or OU

Fault handling according to 

PROTECTION AND ALARM

 (page 19).

Impossible to do Auto-set

Auto-set is disconnected during the Start-up delay period or if an alarm indication is
present.

The pump starts and stops too often or seldom, or the level in the pit is too low or too high

Change the settings in window 21 and window 22 according to 

Start conditions and pause

time adjustment

 (page 14).

The pump stops although it is not snoring

Check the stop level value in window 11. This value is probably too high in relation to
measured power in window 04. The pump operating power may have decreased due to
worn out hydraulic parts. Perform a new AUTOSET according to 

DETAILED SETTINGS

(page 11) or change hydraulic parts if necessary. If hydraulic parts are changed, a new
AUTOSET has to be performed.

The pump doesn’t stop when snoring

Check the stop level value in window 11. This value is probably too low in relation to
measured power in window 04. Perform a new AUTOSET according to 

DETAILED

SETTINGS

 (page 11).

The value in window 04 increases when the pump starts to snore

Check that the current transformer(s) is linked to the phase connected to terminal 9 (L1).

“oor” (out of range) is shown on the display

This means that the value is too big to be shown on the display. The values in windows 06,
07 and 08 can be set to 0 by pressing – and + simultaneously for three seconds.

FPC100 unit is damaged or “dead“

• Component failure in FPC100. FPC100 has to be changed.
• Power supply to FPC100 (L2 or/and L3) is interrupted. Check wiring.

TROUBLESHOOTING

Single pump controller Installation and user manual for FPC100

21

Содержание FPC100

Страница 1: ...Single pump controller Installation and user manual for FPC100...

Страница 2: ......

Страница 3: ...NT PANEL LAYOUT AND FUNCTION KEYS 9 Front panel layout and function keys 9 DISPLAY SYMBOLS AND UNITS 10 Display symbols and units 10 DETAILED SETTINGS 11 General 11 Lock and unlock menu settings 11 Re...

Страница 4: ...y voltage to FPC100 and set the Hand 0 Auto switch in the Auto position The pump shall now be pumping water without drawing air If the pump doesn t start press START RESET 3 When the pump is working s...

Страница 5: ...lsiasi lavoro controllare che la centralina degli automatismi sia staccata dalla rete di alimentazione elettrica e che non sia sotto tensione Controleer voordat u begint te werken of de schakelkast ge...

Страница 6: ...l Xylem sales office Keep the packing It can be needed for return of the delivery or in case of inspection at damage The housing of the FPC100 is made of recyclable plastic type PC ABS The circuit boa...

Страница 7: ...be found in TECHNICAL SPECIFICATIONS page 22 PE L1 L2 L3 N M 3 Max 240VAC Hand I Dig in Temp Alarm Pump 1 3 4 5 7 8 6 9 L1 11 L2 L3 13 2 Supply Auto 0 Alarm Auto set Reset High level Thermistor PTC o...

Страница 8: ...gh the current transformer core an additional number of turns to put the available transformer capacity to full use The formula below can be used to determine how many turns the phase conductor of the...

Страница 9: ...oice and adaptation of current transformer page 6 Connect the CT secondary winding to terminals 1 and 2 Note The CT must be linked to the phase connected to terminal 9 L1 Supply voltage connection Con...

Страница 10: ...enable immediate start of the pump 2 External Reset 3 External Auto set Terminal 5 connection e g temperature supervision Terminals 4 and 5 can be used for temperature supervision a thermal contact o...

Страница 11: ...10 Key Function RESET START Resets a latched alarm Starts pump motor AUTO SET Sets the stop level when pressed for 3 s NEXT Proceeds to the next window Decreases the displayed value For fast decrement...

Страница 12: ...07 is 13467 hours Window number 07 is displayed for 2 sec and then 13467 is displayed for 2 sec Symbol Meaning Alarm Time value Parameter lock Unit Meaning V Volt mA Milli ampere m Minutes S Seconds P...

Страница 13: ...9 to 369 and confirm with ENTER A padlock is shown indicating access only to windows 00 09 Re entering value 369 and confirming with ENTER gives access to all windows Returning to default settings If...

Страница 14: ...dlock and get access to parameter settings windows 11 99 4 Clear the present stop level by pressing AUTOSET until SEt is shown on the display The stop level is hence set to 0 since the pump is off 5 S...

Страница 15: ...noring 6 Set the Hand 0 Auto switch in the Auto position to start the pump If necessary press START RESET 7 Run the pump until it starts to snore 8 Press AUTOSET until SEt is shown on the display The...

Страница 16: ...use Calculation of pause time is based on previous pumping and pause times and is controlled by the two parameters level setting window 21 and maximum pause time window 22 The parameters can be adjust...

Страница 17: ...ump start Standard window during pause Symbol is flashing together with m or S 720 15 min 900 0 s 02 Pumping time since the latest pump start Standard window when pumping Symbol is flashing together w...

Страница 18: ...999 0 11 Stop level power in 0 125 0 12 Snore margin in 0 125 10 13 Type of Auto Set AUTOSET is pressed at normal pumping when pump doesn t snore AUTOSET is pressed at snoring or dry running _ or _ 21...

Страница 19: ...nore detection until the pump is stopped 1 90 s 2 s 25 Pump starts when pause time is finished OFF means start only on high level set window 53 to 1 on OFF on 31 Terminal 5 supervision e g temperature...

Страница 20: ...normally open nc no nc 53 Digital input for closing contact 1 High level switch gives immediate start of the pump 2 External Reset 3 External Auto set 1 2 3 1 61 Measured current on terminals 1 and 2...

Страница 21: ...the FPC100 Action Switch off the main supply Disconnected and swap positions of phases L2 and L3 Phase asymmetry F2 An F2 alarm is generated when the phase asymmetry on the supply voltage exceeds the...

Страница 22: ...sed with any device using a voltage free opening contact such as a motor protection unit Terminal 5 supervision is activated when window 31 is set to on and the alarm is latched if window 32 is set to...

Страница 23: ...ED SETTINGS page 11 or change hydraulic parts if necessary If hydraulic parts are changed a new AUTOSET has to be performed The pump doesn t stop when snoring Check the stop level value in window 11 T...

Страница 24: ...AC Pilot duty AC12 Fuse Max 10 A Terminal wire size Use 75 C copper Cu wire only 0 2 4 mm2 single core 0 2 2 5 mm2 flexible core stripped length 8 mm Terminal tightening torque 5 7 lbs in 0 56 0 79 Nm...

Страница 25: ...s A limits for radio noise emissions from digital apparatus as set out in the Canadian interference Causing Equipment Regulations Part numbers FPC100 including current transformer CT Pump main voltage...

Страница 26: ...Contains Dimension Parts Screws 4 pcs TECHNICAL SPECIFICATIONS 24 Single pump controller Installation and user manual for FPC100...

Страница 27: ......

Страница 28: ...ldings factories and farms In more than 150 countries we have strong long standing relationships with customers who know us for our powerful combination of leading product brands and applications expe...

Отзывы: