Window
Function
Value/Range
Default setting
Own settings and
comments
22
Maximum pause
time. Symbol
is displayed.
If the calculated
pause time is longer
than the Maximum
pause time, the
pump will start after
the Maximum pause
time.
0–900 s
15–720 min
600 s
23
Start-up delay.
Symbol
is displayed.
This is the time from
pump start until
snore detection is
activated.
1–170 s
5 s
24
Stop delay. Symbol
is displayed.
This is the time from
snore detection until
the pump is stopped.
1–90 s
2 s
25
Pump starts when
pause time is
finished.
“OFF” means start
only on high level
(set window 53 to 1)
on / OFF
on
31
Terminal 5
supervision, e.g.
temperature
supervision.
on / OFF
OFF
32
Terminal 5 alarm
latched “on” or not
latched “OFF”.
Can only be used
when window 31 is
“on”.
on / OFF
OFF
41
Permitted
phase
voltage asymmetry
level.
Pressing “–” when the
window shows 5 %
turns off the
supervision (OFF).
OFF/5–50 %
10 %
42
Phase voltage
asymmetry alarm
latched. Can only be
used when window
41 is set between
5-50%.
on / OFF
OFF
DETAILED SETTINGS
Single pump controller Installation and user manual for FPC100
17