9 PROFINET IO
The PROFINET IO maps the object temperature, internal temperature and the status of the pyrometer via
PROFINET IO. Furthermore, PROFINET IO allows you to change a subset of sensor parameters in data exchange
mode. In the initialization phase, the PROFINET module determines the physical structure of the node and creates
a local process image with the pyrometer.
The diagnostics concept is based on channel specific diagnostic messages which are mapped to the respective
alarms. Coding standard is according to IEC 61158 PROFINET IO.
Specification:
Type:
PROFINET IO
Conformance class:
A
Real-Time class:
1 (RT) and the Real-Time class UDP
I/O update cycle time
1 ms
Configurable substitute value behavior in the event of error/failure
9.1 Configuration
The PROFINET IO takes over the task of the I/O device in PROFINET IO. Selecting the I/O module for the process
data exchange and defining the time pattern happens during the I/O controller configuration.
Under PROFINET IO, the device manufacturer describes the device features in a GSD file, which is XML
(Extensible Markup Language) coded and supplied to the end-user.
GSDML-V2.25-FlukeProcessInstruments-Endurance-20160616.xml
The I/O device is configured in accordance with the physical arrangement of the node (slot oriented).
Module slot 0 contains the PROFINET in its function as station substitute. It does not deliver process data itself,
but provides the parameters required to perform communication settings of the I/O device (e.g. update cycle time).
Slot 1 (Input/output module) reflects the physical arrangement of the pyrometer, that deliver a part of the process
and diagnostics data. All specific information on the relevant module is contained in the associated GSD file.
9.2 Parameters
The parameter setting of a connected pyrometer happens via “record data” sets. The I/O module allows diagnostics
message to be locked or released. Once all parameter settings are performed, the I/O device signals that it is
ready to send cyclic productive data.
Certain pyrometer characteristics are parameterizable during the configuration. The parameters of the pyrometer
substitute are used to set the overall settings of the PROFINET I/O node. Some of the setting are used in the
module as default settings and can be optionally overwritten within the module configuration.