DTX Series CableAnalyzer
Technical Reference Handbook
10-2
Diagnosing Loss/Length Test Failures
Table 10-2 describes some typical causes of fiber test
failures.
Table 10-2. Diagnosing Loss/Length Test Failures
Loss measurement gives FAIL result
•
There is one or more dirty, damaged, misaligned, or unseated connections in the cabling. Check all connections and
clean all fiber endfaces, then retest. The tester’s VFL can reveal damaged connectors and other faults. See Chapter 8 for
details. An OTDR, such as the Fluke Networks OF-500 OptiFiber
®
Certifying OTDR, can help you locate faults not
revealed with the VFL.
•
There is a kink or sharp bend in a test reference cord or the fiber under test. Use the VFL to reveal these faults.
•
A test reference cord is broken.
•
The number of adapters or splices on the Fiber Setup menu is too low (for standards that use a calculated loss value).
•
The wrong fiber type is selected on the Fiber Setup menu.
•
The reference is incorrect. Set the reference again using the same test reference cords to be used for testing.
•
For multimode fiber, the wrong mandrel size was used for testing. Smaller mandrels create tighter bends in the fiber,
resulting in more loss.
•
A test reference cord or fiber segment has the wrong core size. An OTDR is useful for locating mismatched fibers.
•
The cabling has a bad fusion or mechanical splice or a sharp bend. Use the visual fault locator to reveal these faults.
•
The test reference cords have PC or UPC connectors, but the link being tested has APC connectors.
•
The fibers are connected to the wrong ports on the tester, or are swapped at one end of the cabling.
Содержание DTX-1800
Страница 4: ......
Страница 18: ...DTX Series CableAnalyzer Technical Reference Handbook xiv ...
Страница 40: ...DTX Series CableAnalyzer Technical Reference Handbook 1 14 amd30f eps Figure 1 3 Smart Remote Features ...
Страница 43: ...Getting Acquainted Basic Features 1 17 1 amd124f eps Figure 1 4 Charging and Removing the Battery ...
Страница 132: ...DTX Series CableAnalyzer Technical Reference Handbook 4 8 ...
Страница 156: ...DTX Series CableAnalyzer Technical Reference Handbook 6 12 amd100f eps Figure 6 4 Interpreting HDTDR Plots ...
Страница 158: ...DTX Series CableAnalyzer Technical Reference Handbook 6 14 ...
Страница 190: ...DTX Series CableAnalyzer Technical Reference Handbook 7 32 amd125f eps Figure 7 18 Typical OTDR Trace Features ...
Страница 264: ...DTX Series CableAnalyzer Technical Reference Handbook 8 56 amd56f eps Figure 8 28 Using FindFiber in Loopback Mode ...
Страница 270: ...DTX Series CableAnalyzer Technical Reference Handbook 8 62 ...
Страница 274: ...DTX Series CableAnalyzer Technical Reference Handbook 9 4 amd23f eps Figure 9 2 Using the Visual Fault Locator ...
Страница 284: ...DTX Series CableAnalyzer Technical Reference Handbook 10 10 ...
Страница 291: ...Verifying Network Service Verifying Network Connectivity 11 7 11 amd17f eps Figure 11 3 Network Test Connections ...
Страница 304: ...DTX Series CableAnalyzer Technical Reference Handbook 11 20 ...
Страница 372: ...DTX Series CableAnalyzer Technical Reference Handbook A 8 ...
Страница 374: ...DTX Series CableAnalyzer Technical Reference Handbook B 2 ...