SETUP VARIABLES OF THE F133-P
PDU
ADDRESS
REGISTER VARIABLE
TOTAL
NO.
REGISTERS
R/W
TYPE
VALUE / REMARKS
[d] 32
[h] 0x020
40033
unit
1
r/w
uint16 0=none
1=L
2= m
3
3=kg
4= lb
5=GAL
6= USGAL
7=bbl
[d] 33
[h] 0x021
40034
decimals
1
r/w
uint16 0…3
[d] 34
[h] 0x022
40035
K-factor
2
r/w
uint32 1...9999999
Representation: 0.000010…9999999
depending on variable: decimals K-factor.
[d] 37
[h] 0x025
40038
decimals K-factor
1
r/w
uint16 0…6
[d] 218
[h] 0x0DA
40219
batch maximum
2
r/w
uint32 0…9999999
[d] 1078
[h] 0x436
41079
batch total
3
r/w
uint48 0…99999999999999
Representation: 0.001…9999999
[d] 203
[h] 0x0CB
40204
batch counter
2
r/w
uint16 0…9999999, Representation: counts
PDU
ADDRESS
REGISTER VARIABLE
FLOW RATE
NO.
REGISTERS
R/W
TYPE
VALUE / REMARKS
[d] 48
[h] 0x030
40049
unit
1
r/w
uint16 0=mL
1=L
2= M
3
3=mg
4=g
5=kg
6=ton
7=GAL
8=bbl
9=lb
10=cf
11=rev
12=none
13=scf
14=NM
3
15=NL
16=P
[d] 49
[h] 0x031
40050
time unit
1
r/w
uint16 0=/sec
1=/min
2=/hour
3=/day
[d] 50
[h] 0x032
40051
decimals
1
r/w
uint16 0…3
[d] 51
[h] 0x033
40052
K-factor
2
r/w
uint32 1...9999999
Representation: 0.000010…9999999
depending on variable: decimals K-factor.
[d] 54
[h] 0x036
40055
decimals K-factor
1
r/w
uint16 0…6
[d] 55
[h] 0x037
40056
calculation
1
r/w
uint16 per 1 – 255 pulses
[d] 56
[h] 0x0038
40057
cut-off time
1
r/w
uint16 0.1 – 999.9 seconds
[d] 234
[h] 0x0EA
40235
alarm low
2
r/w
uint32 0.001 – 9999999 unit / time unit
[d] 237
[h] 0x0ED
40238
alarm high
2
r/w
uint32 0.001 – 9999999 unit / time unit
[d] 205
[h] 0x0CD
40206
alarm delay
1
r/w
uint16 0.1 – 999.9 seconds
PDU
ADDRESS
REGISTER VARIABLE
DISPLAY
NO.
REGISTERS
R/W
TYPE
VALUE / REMARKS
[d] 67
[h] 0x043
40068
backlight brightness
1
r/w
uint16 0=off
1=20%
2=40%
3=60%
4=80%
5=100%
[d] 110
[h] 0x06E
40111
backlight alarm
1
r/w
uint16 0=off
1=on
2=flash
PDU
ADDRESS
REGISTER VARIABLE
POWER MANAGEMENT
NO.
REGISTERS
R/W
TYPE
VALUE / REMARKS
[d] 80
[h] 0x050
40081
LCD update time
1
r/w
uint16 0=fast
1=1sec
2=3sec
3=15sec
4=30sec
5=off
[d] 81
[h] 0x051
40082
battery mode
1
r/w
uint16 0=operational 1=shelf
PDU
ADDRESS
REGISTER VARIABLE
FLOWMETER
NO.
REGISTERS
R/W
TYPE
VALUE / REMARKS
[d] 96
[h] 0x060
40097
flowmeter signal
1
r/w
uint16 0=NPN
1=NPN LP
2=Reed
3=Reed LP
4=PNP
5=PNP LP
6=NAMUR
7=coil hi
8= coil lo
9=act 8.1V
10= act 12 V
11=act 24V