Page 14
FW_F130P_v1702_02_EN
3.1.7
EXPLANATION OF SETUP-MENU 6 - FLOWMETER
With this setting the type of flowmeter output is selected. The settings with LP (low-pass) filter are
used to apply a build-in noise reduction. Selections "active pulse" offer a detection level of 50% of
the supply voltage.
6
FLOWMETER
61
SIGNAL
TYPE OF SIGNAL
EXPLANATION
RESISTANCE
FREQ. / mV
REMARK
NPN
NPN input
100 kΩ pull-up
max.6 kHz.
(open collector)
NPN - LP
NPN with low pass filter
100 kΩ pull-up
max.1.2 kHz.
(open collector)
less sensitive
REED
Reed-switch input
1 MΩ pull-up
max.1.2 kHz.
REED - LP
Reed-with low pass filter
1 MΩ pull-up
max.120 Hz.
Less sensitive
PNP
PNP input
100 kΩ pull-down
max.6 kHz.
PNP - LP
PNP with low pass filter 100 kΩ pull-down
max 1.2 kHz.
Less sensitive
NAMUR
NAMUR input
820 Ω pull-down
max.4 kHz.
External power
required
COIL-HI
High sensitive coil input
-
min. 20 mV
pp
Sensitive for
interference!
COIL-HI (option ZF)
min. 10 mV
pp
COIL-HI (option ZG)
min. 5 mV
pp
COIL LO
Low sensitive coil input
-
min. 80 mV
pp
Normal sensitivity
8-1 DC
Active pulse input
detection level 8.2V DC
3.9 kΩ
max.10KHz.
External power
required
12 DC
Active pulse input
detection level 12V DC
4 kΩ
max.10KHz.
External power
required
24 DC
Active pulse input
detection level 24V DC
3 kΩ
max.10KHz.
External power
required
3.1.8
EXPLANATION OF SETUP-MENU 7 - RELAY OUTPUT
Two control outputs are available to control relays or valves. Relay 2 can also be used as pulse
output according the batch total (actual) or accumulated total.
7
RELAYS
71
RELAYS
This submenu is used to set the function of related output.
1-Step: The F130-P is used for one-stage batch control while R2 is
used as a scaled pulse output.
2-Step: The F130-P is used for two-stage batch control.
72
PRECLOSE
According to the setting 71 - 2-step, relay two will be used to control a
second valve for the batch process. If the product is batched in two
steps, the switch-off-moment for relay 2 has to be set. The switch
moment is based on the remaining quantity before the end of batch.
If preclose is set to zero, relay 2 will switch simultaneously with relay 1.
The settings: width, decimals, amount and pulse are only valid when
relay 2 is used as a scaled pulse output. A scaled pulse output is used
to indicate that the batch or accumulated total has increased with the
value as set in the setup 75.