Page 30 

FW_F130P_v1702_02_EN 

Serial number and year of production 

This information can be looked-up in the setup menu: Others. 

 

Fig. 23: Example serial number (typical) 

 

Label information pulse input type 

– F1..P-XI (inside and outside the enclosure) 

 

 

 

Fig. 24: Label information - Intrinsically safe application (typical) 

 

 
 

 

Содержание F130-P

Страница 1: ...meter pulse Namur and coil External controls start and stop Digital outputs two control outputs for two stage control or one control output and pulse output Options Intrinsically safe Modbus communica...

Страница 2: ...Page 2 FW_F130P_v1702_02_EN...

Страница 3: ...the general waste system or into a landfill At the end of its life equipment shall be disposed of according to the local regulations regarding waste of the electrical and the electronic equipment Plea...

Страница 4: ...30 P or connected instruments A caution indicates actions or procedures which if not performed correctly may lead to personal injury or incorrect functioning of the F130 P or connected instruments A n...

Страница 5: ...Relay output 14 3 1 9 Explanation of SETUP menu 8 Communication 15 3 1 10 Explanation of SETUP menu 9 Others 15 4 INSTALLATION 16 4 1 General directions 16 4 2 installation surrounding conditions 16...

Страница 6: ...al application Configuration of the F130 P The F130 P is designed for use in many types of applications For that reason a setup menu is available to program the F130 P according to your specific requi...

Страница 7: ...ct the total and the accumulated total The STOP key is also used to select a digit or an option after the PROG ENTER key has been pressed read chapter 3 2 2 OPERATOR INFORMATION AND FUNCTIONS In gener...

Страница 8: ...e the batch process cannot be resumed Fig 6 Process paused typical Clear batch total The value for total can be reset To do so select Total and press PROG followed by STOP STOP After pressing the STOP...

Страница 9: ...ttings may have an influence on the operation It is possible to prevent access to the SETUP menu with a password A password may be required to enter the SETUP menu Without this password access to SETU...

Страница 10: ...previous submenu The submenu UNIT shows 4 Press the STOP key again to go to the previous submenu The main menu PRESET shows This is normal behavior because the submenu UNIT is the first submenu of th...

Страница 11: ...h max 0000000 9999999 2 OVERRUN 21 overrun disable enable 22 time 0 1 999 9 seconds 3 ALARM 31 no flow disable enable 32 time 0 1 999 9 seconds 4 DISPLAY 41 display increase decrease 42 light 0 off 20...

Страница 12: ...re accurate operation of the system Example 1 Calculating the K Factor The flowmeter generates 2 4813 pulses per liter and the selected unit is m3 A cubic meter consists of 1000 liter which gives 2 48...

Страница 13: ...larm When the alarm condition is still valid after the delay time an alarm is given 3 1 5 EXPLANATION OF SETUP MENU 4 DISPLAY 4 DISPLAY 41 DISPLAY This setting is used to set the behavior of the count...

Страница 14: ...8 2V DC 3 9 k max 10KHz External power required 12 DC Active pulse input detection level 12V DC 4 k max 10KHz External power required 24 DC Active pulse input detection level 24V DC 3 k max 10KHz Exte...

Страница 15: ...or the cyber security omissions or errors in the communication safety To maintain a secure operation automation and control it is the sole responsibility of the owner to install and manage the appropr...

Страница 16: ...en the housing cover is removed or the panel cabinet has been opened danger from electrical shock The housing may only be opened by trained persons authorized by the operator of the facility Take care...

Страница 17: ...mm 30mm M20 x 1 5 M16 x 1 5 M16 x 1 5 30mm 30mm M20 x 1 5 M20 x 1 5 M20 x 1 5 25mm 25mm 1 2 NPT 0 9 3x 1 2 NPT 0 12 0 12 HA HM HN HO HP HT HU 6 x M12 12mm 12mm 24mm 24mm 36mm 36mm 14mm 17mm 115 mm 4 5...

Страница 18: ...120 mm 4 72 HD HK HK back box flat bottom HE HF HG HH D 12mm 12mm 12mm 24mm 24mm 36mm 36mm 14mm 17mm 22 5mm 30mm 30mm D 16mm D 20mm 0 9 D 22mm 0 866 22 5mm 25mm 25mm D 20mm D 20mm D 16mm HC 75 mm 2 9...

Страница 19: ...hat came with a power module type PM 110V 230V AC or type PD PF with an option OR the relays can handle 110V 230V AC shall be connected to the Protective Earth PE stud which is installed in the metal...

Страница 20: ...screws that attach the cover to the back panel Type PM 110 230V AC The PE connection in the metal back panel is made with a serrated washer a terminal a washer and a screw The PE connection to the me...

Страница 21: ...C GRP ENCLOSURE The PE connection The F130 P in a GRP enclosure meets the requirements of class 2 double insulated Therefore the incoming PE wire is terminated with an insulating end cap Type PM 110 2...

Страница 22: ...influence the battery life time It is strongly advised to use a zero power pickup such as a coil or reed switch when operating without external power It is possible to use some low power NPN or PNP ou...

Страница 23: ...4V DC 18Vin AC 26Vin DC Type PF Power supply in 15 24V AC 20 30V DC Switch location typical Sensor Vout selection Sensor supply out A 1 2 3 4 int off off Coil 1 2V DC 1mA Reed 3V DC 1mA ext on on off...

Страница 24: ...signal according to the functions R1 and R2 is available with this option Max driving capacity 50mA 24V per output Requires power supply type PD PF PM Fig 12 Terminal connections Active output typical...

Страница 25: ...mmon ground terminal 09 unless earthed at the sensor itself The maximum input frequency is approximately 10 kHz depending on the type of signal The input signal type has to be selected in the flowmete...

Страница 26: ...reliable pulse detection the pulse amplitude has to go above 1 2V Signal setting PNP LP employs a low pass signal noise filter which limits the maximum input frequency read chapter 3 A sensor supply...

Страница 27: ...signal The standard F130 P is not able to power the Namur sensor as an external power supply for the sensor is required However a 8 2V sensor supply voltage terminal 11 can be provided with power sup...

Страница 28: ...s Full serial communications and computer control in accordance with RS232 length of cable max 15 meters or RS485 length of cable max 1200 meters is possible When using the RS232 communication option...

Страница 29: ...ith IEC 60529 suitable cable entries and blanking elements must be used and correctly installed For enclosures and windows with a high surface resistance potential charging hazard exists Do not rub th...

Страница 30: ...of production This information can be looked up in the setup menu Others Fig 23 Example serial number typical Label information pulse input type F1 P XI inside and outside the enclosure Fig 24 Label...

Страница 31: ...nd 1 option PD The maximum values for any of those circuits are those as defined for group IIB IIIC No other active external Intrinsically safe circuits may be connected to the indicator with exceptio...

Страница 32: ...fe If applicable mind the battery power 2 Open the F130 P and carefully remove the cable connectors and the protective cover 3 Find and set the switches and select the Vout as required 4 Close the pro...

Страница 33: ...Page 33 FW_F130P_v1702_02_EN 5 2 CONFIGURATION EXAMPLES Fig 27 F130 P OT PC PX XI Battery powered IIB IIC IIIC...

Страница 34: ...Page 34 FW_F130P_v1702_02_EN Fig 28 F130 P CT OT PX XI External power supply IIB IIC IIIC...

Страница 35: ...t care to prevent a short circuit and damage 4 Do not recharge crush disassemble incinerate heat above its rated temperature or expose the contents to water 5 Dispose of the battery in accordance with...

Страница 36: ...P inputs consume more energy than coil inputs Input frequency the higher the frequency the shorter the battery life time Display update fast display update uses significantly more power Pulse output a...

Страница 37: ...E Type HF Type HG Type HJ Type HH Type HK Dimensions 130 x 120 x 75mm 5 10 x 4 72 x 2 95 LxHxD IP67 TYPE 4 X Drilling 2x PG9 1x M20 Drilling 2x NPT Drilling 2x M16 1x M20 Drilling 1x M20 Drilling 2x M...

Страница 38: ...1 ATEX IECEx EN IEC 60079 0 EN IEC 60079 11 RoHS EN 50581 IP NEMA EN 60529 NEMA 250 INPUT Flowmeter Type P npn npn lp reed reed lp pnp pnp lp namur coil hi coil lo 8 1 DC 12 DC 24 DC Frequency Minimu...

Страница 39: ...Shown information preset value running batch total or remaining quantity total and accumulated total number of completed batches Preset Total Digits 7 digits Unit L m3 GAL USGAL kg lb bbl no unit Dec...

Страница 40: ...does not function Check amount pulse per x quantity is the value programmed reasonable and will the maximum output be under 20Hz width is the external device able to recognize the selected pulse width...

Страница 41: ...ase read the Fluidwell General Modbus Communication Protocol and Modbus troubleshooting guide that are available through our website or your distributor Runtime variables PDU ADDRESS REGISTER VARIABLE...

Страница 42: ...BLE DISPLAY NO REGISTERS R W TYPE VALUE REMARKS d 195 h 0x0C3 40196 display 1 r w uint16 0 increase 1 decrease d 67 h 0x043 40068 backlight brightness 1 r w uint16 0 off 1 20 2 40 3 60 4 80 5 100 PDU...

Страница 43: ...DDRESS REGISTER VARIABLE NO REGISTERS R W TYPE VALUE REMARKS d 223 h 0x0DF 40224 batch mode 1 r uint16 Bitfiel d 0 idle 1 running Bitfiel d 2 paused 4 finished Bitfiel d 8 in overrun d 154 h 0x09A 401...

Страница 44: ...Page 44 FW_F130P_v1702_02_EN DECLARATION OF CONFORMITY...

Страница 45: ...6 hardware version 4 intrinsic safety 29 Intrinsic safety 29 Intrinsically Safe options 32 IP classification 16 Low battery alarm 8 maintenance 36 manual version 4 namur signal 27 operational 7 9 10...

Страница 46: ...output typical 25 Fig 15 Terminal connections Coil signal input typical 25 Fig 16 Terminal connections NPN signal input typical 26 Fig 17 Terminal connections PNP signal input typical 26 Fig 18 Termi...

Страница 47: ...disable 22 time 1 0 3 ALARM 31 no flow disable 32 time 10 4 DISPLAY 41 display increase 42 light 100 5 POWER MANAGEMENT 51 LCD new 1 sec 52 battery mode operational 6 FLOWMETER 61 signal coil lo 7 RE...

Страница 48: ...O box 6 Voltaweg 23 Website www fluidwell com 5460 AA Veghel 5466 AZ Veghel Find your nearest representative www fluidwell com representatives the Netherlands the Netherlands 2017 Fluidwell B V FW_F13...

Отзывы: