Page 15
FW-F030-P-M_v0404_01_EN.docx
3.3.4
EXPLANATION OF SETUP-MENU 3 - DISPLAY
SETUP
FUNCTIONS
AND
VARIABLES
3
DISPLAY
3.1
FUNCTION
The large 17mm digits can be set to display actual batched quantity
(increase) OR to display the remaining quantity to be batched
(decrease).
The functions below will only effect the optional LED-backlight.
3.2
BACKLIGHT (optional)
If a LED backlight has been supplied, it can be turned on or off.
3.3
BL. BRIGHTNESS
(optional)
The backlight brightness is adjustable. The following can be selected:
1
– 5 (where 1 is minimum and 5 is maximum brightness)
3.3.5
EXPLANATION OF SETUP-MENU 4 - POWER MANAGEMENT
When used with the internal battery option, the user can expect reliable measurement over a long
period of time. The F030-P has several smart power management functions to extend the battery life
time significantly. Two of these functions are available.
SETUP
FUNCTIONS
AND
VARIABLES
4
POWER MANAGEMENT
4.1
LCD NEW
The calculation of the display-information influences the power
consumption significantly. When the application does not require a
fast display update, it is
strongly advised
to select a slow refresh
rate. Please understand that NO information will be lost; every pulse
will be counted and the output signal will be generated in the normal
way.
The following can be selected:
Fast - 1 sec - 3 sec - 15 sec - 30 sec - off.
Example battery life-time with a coil pick-up:
•
1kHz pulse and FAST update: about 2 years.
•
1kHz pulse and 1 sec update: about 5 years.
After a button has been pressed by the operator - the display refresh
rate will always switch to FAST for 30 seconds. When "OFF" is
selected, the display will be switched off after 30 seconds and will be
switched on as soon as a button has been pressed.
4.2
BATTERY MODE
The F030-P has two modes: operational or shelf.
After "shelf" has been selected, the F030-P can be stored for several
years; it will not process the sensor signal; the display is switched off
but all settings and totals are stored. In this mode, power consumption
is extremely low.
To wake up the F030-P again, press the SELECT/
key twice.