Fluidwell F030-A Скачать руководство пользователя страница 36

Page 36

 

FW-F030-P-M_v0404_01_EN.docx 

5.2 

ELECTRICAL INSTALLATION IN HAZARDOUS AREA 

5.2.1 

GENERAL INFORMATION AND INSTRUCTIONS 

 

Cautions 

  Mounting, electrical installation, start-up and maintenance of this device may only be 

carried out by trained persons authorized by the operator of the facility. Persons must 
read and understand this manual before carrying out its instructions. 

  This device may only be operated by persons who are authorized and trained by the 

operator of the facility. All instructions in this manual are to be observed. 

  Make sure the measuring system is correctly wired up according to the wiring diagrams. 

Protection against accidental contact is no longer assured when the enclosure cover is 
removed or the panel cabinet is opened (danger from electrical shock). The enclosure 
may only be opened by trained persons authorized by the operator of the facility. 

  To maintain the degree of protection of at least IP65 in accordance with IEC 60529, 

suitable cable entries and blanking elements must be used and correctly installed. 

  Take careful notice of the "Safety rules, instructions and precautionary measures" in the 

front of this manual. 

  Chapter 4 shows general information regarding the electrical installation of your indicator.  

This chapter gives additional specific information regarding Intrinsically safe installation 
and overrules the information given in chapter 4. 

  When installing this device in hazardous areas, the wiring and installation must comply 

with the appropriate installation standards for your industry. 

 

 

 

Safety instructions 

  For the combined connection of the different supply, input and output circuits, the 

instructions in this manual must be observed.  

  Precautions shall be taken to avoid the risk of electrostatic discharge (ESD) and 

propagating brush discharges. 

  For reasons of ESD and safety, always ground the metal enclosure properly as indicated 

in section “4.5. Electrical installation” of this manual. 

  Do not blend metal front covers with non-metallic rear covers, vice versa and / or cable 

glands. A metal cover on a non-metallic rear cover could lead to ESD. A metal cable 
gland in a non-metallic enclosure could invalidate isolation.

 

  For enclosures and windows with a high surface resistance, potential charging hazard 

exists. Do not rub these surfaces of the indicator. Clean window and enclosure only with a 
lint-free cleaning cloth made damp with a mild soap solution.

 

 

 

 

Please note 

  Certificates and related documents are available on our website or from your distributor. 

  Carefully study the configuration examples with wiring diagrams per classification in the 

following paragraphs. 

5.2.2 

INSTALLATIONS BASED ON FM OR CSA CERTIFICATE 

 

Installation instructions 

  For installation in the 

US

: this Intrinsically Safe device must be installed in accordance 

with the National Electrical Code, NFPA 70, Article 504 and ANSI/ISA-RP 12.6 and 
product certificate FM16US0177X or CSA.08.2059461. 

 

  For installation in 

Canada

: this Intrinsically Safe device must be installed in accordance 

with the Canadian Electrical Code, Part 1 Appendix F and product certificate 
CSA.08.2059461.

 

Covered markings 

  Intrinsically Safe for Class I/II/III, Division 1, Groups A,B,C,D,E,F,G, Temperature class T4

 

  Class I, Zone 0, AEX ia IIC T4 

Safety instructions 

  Please consult the control drawing for this F0-Series model on the following page. 

  Read paragraph 6.3 for battery replacement instructions. 

Specific conditions of use 

  When the enclosure of the indicator is made of aluminum alloy, when used in a potentially 

explosive atmosphere requiring apparatus of equipment protection level Ga, the indicator 
shall be installed so, that even in the event of rare incidents, an ignition source due to 
impact or friction sparks between the enclosure and iron/steel is excluded.

 

Содержание F030-A

Страница 1: ...ignal input flowmeter pulse Namur and coil Control output one control output for one stage batching Options Intrinsically Safe F Series Field mounted indicators for safe and hazardous areas More info...

Страница 2: ...t be disposed of into the general waste system or into a landfill At the end of its life equipment shall be disposed of according to the local regulations regarding waste of the electrical and the ele...

Страница 3: ...amage of the F030 P or connected instruments A caution indicates actions or procedures which if not performed correctly may lead to personal injury or incorrect functioning of the F030 P or connected...

Страница 4: ...conditions 17 4 3 Handling the F Series enclosure 18 4 3 1 Identification 18 4 3 2 Opening Removing the cover 20 4 3 3 Closing Replacing the cover 20 4 4 Mechanical installation 21 4 4 1 Dimensions Al...

Страница 5: ...Safe applications 41 5 4 1 F030 P OT PC PX XI ZB Battery powered Ex ia IIC IIIC 41 5 4 2 F030 P OT PX XI ZB Ex ia IIC IIIC 41 5 4 3 F030 P OT PX XI ZB Ex ia IIC IIIC 42 5 4 4 F030 P OT PD XI ZB Ex ia...

Страница 6: ...signal output can be connected to the F030 P To power the sensor several options are available Fig 1 Typical application for the F030 P Configuration of the F030 P The F030 P has been designed to be i...

Страница 7: ...ch cannot be continued When the batch process is stopped the STOP key is used to select total and accumulated total The STOP key is also used to select the next digit after the PROG key has been press...

Страница 8: ...at all times by pressing STOP twice in which case the actual values are lost and the system returns to steady state the batch cannot be resumed Fig 5 Example display information when interrupted After...

Страница 9: ...the battery MUST be replaced shortly after The remaining lifetime after the first moment of indication is generally several days up to some weeks See paragraph 6 3 for further information on battery...

Страница 10: ...ill active Make sure that the unit is not being used for any application when altering the settings 3 2 1 ENTERING SETUP LEVEL Configuration of the F030 P is done at SETUP level which can be reached a...

Страница 11: ...n either contains a value a number with optionally a decimal point e g 123 45 or a list with items e g Disable Enable For each function that needs to change navigate to that function and follow the st...

Страница 12: ...ey During the programming sequence this key is used to confirm the new value and return to SETUP level To cancel the operation either press the PROG key for 3 seconds or wait for 20 seconds the progra...

Страница 13: ...00010 9 999 999 1 4 DECIMALS K FACTOR 0 6 1 5 BATCH MAXIMUM X XXX XXX quantity 2 OVERRUN 2 1 OVERRUN disable enable 2 2 TIME 0 1 999 9 seconds 3 DISPLAY 3 1 DISPLAY increase decrease 3 2 BACKLIGHT opt...

Страница 14: ...SETUP 1 3 6523100 and for SETUP 1 4 decimals K factor 6 1 4 DECIMALS K FACTOR This setting determines the number of decimals for the K factor entered SETUP 1 3 The following can be selected 0 1 2 3 4...

Страница 15: ...W The calculation of the display information influences the power consumption significantly When the application does not require a fast display update it is strongly advised to select a slow refresh...

Страница 16: ...put 820 pull down 4 kHz External power required COIL HI High sensitive coil input 20 mV p t p Sensitive for disturbance COIL LO Low sensitive coil input 90 mV p t p Normal sensitivity ACTIVE Active pu...

Страница 17: ...e g F030 P XF Follow the electrical installation instructions as shown in chapter 4 and the mechanical installation instructions of the enclosure that are supplied separately Type XI Suitable for int...

Страница 18: ...y your F0 Series device all field mount enclosures have a weatherproof identification label placed on the outside of the unit Fig 7 Identification Example of F0 Series identification label safe area I...

Страница 19: ...fe area Type PM or PF Serial number and year of production The serial number can be reviewed on the identification label or in SETUP menu Others The production date is either shown separately on the l...

Страница 20: ...heir mating parts and the front cover is now completely separate 4 3 3 CLOSING REPLACING THE COVER To replace the cover on the F Series enclosure follow this procedure 1 Re insert all terminals to the...

Страница 21: ...rt B after H HBx Fig 10 Dimensions Aluminum and stainless steel enclosures 75 mm 2 95 130 mm 5 12 112 mm 4 40 60 mm 2 36 120 mm 4 72 M20 x 1 5 PG9 PG9 30mm 30mm 22 5mm M20 x 1 5 M16 x 1 5 M16 x 1 5 30...

Страница 22: ...mm 5 12 112 mm 4 40 60 mm 2 36 120 mm 4 72 HD HK HK back box flat bottom HE HF HG HH D 12mm 12mm 12mm 24mm 24mm 36mm 36mm 14mm 17mm 22 5mm 30mm 30mm D 16mm D 20mm 0 9 D 22mm 0 866 22 5mm 25mm 25mm D 2...

Страница 23: ...ng the mounting plate please follow the instructions that came with the accessories Alternatively the unit can be panel mounted by using only the front cover Wall mount by using the openings on the ou...

Страница 24: ...ack panel The metal front panel is connected to the Protective Earth by the mounting screws and serrated washers The wire screens shield are meant to prevent electromagnetic interference and shall be...

Страница 25: ...tional Rules and Regulations When a power supply is connected to the field wiring connections please also consider the demands for power supply wiring shown in paragraph 4 5 4 The installation must co...

Страница 26: ...your distributor The sensor supply at terminal 3 is fixed to 1 2V DC for coil type inputs and 3 2V DC for all other types of flowmeter inputs set by firmware For type PD Terminal 6 sensor supply 8 2V...

Страница 27: ...to the common ground terminal See paragraph 4 5 The input signal type has to be selected with the correct SETUP function read chapter 3 3 2 On terminal 3 and 6 an internal and external sensor supply i...

Страница 28: ...for use with flowmeters which have a PNP output signal Terminal 3 offers 3 2V which has to be switched by the sensor to terminal 2 SIGNAL For a reliable pulse detection the pulse amplitude has to go...

Страница 29: ...6 can be provided with type PD Fig 21 Terminal connections NAMUR signal input 4 6 2 TERMINAL 4 5 POWER SUPPLY TYPE PX DEFAULT AND PD OPTION To power the F030 P an internal battery can be used type PB...

Страница 30: ...process Maximum switch power 300mA 50V DC Fig 22 Terminal connections Passive transistor output Type OT 4 6 5 TERMINAL 9 10 POWER SUPPLY BACKLIGHT TYPE ZB OPTION To power the backlight a voltage in t...

Страница 31: ...02 Type PF 24V AC 10 AC AC Type PF 24V DC 10 L L Type PM 115 230V AC 10 AC AC The total consumption of the sensor transistor output type OA and backlight type ZB may not exceed 400mA 24V DC Risk of d...

Страница 32: ...active pulse or coil The screen of the signal wire can be connected to the common ground terminal See paragraph 4 5 The input signal type has to be selected with the correct SETUP function read chapt...

Страница 33: ...N signal input Pulse signal PNP PNP LP The F030 P is suitable for use with flowmeters which have a PNP output signal For a reliable pulse detection the pulse amplitude has to go above 1 2V Signal sett...

Страница 34: ...rom the reed switch it is advised to select REED LP low pass filter read chapter 3 3 2 Fig 32 Terminal connections Reed switch signal input NAMUR signal The F030 P is suitable for flowmeters with an N...

Страница 35: ...r F0 Series device all field mount enclosures have a weatherproof identification label placed on the outside of the unit Fig 34 Identification Example of F0 Series identification label intrinsic safet...

Страница 36: ...sh discharges For reasons of ESD and safety always ground the metal enclosure properly as indicated in section 4 5 Electrical installation of this manual Do not blend metal front covers with non metal...

Страница 37: ...7 and 8 11 and 12 the input parameters of the connected hazardous location apparatus must meet the following requirements Vmax The Voc of the of the circuit Imax The Isc of the circuit Pmax The Pmax o...

Страница 38: ...cuits precautions must be taken to separate the Intrinsically safe circuits in accordance with EN 60079 11 For electrical data consult Annex 1 for this F0 Series model on the following page Substituti...

Страница 39: ...PD PX terminals 4 and 5 in type of protection intrinsic safety Ex ia IIC IIIC only for connection to a certified intrinsically safe circuit with following maximum values Ui 30 V Ii 200 mA Pi 1 2 W Li...

Страница 40: ...ll energy used by the flowmeters pick up will directly influence the battery life time It is strongly advised to use a zero power pickup such as a coil or reed switch when operating without external p...

Страница 41: ...series 1 2 3 Common ground Signal Supply Circuit depends on type of signal 7 8 Common ground 4 5 Common ground Main supply 9 10 Common ground Supply backlight Power supply or switch interface For exa...

Страница 42: ...ty values Consult the technical specification for operational values Power supply For example MTL5025 Uo Io Po Power supply type PX 8 30V DC Backlight option type ZB Sensor supply voltage for pulse ty...

Страница 43: ...ay update uses significantly more power Pulse output Low temperatures the available power will be less due to battery chemistry Check periodically The condition of the casing cable glands and front pa...

Страница 44: ...ons Intrinsically safe applications Type PC Only batteries of type FW LiBAT 021 that hold the Ex marking as shown below are suitable replacements and certified for use in hazardous areas Before replac...

Страница 45: ...the battery connector to prevent a short circuit Fig 43 Battery replacement procedure Install the new battery as follows 1 Make sure the new battery is undamaged in good condition and suitable for us...

Страница 46: ...HO HBO HSO Type HP Type HT Type HU HBU HSU Type HV Type HZ GRP enclosures Type HC Type HD Type HE Type HF Type HG Type HH Type HJ Type HK types HS_ are stainless steel versions HB_ are extended alumi...

Страница 47: ...250 x 200mm 13 7 x 9 9 x 7 9 WxHxD Directives Standards EMC EN 61326 1 FCC 47 CFR part 15 Low voltage EN IEC 61010 1 CSA C22 2 No 61010 1 UL61010 1 ATEX EN IEC 60079 0 EN 60079 11 IECEx IEC 60079 0 IE...

Страница 48: ...cess Total can be reset to zero Displayed information Preset value Running batch total or remaining quantity Total and accumulated total Preset Total Digits 7 digits Unit L m3 kg lb GAL USGAL bbl no u...

Страница 49: ...re for flowmeter signals and connect screen to terminal 9 unless connected at sensor The pass code is unknown If the pass code is not 1234 there is only one possibility left call your supplier ALARM W...

Страница 50: ...echnology Bo 6 5 60 AA e hel he etherlands oltawe 5 66 A e hel he etherlands luidwell B is 001 certified b A ertification B eander 1051 6 5 Arnhem he etherlands eghel February 2 22 e Fluidwell declare...

Страница 51: ...unctional description 6 high alarm output 30 intrinsic safety 35 Intrinsic safety 36 40 43 45 keys 7 low battery 9 main function 10 maintenance 43 namur signal 29 34 operational 7 10 17 43 operator le...

Страница 52: ...nal input 29 Fig 22 Terminal connections Passive transistor output Type OT 30 Fig 23 Terminal connections Backlight ZB 30 Fig 24 Overview of terminal connectors F030 P type PF PM 31 Fig 25 Terminal co...

Страница 53: ...Page 53 FW F030 P M_v0404_01_EN docx...

Страница 54: ...Page 54 FW F030 P M_v0404_01_EN docx...

Страница 55: ...Page 55 FW F030 P M_v0404_01_EN docx...

Страница 56: ...tness 5 4 POWER MANAGEMENT 4 1 LCD new 1 sec 4 2 mode operational 5 FLOWMETER 5 1 signal coil lo 6 OTHERS 61 model F030 P F030 P F030 P 6 2 software version 03 ____ ____ 03 ____ ____ 03 ____ ____ 6 3...

Отзывы: