background image

AUTO RESETTABLE ALARMS
Over-voltage

It is active when main power supply is:

> 135 Vac for nominal 115 Vac;
> 245 vac for nominal 230 Vac.

It is inactive when main power supply is:

< 125 Vac for nominal 115 Vac;
< 245 Vac for nominal 230 Vac.

Under-voltage

It is active when main power supply is:

< 50 Vac for nominal 115 Vac;
< 100 vac for nominal 230 Vac.

It is inactive when main power supply is:

> 60 Vac for nominal 115 Vac;
> 120 Vac for nominal 230 Vac.
 

Over-temperature (controller)

It is active when the power module temperature is > 90°C (194°F).
It is inactive when the power module temperature is < 80°C (176°F) 
When an auto resettable alarm is active, the unit switch off, the Fault 
signal is low (0V) and the alert LED flash. When an auto resettable 
alarm cease the Fault signal goes high (5V), alert LED is steady and 
the unit restart with set settings, if ON signal is present.

SEMI-PERMANENT ALARMS
Start-up 

If the starting sequence of the unit fails (eg. phase disconneted, rotor 
blocked before start, etc...), the driver opens the power module and 
attempts to restart for 20 times (around 20 sec). The counter to 
attempt the restart resets completely when unit works for more then 
16 sec. After 20 attempts, the drive passes in blocking state, the 
fault signal is low (0V) and the alert LED blinks.

N

ote

:

 During restart no alarm is active. The alert LED is temporary 

OFF.

Rotor blocked

If the pump rotation is blocked, the driver opens the power module 
and it passes into blocking state. 

Module Fault (hardware)

Intended during running. Tipically if an overload condition happens. If 
in the pump rotation a peak (typically more than 1000 W) of current 
appears in the module, the driver disables the power module and 
the TMFR/TSFR motor passes in blocking state. 

Over-load power

If in the pump rotation an overload happens and with a speed 
regulation is not able to reduce power within 375 W, the driver 
disables the power module and passes in blocking state. 

Over-current limit (50% more than the over-load power)

If in the pump rotation a peak of the current appear for an overload 
(more 400 W), the driver opens the power module and it passes in 
blocking state. When a semi-permanent alarm happens (blocking 
state) the Fault signal goes low (0V), the alert LED blinks and for 
restarting the unit it is necessary one of these two operations:
-  Turn off the main power supply and after turn on it again;
-  Turn off the ON/OFF digital signal and after turn on it again.
These two operations RESET the driver. If the cause of the block is 
removed the unit will start removing the Fault signal.

TYPICAL DRIVER BEHAVIOUR WHEN IN OVERLOAD

The driver, when the power output reach the maximum value (more 
then 400W), it decrease and modulate automatically the rotational 

speed, up to minimum speed, for maintaining the maximum load 
within 375W. If it couldn’t modulate it enter in “over-load power” 
semi-permanent alarm mode.

ELECTRIC INSTALLATION

The power connection wires must be of appropriate section, in 
proportion to the current absorbed in the specific application. 
The cable shield must be connected to the ground both on the 
inverter and on the motor side. 
The power cables must be separated from the control cables; it is 
forbidden passing them in the same raceway. It is important to keep 
separated the motor cable from the cable going to the electronic. 

MECHANICAL INSTALLATION

The TMFE2 controller and TMFR/TSFR motor+pump unit are cooled 
by forced or natural ventilation. For this reason the unit must be 
mounted taking into account a 40 mm space around it and, in 
correspondence to the heat sink, 150 mm on top and underneath in 
order to grant the free circulation of cooling air. In case of mounting 
more units stacked it is necessary to leave a minimum of 300 mm 
vertically between the 2 units.
The air must be free from dust or corrosive substances. In case 
this is not possible, the heat sink must be periodically cleaned. 
Condensation of vaporized fluids must be avoided at all times. 
The environmental humidity must not exceed 90%. The ambient 
temperature in the chassis of the machine must not exceed 40 
°C; it is otherwise necessary a derating of the device or a forced 
ventilation to avoid stagnation of air.
The controller, the unit and electrical connection must be protected 
from fluids drips that could damage unit and cause short circuit.

Hydraulic Note

Electric/Manual valves in pump inlet/outlet circuit have to be 
opened before TMFR/TSFR start-up. If the pump is equipped with 
a relief valve (by-pass), the valve will work, in case of accidental 
overpressure, in order to limit the peak pressure, by an internal 
recirculation of the fluid. Thanks to the magnetic coupling the pump 
does not need a mechanical seal in order to prevent leakage. 
This eliminates the problems connected to the use of a mechanical 
seal. The maximum pressure depends on the pump model and it 
decreases with the increase of the flow rate.
The outlet pressure must not exceed 20 bar/290 psi in any case.

REPLACING THE PUMP

In order to replace the pump it is necessary to remove the three 
screws on the front end of the motor. Once these screws are 
removed it is sufficient to pull the pump back. During this operation 
it is necessary to verify that the magnet cap does not make in 
contact and damage the stator winding. The pump magnet is very 
powerful, it is therefore important to keep it far from pacemakers, 
credit cards, watches and all equipment sensitive to magnet fields. 
It is also necessary to replace the pump in a clean environment, 
as any magnetic particles in close proximity to the magnet will be 
attracted from it and it might cause the pump to fail prematurely.

After each manipulation is necessary to re-conduct safety tests 
(disconnecting controller), as prescribed in EN-60335 and 
UL-1004, for this reason is recommended that operations are 
conducted by Fluid-o-Tech qualified operators. 

Содержание TMFE2

Страница 1: ...amage are not marked by a warning triangle The warnings appear in decreasing order of risk as given below Danger Indicates that death or serious injury will result if proper precautions are not taken Warning Indicates that death or serious injury may result if proper precautions are not taken Caution With a safety alert signal indicates that minor personal injury can result if proper precautions a...

Страница 2: ...s must be taken into account All work should be undertaken with the system in a no voltage condition If this is not observed this can result in injury Warning The capacitors mounted in the unit have dangerously high voltage For this reason once the power cord has been disconnected it is necessary to wait three 3 minutes minimum before any service on the device ESDS information and instructions Ele...

Страница 3: ...tamination of the cooling system in order to maintain proper cooling efficiency Supply system Switches contactors fuses Filter MicroProcessor Power module Pump Motor Sensoriess feed back Cable Choke Cable Filter optional Closed loop control Digital Analog Optional MODEL Input Inverter Nominal Out motor Motor Weight Standard Vac KW input current power Kg current A A FEXXEXXX 230V 10 0 25 1 8 0 9 Sa...

Страница 4: ...ose proximity to the inverter storage temperature 20 C to 60 C Environment conditions ventilation natural circulation humidity from 20 to 90 without condensation altitude of installation max 2000 m u s l derating for higher altitudes protection IP 20 Type External connections Digital opto coupled LED orange Indication of Supply permanent Alarms blink Alerts Is located in the center of the main boa...

Страница 5: ...eve max Conductor cross section stranded min 0 2 mm 1 5 mm Conductor cross section stranded max 2 5 mm Conductor cross section stranded with ferrule with plastic sleeve min Conductor cross section stranded with ferrule 0 25 mm Without plastic sleeve min Conductor cross section stranded with ferrule with plastic sleeve max 1 5 mm Conductor cross section AWG kcmil min 24 Conductor cross section AWG ...

Страница 6: ...C NC NC 5 to 24 V polarity can be reversed 0 V polarity can be reversed NC NC SERVICE CONNECTOR TYCO 3 643814 7 OR EQUIVALENT 1 2 3 4 5 6 7 MODE OPTO DIGITAL EXTERNAL DIP MOTOR OFF ON 4 2 1 3 6 5 MOTOR ON DIP SWITCH SETTINGS see previous table 0V 0 5 to 24 V 1 PIN 3 DIP STATUS SERVICE Connector 0V 0 0V 0 PIN 4 SERVICE Connector FUNCTION MODE DIGITAL OPTO ON OFF 7 6 5 4 3 2 1 NC NC NC 5 to 24 V pol...

Страница 7: ...STATUS ON 4 2 7 6 5 4 3 2 0 Vs 0 Vs A I 4 20 mA 0 Vs ON 5 V FAULT OUT Active low 1 3 6 5 DIP STATUS ON 4 2 7 6 5 4 3 2 1 NC 0 Vs A I PWM 5 to 95 TTL signal 0 Vs ON 5 V FAULT OUT Active low 5 Vs SERVICE CONNECTOR TYCO 3 643814 7 OR EQUIVALENT MODE ANALOG IN PWM COMMAND 100 10 000 Hz 1 3 6 5 TATUS 4 7 6 5 4 3 2 1 NC 0 Vs A I 0 5 V 0 Vs ON 5 V FAULT OUT Active low 5 Vs SERVICE CONNECTOR TYCO 3 643814...

Страница 8: ...rature controller 4 Start up 5 Rotor blocked 6 Module Fault hardware 7 Over load power 8 Over current limit 50 more than the over load power In the picture below there is the diagram with the electronic characteristic of the Fault Signal It is active when low 0V When the TMFR TSFR unit runs correctly the FAULT signal is high 5V From µProcessor R 2 1 JP4 5 VField FAULT 0V Field 6 From µProcessor R ...

Страница 9: ... over load power semi permanent alarm mode ELECTRIC INSTALLATION The power connection wires must be of appropriate section in proportion to the current absorbed in the specific application The cable shield must be connected to the ground both on the inverter and on the motor side The power cables must be separated from the control cables it is forbidden passing them in the same raceway It is impor...

Страница 10: ......

Страница 11: ...ncy 50 60Hz OUTPUT RATING Vn 180 Vac 3phase P N FEE2AWR1 99260905 02 I in 5 4 A rms In 1 89A rms W in 375 W 4 3110 in 4 7243 in 2 1692 in 4 2795 in Ø 23 82 5 3 25 in 36 5 57 2 24 in 114 4 49 in 38 1 5 in 90 3 54 in 125 4 92 in X X 4x Ø11 2 x 3 8 NPT 2 x 3 8 GAS TO CONTROLLER CARD BY CONNECTION CABLE X X 125 4 92 in 37 1 46 in 65 2 56 in Ø 0 91 in 1 44 in Ø 0 43 in ...

Страница 12: ...garded The unit has been disassembled or modified by anyone other than a Fluid o Tech or authorized by Fluid o Tech engineer or repaired with non original components The unit operated dry or in cavitation throttled undersized inlet or filter Solid extraneous particles are found in the pump Evident signs of operating pressure higher than 16 bar high pressure may compromise the integrity of the inte...

Отзывы: