HART COMMUNICATION
The Logix
®
series positioners use the HART
communication
protocol
specified
by
the
HART
Communication Foundation.
23.1 ValveSight
®
DTM
Flowserve Corporation has produced a custom Device
Type Manager (DTM) for the Logix
®
digital
positioners to support the ValveSight
®
diagnostics platform.
The DTM contains a high level “Dashboard” view of the
system health and status information. See
Error!
Reference source not found.
28. It also contains
comprehensive user-friendly interfaces for control and
reporting of alarms, of-line and on-line diagnostic tests,
calibrations and system configurations.
The ValveSight
®
DTM is available from a Flowserve
representative or from www.valvesight.com.
Figure 28: ValveSight DTM Dashboard
23.2 HART 375/475 Handheld
Communicator
The Logix
®
digital positioner supports and is
supported by the HART 375/475 Handheld Communicator.
The Device Description (DD) files can be obtained from the
HART Communication Foundation or from your Flowserve
representative.
23.3 Changing HART Versions
The Logix
®
positioner comes standard with the
HART 6 communication protocol. Follow this procedure to
change to HART 7.
1
Remove the outer cover.
2
Remove the inner cover by removing the 3 inner
cover retaining screws.
CAUTION:
Observe precautions for
handling
electrostatically sensitive devices.
3
With a clean, non-conductive instrument, change the
position of DIP switch according to
Error! Reference
source not found.
. After changing the DIP switch,
the positioner will immediately recognize the new
HART communication protocol.
4
Replace the covers.
HART DIP Switch
HART 6
(Default)
HART 7
1
2
3
4
1
2
3
4