INSTALLATION INSTRUCTIONS
37
T
S
4.3 Flushing the system
Failure to flush and add inhibitor to the system will invalidate the appliance operation.
All systems must be thoroughly drained and flushed out using additives – corrosion inhibitors and flushing
agents/descalers. All flushing must be done for new and retrofit installs.
Warning: Failure to clean the system and add adequate inhibitor invalidates the warranty.
To flush out the primary side of this unit:
a.
Fill the water heater with clean water as per the filling instructions.
b.
Using a drain off cock on the lowest point of the system allow the water to drain from the system and water
heater.
c.
In order to flush the system correctly, turn off all radiators or fan coils, Open the filling loop and drain cock
simultaneously and allow the water to flow through the water heater.
d.
Open each individual radiator or fan coil, allowing water to flow through. Then turn that radiator or fan coil off
and repeat for all radiators or fan coils on the system.
e.
Turn off the filling loop and close the drain cock. Open all radiators or fan coils and open the filling to fill the
system.
f.
Continue to fill the system until the pressure gauge reaches 14.5 psi (1 bar).
g.
Add an inhibitor to the system water to prevent limestone and magnetite deposits from forming and to protect
the water heater from galvanic corrosion.
h.
In areas where freezing might occur, an antifreeze (Gycol) may be added to the system water to protect the
system. Please adhere to the specifications given by the antifreeze manufacture. Do not use automotive
silicate based antifreeze. Please observe that the antifreeze and water mixture does not exceed 40% of the
antifreeze content. Do not use antifreeze other than that specifically made for hot water heating systems.
Advise systems operator/ultimate owner that system is filled with antifreeze.
To flush out domestic hot water circuit:
a.
Open all hot water outlets.
b.
Turn on inlet group supply so water enters the water heater; leave to fill until water is released from the hot
water outlets. Turn off all hot water outlets.
c.
Connect a hosepipe to the cylinder drain cock and open the drain cock.
d.
Allow water to flow through the water heater and out of the drain cock.
e.
Turn off water supply, disconnect the hosepipe, close the drain cock and refill the water heater.
4.4 Filling the condensate trap
The condensation trap must be pre-filled when
starting the water heater for the first time in order to
prevent flue gases from flowing back through the
trap.
The filling operation is carried out as follows
(see fig. 1):
•
Remove plug
T
and fill the trap
S
three quarters
full with water;
•
Replace plug
T
and connect the drainpipe
P
into
a condensate discharge trap conforming to
current legislation;
Attention!
It is recommended to clean the
condensate trap, after a few months of water heater
operation, to remove deposits/residuals left after the
first condensate passage within the water heater
new components that may interfere with the correct
operation of the trap itself.
Fig. 1
Содержание FLOWMAX-120
Страница 2: ......
Страница 9: ...GENERAL INFORMATION 5...
Страница 10: ...GENERAL INFORMATION 6...
Страница 11: ...GENERAL INFORMATION 7...
Страница 12: ...GENERAL INFORMATION 8...
Страница 26: ...INSTALLATION INSTRUCTIONS 22 3 6 Schematic of Piping Installation...
Страница 27: ...INSTALLATION INSTRUCTIONS 23...
Страница 34: ...INSTALLATION INSTRUCTIONS 30...
Страница 35: ...INSTALLATION INSTRUCTIONS 31...
Страница 36: ...INSTALLATION INSTRUCTIONS 32...
Страница 37: ...INSTALLATION INSTRUCTIONS 33...
Страница 38: ...INSTALLATION INSTRUCTIONS 34...
Страница 72: ...FLOW CHART 68...
Страница 73: ...FLOW CHART 69...
Страница 74: ...FLOW CHART 70...
Страница 75: ...FLOW CHART 71...
Страница 76: ...FLOW CHART 72...
Страница 77: ...FLOW CHART 73...
Страница 78: ...FLOW CHART 74...
Страница 79: ...FLOW CHART 75...
Страница 80: ...FLOW CHART 76...
Страница 87: ......