background image

MAINTENANCE INSTRUCTIONS 

 

57

Modulation circuit board 

(see fig. 1-2)

 

  Open the control panel 

(see 6.4 “Accessing the water 

heater”);

    

 

  Disconnect all the connectors, remove the

 

regulating knobs, unscrew the four fixing screws and 
remove the modulation circuit board; 

  Replace the circuit board and re-assemble the  

components following the above procedure in 
reverse order; 

  Switch on the electricity, water and gas supplies  

and regulate the water heater 

(see 5.3 “Gas data”)

 

The  preset  parameters  of  the  printed  circuit 
board  correspond  to  an  instantaneous  type 
water heater fed by natural gas.  

When  replacing  the  modulation  circuit  board, 
check  the  “Minimum  heating  flow  rate”  – 
Parameter  19  and  “Max  Heating  power”  – 
Parameter 20. 

 

 

Electric fan circuit board 

(see figs. 1-2)

 

  Open the control panel 

(see 6.4 “Accessing the water 

heater”)

  Disconnect the two connectors from the circuit board, 

unscrew the two fixing screws and remove the board;

 

  Replace  the  circuit  board  and  re-assemble  the 

components  following  the  above  procedure  in 
reverse order; 

  Switch on the electricity, water and gas supplies. 

 

electric fan circuit board  

modulation circuit board 

Fig. 1 

electric fan circuit board 

modulation circuit board  

Fig. 2 

Содержание FLOWMAX-120

Страница 1: ...sonal injury or death Do not store or use gasoline or other flammable vapours and liquids in the vicinity of this or any other appliance WHAT TO DO IF YOU SMELL GAS Do not try to light any appliance D...

Страница 2: ......

Страница 3: ...ard 16 3 2 Unpacking 17 3 3 Installation water heater 18 3 4 Water connections 19 3 5 Domestic Hot Water Circuit Hard Water Warning Condensate Drain 20 3 6 Schematic of Piping Installation 22 3 7 Gas...

Страница 4: ...Flushing out the primary side 50 6 6 Draining the central heating and domestic hot water system 51 6 7 Maintenance operations 52 6 8 Wiring diagrams 59 6 9 D H W Sensor Connection 65 6 10 Troubleshoo...

Страница 5: ...ystem and any gas control which has been underwater Be sure not to reverse the water and gas connections as this may damage the gas valves Water temperatures over 125 F can cause severe burns instantl...

Страница 6: ...lammable liquids or engine driven equipment or vehicles are stored operate or are repaired Flammable vapours are heavy and travel along the floor and may be ignited by the igniter or main burner flame...

Страница 7: ...hould there be a smell of gas present in the room where the appliance is installed DO NOT attempt to activate any electric switches telephones or any other equipment that may cause sparks Open doors a...

Страница 8: ...f qualified licensed professionals for the installation of hard wired carbon monoxide detectors a In the event that the side wall horizontally vented gas fuelled equipment is installed in a crawl spac...

Страница 9: ...GENERAL INFORMATION 5...

Страница 10: ...GENERAL INFORMATION 6...

Страница 11: ...GENERAL INFORMATION 7...

Страница 12: ...GENERAL INFORMATION 8...

Страница 13: ...to operate In its simplicity the wall mounted appliance is equipped with all the appropriate accessories required to make it a fully independent water heater capable of satisfying domestic hot water p...

Страница 14: ...pressure heating Bar psi 0 3 4 29 Domestic Hot Water circuit D H W temperature setting min max C F 35 60 95 140 Max Hot water working pressure Bar psi 6 86 Min Hot water working pressure Bar psi 0 5...

Страница 15: ...2 5 2 28 7 HO CWI G HI HWO 1 9 3 1 4 1 2 12 2 28 7 4 4 7 3 4 4 1 9 12 3 1 9 4 9 2 7 3 2 2 2 Dimensions LEGEND HI HEATING INLET 3 4 HO HEATING OUTLET 3 4 G GAS 1 2 CWI COLD WATER INLET 1 2 HWO HOT WAT...

Страница 16: ...C AIR VENT VALVE 12 HEATING SAFETY THERMOSTAT 13 HEATING SENSOR 14 PUMP WITH AIR VENT 15 WATER PRESSURE SWITCH 16 FLUE HOOD 17 SAFETY THERMOFUSE 18 EXPANSION VESSEL 19 D H W SENSOR 20 CONDENSATE TRAP...

Страница 17: ...URE SWITCH 16 FLUE HOOD 17 SAFETY THERMO FUSE 18 EXPANSION VESSEL 19 D H W SENSOR 20 CONDENSATE TRAP 21 WATER PRESSURE GAUGE 22 AUTOMATIC BY PASS 23 CONDENSATE DRAIN PIPE 24 SYSTEM DRAIN VALVE 25 ROOM...

Страница 18: ...TECHNICAL CHARACTERISTCS 14 2 5 Circulation pump head flow graph Pump head I II III Pump speed Boiler losses I II III 0 5 10 15 20 25 30 0 2 4 6 8 10 Water flow US gpm Head ft...

Страница 19: ...er deficiency indicator Temperature display When the water heater is switched off at the switch on the control panel the word OFF appears on the display The D H W and central heating frost protection...

Страница 20: ...and Instantaneous Conforms to ANSI STD Z21 10 3 certified to CSA STD 4 3 Failure to install a gas appliance correctly and in accordance with the above norms could lead to prosecution It is in the inte...

Страница 21: ...ntial hazard A Place the packed appliance on the floor see fig 1 making sure that the up arrow is facing down Remove the staples and open out the four flaps of the box B Rotate the water heater 90 whi...

Страница 22: ...the necessary clearances indicated in figure 1 are respected To make the installation easier the water heater is supplied with a template to enable the pipe connections to be positioned prior to fixin...

Страница 23: ...e drain line is installed to direct discharge to a safe location such as an open drain Avoid scalding and or water damage A pressure relief valve is installed in this dual purpose water heater that is...

Страница 24: ...operates A condensate trap and flexible drain pipe comes factory installed inside each water tank The condensate trap must be primed before operation to prevent exhaust gases from entering the buildi...

Страница 25: ...cleaning be sure to check for any leaks of condensed water or flue gas Space Heating This water heater is suitable for water potable heating and space heating Piping and components connected to the wa...

Страница 26: ...INSTALLATION INSTRUCTIONS 22 3 6 Schematic of Piping Installation...

Страница 27: ...INSTALLATION INSTRUCTIONS 23...

Страница 28: ...connections and re test Always purge the gas line for any debris before connecting to the water heater gas inlet Never use an open flame to test for gas leaks as property damage personal injury or dea...

Страница 29: ...y other voltage to this FLOWMAX Combination Water Heater This will damage the combination water heater and void the warranty Do not disconnect the power supply when the unit is in normal operation If...

Страница 30: ...few fundamental rules must be observed Do not touch the appliance with damp or wet parts of the body or when barefoot Do not pull on the electric wires Do not allow the appliance to be used by childr...

Страница 31: ...moved connect the wires to the terminal board B as follows Connect the ground wire normally coloured green yellow to the terminal marked with the ground symbol Connect the neutral wire normally colour...

Страница 32: ...Make Up Air Will Damage the Unit Recommend not to operate the combination water heater in an area that is or will be under construction or renovation The FLOWMAX warranty will not cover damage and pre...

Страница 33: ...C or ABS FLOWMAX 3 Diam 100 ft Natural Gas Schedule 40 PVC CPVC PVC CPVC or ABS FLOWMAX 3 Diam 100ft Natural Gas Schedule 40 PVC CPVC PVC CPVC or ABS Equivalent Lengths Reduce the maximum vent length...

Страница 34: ...INSTALLATION INSTRUCTIONS 30...

Страница 35: ...INSTALLATION INSTRUCTIONS 31...

Страница 36: ...INSTALLATION INSTRUCTIONS 32...

Страница 37: ...INSTALLATION INSTRUCTIONS 33...

Страница 38: ...INSTALLATION INSTRUCTIONS 34...

Страница 39: ...r heater complies with the data plate 120 V 60 Hz and that the live neutral and ground wires are connected properly Also make sure that the ground connection is sound Check that the gas supply is corr...

Страница 40: ...runs freely Check that the plug of the air vent valve has been slackened slightly to allow air to escape from the system fig 1 Open the main domestic water supply valve Open the filling tap R fig 2 Un...

Страница 41: ...l may be added to the system water to protect the system Please adhere to the specifications given by the antifreeze manufacture Do not use automotive silicate based antifreeze Please observe that the...

Страница 42: ...order to eliminate all the air from the pipes To repeat the operation wait approximately three minutes before re attempting to light the water heater To reset the water heater Switch off switch 1 see...

Страница 43: ...mospheric not premix FLOWMAX 90 FLOWMAX 120 FLOWMAX 170 152 Zone management board activation 00 01 Off On 163 Telephone control activation 00 01 Off On 17 Minimum fan speed setting 55 Hz Natural Gas 5...

Страница 44: ...ssed Wait for PL 0 to appear on the display 3 Release buttons and 4 Keep button S pressed and use button to select the parameter to modify 5 Release button S then re press and release it The display w...

Страница 45: ...value of the parameter 00 natural gas 01 propane 7 Press and release button S to confirm The parameter number 2 will appear on the display 8 Switch off the appliance and switch it back on again to ren...

Страница 46: ...n default 2 7 Press and release button S to confirm The parameter number 5 will appear on the display 8 Switch off the appliance and switch it back on again to render the new parameter operative PARAM...

Страница 47: ...5 min The default value is 18 90 1 5 min 7 Press and release button S to confirm The parameter number 8 will appear on the display 8 Switch off the appliance and switch it back on again to render the...

Страница 48: ...SYSTEM 6 If the system is fitted with zone valves set the parameter at 01 If a remote control is installed an extra interface board must be installed to control the zone valves Then set the parameter...

Страница 49: ...the new parameter operative PARAMETER 19 MINIMUM FAN SPEED SETTING CENTRAL HEATING MODE 6 Use buttons o to modify the value of the parameter between min 33 max value of parameter 18 The default value...

Страница 50: ...pliance and switch it back on again to render the new parameter operative PARAMETER 22 FAN FREQUENCY VALUE DISPLAY 6 Use buttons o to modify the value of the parameter 00 Off 01 On If parameter value...

Страница 51: ...60 50 40 30 20 10 0 Natural gas G20 L P G G31 Table no 1 CO2 Values Gas type CO2 Natural gas G20 9 18 Liquid Propane Gas G 31 10 3 Table no 2 Frequency Gas type Minimum Hz Maximum Hz Natural gas G20 5...

Страница 52: ...ris is visible on the burners remove and clean with a vacuum cleaner All electric motors are permanently lubricated and do not need oiling Remove the combustion air blower and clean wheel and housing...

Страница 53: ...eck the pre fill pressure of the expansion tank see expansion tank rating plate For safety reasons periodically check the integrity and operation of the exhaust system Check that the connection to the...

Страница 54: ...ight control panel support brackets see fig 5 and pull them outwards at the same time rotating the panel downwards Unscrew the four fixing screws see fig 6 and remove the panel back piece 6 5 Flushing...

Страница 55: ...n the radiators starting with the highest and moving down the system to the lowest When the system has been drained close the radiator breather valves and the drain valve If only the water heater need...

Страница 56: ...he ceramic fibre protection from the bottom of the heat exchanger Check that the burner is not affected by deposits scaling or excessive oxidation Check that all the holes in the burner are free Clean...

Страница 57: ...check for any leaks from the joints Part replacement Ignition and or flame ionization electrodes see fig 2 Un Plug the electrode wires Slacken the fixing screws Remove the electrodes When fitting the...

Страница 58: ...he shut off valves and fill the central heating circuit Then restart the appliance remembering to discharge any air that may be trapped in the system Gas valve see fig 2 Disconnect the joints and remo...

Страница 59: ...reverse order Switch on the electricity water and gas supplies and check the soundness of the joint by measuring the CO2 levels Expansion tank see fig 2 Close the shut off valves and drain the central...

Страница 60: ...ing circuit of the water heater Unscrew the fixing screws securing the transparent cover of the diverter valve and remove the cover Unscrew the four fixing screws and remove the diverter valve body an...

Страница 61: ...ted circuit board correspond to an instantaneous type water heater fed by natural gas When replacing the modulation circuit board check the Minimum heating flow rate Parameter 19 and Max Heating power...

Страница 62: ...return pipes Remove the support brackets and pull out the heat exchanger Remove the regulation sensor from the old heat exchanger and refit it together with the two condensate drainpipes to the new o...

Страница 63: ...FAN type RG 128 N L yellow green fusibile 2A brown green light blue brown light blue brown orange orange light blue light blue brown white light blue black red black orange orange Heating D H W brown...

Страница 64: ...When the wires have been connected place plate A back to position and then the front case panel Connecting the outside temperature sensor Option Connect the wires to the terminal board inside the inst...

Страница 65: ...remote controller wires When the wires have been connected place plate A back to position and then the front case panel Connecting the remote controller and the telephone control option Connect the wi...

Страница 66: ...one valve management option remote controller board Remote control and zone valves wiring For the installation of a zone valve p c b it is necessary to access the main p c b for electrical connection...

Страница 67: ...INSTRUCTIONS 63 REMOTE OPEN THERM Telephone control Terminal block Outside temperature sensor option Zone valve management option remote controller board Remote control zone valves and telephone cont...

Страница 68: ...the correction are reported in figure 1 The selection of the compensation curve is determined by the maximum delivery temperature Tm and the minimum outdoor temperature Te N B The y axis values of the...

Страница 69: ...INTENANCE INSTRUCTIONS 65 M2 FILLING LOOP REMOTE DHW CYLINDER FLOW REMOTE DHW CYLINDER RETURN MAX LENGHT 8 mt HOT WATER SENSOR LEAD PRINTED CIRCUIT BOARD CVI M SM20021 6 9 D H W Sensor connection Fig...

Страница 70: ...SWITCH k REPLACE PART l CHECK FLUE GAS DUCTS m CHECK CABLE E03 FLUE SAFETY THERMOSTAT n THERMOSTAT BROKEN o THERMOSTAT CABLE DICONNECTED p THERMOSTAT LOCK OUT HIGH FLUE TEMPERATURE n REPLACE PART o C...

Страница 71: ...ing 08 Frost Protection Central heating circuit The function is activated when the heating sensor senses a temperature of 5 C The water heater operates at minimum gas pressure with the 3 way diverter...

Страница 72: ...FLOW CHART 68...

Страница 73: ...FLOW CHART 69...

Страница 74: ...FLOW CHART 70...

Страница 75: ...FLOW CHART 71...

Страница 76: ...FLOW CHART 72...

Страница 77: ...FLOW CHART 73...

Страница 78: ...FLOW CHART 74...

Страница 79: ...FLOW CHART 75...

Страница 80: ...FLOW CHART 76...

Страница 81: ...TION ELECTRODE 35032LA IONISTATION ELECTRODE 36072LA VENTURI MINIFOLD RK50 57KW 36075LA GAS VALVE UL CSA 37033LA FAN RG 128 1300 UL CSA 59015LA WATER PRESSURE SWITCH PC 5411 BRASS 59020LA AIR PRESSURE...

Страница 82: ...X EPDM ORM 14X30 10 15 43151LA BY PASS REGULATOR EPDM O RING 1 16 43159LA WASHER EPDM 80 SH M PLEX 16x24x2 5 3 4 1 17 43208LA WASHER 23x30x3sp EPDM 80sh 1 1 18 43248LA O RING 4081 EPDM 18 68X3 53 70SH...

Страница 83: ...t heavy calcification lime deposits minerals and or other waterborne build up in the plate heat exchanger or corrosion due to chemical anti freeze additive is not considered defects in workmanship and...

Страница 84: ...include expenses of inspection obtaining substitute goods transportation etc Consequential damages include injury to persons or property inconvenience or other consequential damage resulting from a br...

Страница 85: ...________________________________________________ City______________________State Province________________ Zip Postal Code___________ Phone No ____________________________ Fax__________________________...

Страница 86: ...ith the part request Sold To Address Phone Fax Item Requested Water Heater Model No Water Heater Serial No Date of Purchase Date of Start Up Comments Credit will be issued upon receipt of completed fo...

Страница 87: ......

Страница 88: ...FLOWMAX Technologies 209 Citation Drive unit 5 6 Concord Ontario L4K 2Y8 Tel 905 264 1414 Fax 905 264 1147 E mail info flowmaxtechnologies com Web Site www flowmaxtechnologies com...

Отзывы: