The surface temperature of the pump may be influenced by the temperature of the liquid handled.
The maximum, permissible liquid temperature depends on the temperature class and must not exceed
the values in the table applicable below. The temperature rise at the seals, bearings and due to the
minimum permitted flow rate is taken into account in the temperatures.
Maximum permitted liquid temperature for diaphragm pumps:
Temperature
Maximum
Temperature limit of liquid handled
Class to
surface temperature
depending on material and construction variant.
EN 13463–1
permitted
Consult Flotronic Pumps Ltd.
T6
85
o
C (185
o
F)
Consult Flotronic Pumps Ltd
T5
100
o
C (212
o
F)
Consult Flotronic Pumps Ltd
T4
135
o
C (275
o
F)
105
o
C (221
o
F)
T3
200
o
C (392
o
F)
115
o
C (239
o
F)
T2
300
o
C (572
o
F)
115
o
C (239
o
F)
T1
450
o
C (842
o
F)
115
o
C (239
o
F)
Where there is any risk of the pump being run for prolonged periods against a closed or partially closed
valve generating high liquid and casing external surface temperatures, it recommended that users fit
an external surface temperature protection device.
2.5.2 Additional requirements for self-priming conditions
Where the system operation does not ensure control of priming, and the maximum permitted surface
temperature of the T Class could be exceeded, it is recommended for users to fit an external surface
temperature protection device.
2.6 Preventing the build up of explosive mixtures
ENSURE PUMP IS PROPERLY FILLED WHENEVER POSSIBLE AND DOES NOT RUN DRY
FOR LONGER THAN 5 MINUTES CONTINUOUSLY
Ensure the pump and relevant suction and discharge pipeline system is totally filled with liquid during
the pumping operation, so that an explosive atmosphere is prevented.
If the operation of the system cannot avoid this condition, ensure that the pump does not run dry for
more than 5 minutes continuously.
To avoid potential hazards from fugitive emissions of vapour or gas to atmosphere the surrounding
area must be well ventilated.
2.7 Preventing sparks
To avoid the potential hazard from random induced current generating a spark, the earth stud
on the pump casing or foot must be connected.
6-4
ATEX Safety Manual
Содержание F 500 series
Страница 15: ...7 Your Notes...
Страница 26: ...18 F Series 500 Style Plastic Aluminium Pumps Section 11 F Series 500 Style Plastic Aluminium Pumps...
Страница 30: ......
Страница 31: ...F Series 710 Style Stainless Steel Pumps 24 Section 12 F Series 710 Style Stainless Steel Pumps...
Страница 35: ......
Страница 36: ...30 F Series Good Food Style Pump Section 13 F Series Good Food Style Pump...
Страница 38: ......
Страница 40: ...35 F Series Slim Style Metallic Pumps Section 14 F Series Slim Style Metallic Pumps...
Страница 43: ......
Страница 44: ...40 F Series K Style Chemflo All PTFE Section 15 F Series K Style Chemflo All PTFE...
Страница 46: ......
Страница 48: ...45 Air Valves Section 16 Air Valves...
Страница 50: ...47 Pulsation Dampers Section 17 Pulsation Dampers...
Страница 54: ...51 Your Notes...
Страница 55: ...52 Rupture Protection Barriers Alarm Systems Section 18 Rupture Protection Barriers Alarm Systems...
Страница 59: ...56 Your Notes...
Страница 61: ......
Страница 62: ...60 Count Stop Pumps All Series Section 19 Count Stop Pumps All Series...
Страница 65: ...63 Your Notes...
Страница 67: ...65 Your Notes...
Страница 68: ...66 Your Notes...