2.7.6
Intrinsically Safe Flowmeters (EX i)
Intrinsically safe flowmeters and instruments are designed and certified for use in zone 1,
and zone 2; they function by limiting the power and energy available in the electrical
equipment to a level that is low enough that it cannot ignite the hazardous atmosphere.
Intrinsic safety installations are carried out in accordance with IEC/EN60079:14 and
IEC/EN60079:25.
Intrinsically safe products may be installed with standard wiring carried in regular
conduit; however
any wiring that crosses from a hazardous area to a safe area must pass
through an appropriately certified Intrinsically Safe barrier/ isolator.
If your meter is fitted with an integral intrinsically safe Instrument; installation must not
be carried out before reading the Instrument product manual, and any supplementary
manual (if applicable).
In regions that operated under ATEX or IECEx schemes, meters purchased with the ‘Reed
Only’ option can be used as an Intrinsically Safe ‘simple apparatus’ if the reed switch output
is used in conjunction with suitably certified associated equipment. The use of ‘simple
apparatus’ is defined in the international standard EN60079:11 and in many
countries/regions is allowed to be used in all hazardous areas with a temperature class of
T4 provided it is wired to a certified Intrinsically safe receiving instrument within the same
zone, or to a certified Intrinsically Safe barrier in the safe area.
Pulse output flowmeters may be used with the following grouping:
Ex ib IIB T4 Gb (Tamb<80
o
C)
Zones 1 & 2
Flowmeters fitted with an integral certified Intrinsically Safe instrument, use equipment
grouping from the certified instrument.
Please consult with a hazardous area expert within your country/region
before installing a simple apparatus flowmeter in a hazardous area
installation to be sure this is allowed in the relevant national standards.
NEVER INSTALL AN OM025P PLASTIC FLOWMETER IN A HAZARDOUS AREA
DUE TO THE RISK OF STATIC DISCHARGE.
CAUTION