Flo Corp TRACER 1000 LTT1 Скачать руководство пользователя страница 7

(877) 356-5463    |     (p) 330-331-7331    |     (f) 330-331-7172    |    www.FLO-CORP.com    |    ©  2017 FLO-CORP    |     REVA 1116         

5

   

(877) 356-5463    |     (p) 330-331-7331    |     (f) 330-331-7172    |    www.FLO-CORP.com    |    ©  2017 FLO-CORP    |     REVA 1116         

6

   

(877) 356-5463    |     (p) 330-331-7331    |     (f) 330-331-7172    |    www.FLO-CORP.com    |    ©  2017 FLO-CORP    |     REVA 1116         

7

   

(877) 356-5463    |     (p) 330-331-7331    |     (f) 330-331-7172    |    www.FLO-CORP.com    |    ©  2017 FLO-CORP    |     REVA 1116         

8

   

(877) 356-5463    |     (p) 330-331-7331    |     (f) 330-331-7172    |    www.FLO-CORP.com    |    ©  2017 FLO-CORP    |     REVA 1116         

9

   

(877) 356-5463    |     (p) 330-331-7331    |     (f) 330-331-7172    |    www.FLO-CORP.com    |    ©  2017 FLO-CORP    |     REVA 1116         

10

   

FLO-CORP assumes no responsibility for users incorrectly wiring their device.  Please refer to the wiring diagrams and read all wiring 

instructions for correct wiring of this device.

The Tracer 1000 is an active, single ended, non-isolated, 3 or 4 wire analog output transmitter. That is to say, the 
common’s (or returns) for both the 24 volt DC AND the 4 - 20 mA output are tied together internally in the Tracer 1000 

transmitter electronics. Therefore, when connected to a receiving device such as a PLC or multi-channel recorder, 

please make sure to follow the devices connection instructions for single ended, non-isolated inputs. If in doubt, use an 

input loop isolator to reduce ground loop problems.

Cable Entries & Shielding:

The Tracer 1000 enclosure has two 1/2” NPT cable entries that can be ordered with cable glands or sealed screw plugs. 

In order to retain the IP-68 enclosure rating, both cable entries must be fitted with IP-68 rated glands and/or screws and/

or conduit entry systems properly sealed. When wiring with shielded or armored cable, suitable cable glands must be 

used. The contact between the metal housing and the shielding of the cable is made by using a suitable EMC type cable 

gland.  For proper signal/noise shielding, ground the cable shield on the transmitter side ONLY, not on the supply side.

Wiring:

First, verify that the power supply for the Tracer 1000 is switched off. Next, open the Tracer 1000 enclosure by turning 

counterclockwise.  It may be necessary to loosen the cover locking screw with a .15cm allen key. The grounding 

screw on the transmitter housing should only be connected if there is complete assurance that the earth ground it will 

be connected to is exactly equal to the ground potential of the transmitters power.  If there is a ground offset you will 

potentially experience faulty signal outputs.  The grounding screw is not necessary to connect to earth ground for the 

Tracer 1000 to work properly.  Occasionally electrical codes will dictate the necessity for connection of the grounding 

screw and again, in these cases make sure the ground potentials are equivalent. After pulling the cable into the housing 

through the cable entry, install a drip loop outside the housing where the bottom of the loop is lower than the cable 

entry of the housing.  Using 16 to 22 AWG twisted shielded instrument wire, strip the wire ends carefully exposing each 

conductor.  The green terminals are screw-less,  cage clamp terminals that only require a small flat ended instrument 

screwdriver to be simply pressed down on the orange lever.  Insert the stripped end of the wire and release the 

screwdriver from the lever; the wire is now connected.  Follow the upper wiring decal by the terminals or follow the wiring 

diagram on fig. 4 (below)

Things to Avoid:

Avoid connecting the cable shielding on both ends.  If you shield both ends of the instrument cable, you run the risk of 

receiving electrical (RFI) or magnetic (EMI) noise or interference with the measuring signal.

Avoid conduit system leaks or joints or connections that will allow water to enter into the transmitter housing.  Any amount 

of water that will enter the housing will damage the electronics and will induce failure to the system.

Avoid using cable end sleeves on the terminations of the instrument cable.  The cage clamp terminals work best with 

bare conductors.

Operation 

Human Interface: 

The basic configuration of the Tracer 1000 can be changed from the customized settings as shipped from the factory.  

There are 2 ways that the user can change these settings.  1.) Tracer Configuration Tool: The Tracer Configuration Tool 

Содержание TRACER 1000 LTT1

Страница 1: ...877 356 5463 p 330 331 7331 f 330 331 7172 www FLO CORP com 2017 FLO CORP REVA 1116 1 TRACER 1000 LTT1 GUIDED WAVE RADAR LEVEL TRANSMITTER OPERATING INSTRUCTIONS...

Страница 2: ...zed Personnel All operations described in this operating instructions manual must be carried out only by trained specialist personnel authorized by the plant operator During work on and with the devic...

Страница 3: ...8 Resolution 04 Probe Type 316 SS Rod 1 4 Dia Coated Rod 3 8 Dia 316 SS Coaxial 3 8 Dia Wire Cable 1 2 Dia Probe Length L 316 SS Rod 2 41 120 316 SS Coaxial 0 120 Wire Cable 2 41 480 Length must be sp...

Страница 4: ...wells Bypass chambers and stilling wells Limited headroom for installation Limited headroom for installation Tall tanks Tall tanks MEDIA CHARACTERISTICS MEDIA CHARACTERISTICS Bulk solids Bulk solids...

Страница 5: ...80 PSIG Preparation FLO CORP s Tracer 1000 level transmitters are ready to install as is and are completely pre configured per the application data sheet or customer application information at time of...

Страница 6: ...is made of 316L Stainless Steel 1 4 diameter The Rod probe can be ordered with an optional teflon isolation sleeve and connections Both configurations have a threaded female connection on one end and...

Страница 7: ...und it will be connected to is exactly equal to the ground potential of the transmitters power If there is a ground offset you will potentially experience faulty signal outputs The grounding screw is...

Страница 8: ...877 356 5463 p 330 331 7331 f 330 331 7172 www FLO CORP com 2017 FLO CORP REVA 1116 8 Figure 3 Wiring Diagram Interconnecting Wiring to DigaCom 2000 Typical 3 Wire Connection...

Страница 9: ...877 356 5463 p 330 331 7331 f 330 331 7172 www FLO CORP com 2017 FLO CORP REVA 1116 9 External Power Wiring To Input ie PLC External Powered Wiring To DigaCom 2000 Level Monitor...

Страница 10: ...877 356 5463 p 330 331 7331 f 330 331 7172 www FLO CORP com 2017 FLO CORP REVA 1116 10 PNP Output Wiring...

Страница 11: ...ONLY BLUE Indicates the DIP switch positions through which groups of functions are selected example all functions related to the analog current output or the switching output GRAY Indicates the DIP sw...

Страница 12: ...w seconds while the disturbance signal scan is being performed Once the scan is completed successfully the LED will return to blinking alternately green and red If this is the only function you want t...

Страница 13: ...the tank to the level of the tank where you want the switch point to be activated Next set the following DIP switch to the ON 1 position 8 6 3 All other switches should be in the off position The LED...

Страница 14: ...surface of the connection thread The probe length is an important mechanical dimension which is needed to make sure the probe physically fits into the tank at the anticipated mounting location The pr...

Страница 15: ...by returning to the RUN mode Tracer still reading high Increase upper deadband to medium 7 4 This may require adjustment of 20mA set point 1 2 Tracer 1000 erratic output throughout the span of the pro...

Страница 16: ...by returning to the RUN mode Tracer still reading high Increase upper deadband to medium 7 4 This may require adjustment of 20mA set point 5 2 Tracer 1000 erratic output throughout the span of the pro...

Страница 17: ...h button Verify output by returning to the RUN mode Tracer still reading high Increase upper deadband to medium 7 4 This may require adjustment of 20mA set point 9 2 Tracer 1000 erratic output through...

Страница 18: ...struct your FLO CORP Model Number Simply match the category number to the corresponding box number Example LTT1 RN6 01 120 N 000 Tracer 1000 GWR Level Transmitter with 316 SS Rod Probe Type NEMA 6 Enc...

Отзывы: