Introduction

Please read carefully! No liability can be accepted for damage caused by improper use or installation of the Tracer 1000 Level Transmitter. 

Featuring TDR (Time Domain Reflectometry) technology, the Tracer 1000™ provides continuous radar level measurement 

and point level detection in liquids and solids, with analog and switching output. This innovative radar device has almost 

no installation restrictions – the 1” radar beam can be mounted in small tanks, tall and narrow nozzles and it measures 

precisely even with difficult tank geometries or close to interfering structures. Factory settings may be configured via 

HART® Communication protocol. Tracer 1000 is ideal for various types of processing and storage applications and has 

an exceptional performance in liquids even with low reflectivity such as light oils and hydrocarbons. 

       Safety Precautions

I

f you are unsure of the suitability of a Tracer 1000 for your installation, please consult your FLO-CORP representative for 

further information.

NOTE: REMOVE ALL PACKING INSERTS BEFORE OPERATING LEVEL TRANSMITTER.

Authorized Personnel

All operations described in this operating instructions manual must be carried out only by trained specialist personnel 
authorized by the plant operator. During work on and with the device the required personal protection equipment must 

always be worn.

Warning about misuse

Inappropriate or incorrect use of the instrument can give rise to application-specific hazards, e.g. vessel over fill or damage 

to 

system components through incorrect mounting or adjustment.

General Safety Instructions

The user must take note of the safety instructions in this operating instructions manual , the country specific installation 
standards as well as all prevailing safety regulations and accident prevention rules. The instrument must only be operated 

in a technically flawless and reliable condition. The operator is responsible for trouble-free operation of the instrument. 

During the entire duration of use, the user is obliged to determine the compliance of the required occupational safety 

measures with the current valid rules and regulations and also take note of new regulations.

Disclaimer

The information contained in this document is subject to change without notice. FLO-CORP makes no representations or 

warranties with respect to the contents hereof and specifically disclaims any implied warranties of merchantability or fitness 

for a particular purpose.

Содержание TRACER 1000 LTT1

Страница 1: ...877 356 5463 p 330 331 7331 f 330 331 7172 www FLO CORP com 2017 FLO CORP REVA 1116 1 TRACER 1000 LTT1 GUIDED WAVE RADAR LEVEL TRANSMITTER OPERATING INSTRUCTIONS...

Страница 2: ...zed Personnel All operations described in this operating instructions manual must be carried out only by trained specialist personnel authorized by the plant operator During work on and with the devic...

Страница 3: ...8 Resolution 04 Probe Type 316 SS Rod 1 4 Dia Coated Rod 3 8 Dia 316 SS Coaxial 3 8 Dia Wire Cable 1 2 Dia Probe Length L 316 SS Rod 2 41 120 316 SS Coaxial 0 120 Wire Cable 2 41 480 Length must be sp...

Страница 4: ...wells Bypass chambers and stilling wells Limited headroom for installation Limited headroom for installation Tall tanks Tall tanks MEDIA CHARACTERISTICS MEDIA CHARACTERISTICS Bulk solids Bulk solids...

Страница 5: ...80 PSIG Preparation FLO CORP s Tracer 1000 level transmitters are ready to install as is and are completely pre configured per the application data sheet or customer application information at time of...

Страница 6: ...is made of 316L Stainless Steel 1 4 diameter The Rod probe can be ordered with an optional teflon isolation sleeve and connections Both configurations have a threaded female connection on one end and...

Страница 7: ...und it will be connected to is exactly equal to the ground potential of the transmitters power If there is a ground offset you will potentially experience faulty signal outputs The grounding screw is...

Страница 8: ...877 356 5463 p 330 331 7331 f 330 331 7172 www FLO CORP com 2017 FLO CORP REVA 1116 8 Figure 3 Wiring Diagram Interconnecting Wiring to DigaCom 2000 Typical 3 Wire Connection...

Страница 9: ...877 356 5463 p 330 331 7331 f 330 331 7172 www FLO CORP com 2017 FLO CORP REVA 1116 9 External Power Wiring To Input ie PLC External Powered Wiring To DigaCom 2000 Level Monitor...

Страница 10: ...877 356 5463 p 330 331 7331 f 330 331 7172 www FLO CORP com 2017 FLO CORP REVA 1116 10 PNP Output Wiring...

Страница 11: ...ONLY BLUE Indicates the DIP switch positions through which groups of functions are selected example all functions related to the analog current output or the switching output GRAY Indicates the DIP sw...

Страница 12: ...w seconds while the disturbance signal scan is being performed Once the scan is completed successfully the LED will return to blinking alternately green and red If this is the only function you want t...

Страница 13: ...the tank to the level of the tank where you want the switch point to be activated Next set the following DIP switch to the ON 1 position 8 6 3 All other switches should be in the off position The LED...

Страница 14: ...surface of the connection thread The probe length is an important mechanical dimension which is needed to make sure the probe physically fits into the tank at the anticipated mounting location The pr...

Страница 15: ...by returning to the RUN mode Tracer still reading high Increase upper deadband to medium 7 4 This may require adjustment of 20mA set point 1 2 Tracer 1000 erratic output throughout the span of the pro...

Страница 16: ...by returning to the RUN mode Tracer still reading high Increase upper deadband to medium 7 4 This may require adjustment of 20mA set point 5 2 Tracer 1000 erratic output throughout the span of the pro...

Страница 17: ...h button Verify output by returning to the RUN mode Tracer still reading high Increase upper deadband to medium 7 4 This may require adjustment of 20mA set point 9 2 Tracer 1000 erratic output through...

Страница 18: ...struct your FLO CORP Model Number Simply match the category number to the corresponding box number Example LTT1 RN6 01 120 N 000 Tracer 1000 GWR Level Transmitter with 316 SS Rod Probe Type NEMA 6 Enc...

Отзывы: