When programming or changing the configuration of the Coaxial probe, the only values needed to be changed should be the 

Lower Range Value and the Upper Range 

Value, switch settings and response time.

See programming steps 2 & 3 for setting these 

values.

Please remember to tighten the housing cover 

properly by turning it clockwise.

Things to Avoid:

Avoid reversing the sequence when setting the DIP switches to the ON/1 position or when switching them back to OFF/0 

position.  The DIP switches should always be turned on from the 8th position first to the least position last.  Alternately, when 

setting the DIP switches to the off position, they should always be turned off from the least position first and the 8th position last.

Avoid cycling power while performing the programming steps.  If power is interrupted in mid-programming mode, with power 

off return all DIP switches to the OFF/0 position and apply power.  Then, start process from the beginning of the step that was 

interrupted.

Avoid lifting the DIP switch levers with pliers.  Using a small flat instrument screwdriver or flat object will decrease the chances 

of lifting the lever off of the switch foundation.

Probe Length, Dead Band and Measuring Range    

Probe Length: 

The upper or top reference point for definition of the probe length (L) is always the sealing surface of the connection thread.  

The probe length is an important mechanical dimension which is needed to make sure the probe physically fits into the tank at 

the anticipated mounting location.  The probe can touch the bottom of the tank, but it is not necessary.  The actual measuring 

range (M) of the Tracer 1000 is not the probe length (L).  The measuring range of the Tracer 1000 is the total probe length less 

the upper dead band (D1).  The dead band is a small inactive area at the top (D1) of the probe.  These are due to the presence 

of unavoidable signal disturbances at the top of the probe.  In the top dead band the measurements are non-linear or have 

reduced accuracy.  Therefore, it is not practical to actually measure level within those inactive or dead band area.  The length 

of the dead band depends on the probe type and the ∑r (dielectric) strength of the material being measured.

Restore Defaults

Set the following DIP switches to the ON/1 position. 8 - 5 - 4  All other switches should be in the off position. The LED will 

blink alternately green and red.  Press the push button. The LED will remain green for a few seconds while the reset to factory 

configuration is being performed.

Once the configuration 

is completed 

successfully, the LED will return to blinking alternately green and red. If this is the only function you want to perform, set all of 

the DIP switches to the OFF/0 position. Once the DIP switches are set to the off position, the LED will change to blinking green 

indicating the transmitter is in the RUN or Operating mode.

Figure 8:  Set Upper Range Value

Figure 9:  Restore DIP Switch Positions

Содержание TRACER 1000 LTT1

Страница 1: ...877 356 5463 p 330 331 7331 f 330 331 7172 www FLO CORP com 2017 FLO CORP REVA 1116 1 TRACER 1000 LTT1 GUIDED WAVE RADAR LEVEL TRANSMITTER OPERATING INSTRUCTIONS...

Страница 2: ...zed Personnel All operations described in this operating instructions manual must be carried out only by trained specialist personnel authorized by the plant operator During work on and with the devic...

Страница 3: ...8 Resolution 04 Probe Type 316 SS Rod 1 4 Dia Coated Rod 3 8 Dia 316 SS Coaxial 3 8 Dia Wire Cable 1 2 Dia Probe Length L 316 SS Rod 2 41 120 316 SS Coaxial 0 120 Wire Cable 2 41 480 Length must be sp...

Страница 4: ...wells Bypass chambers and stilling wells Limited headroom for installation Limited headroom for installation Tall tanks Tall tanks MEDIA CHARACTERISTICS MEDIA CHARACTERISTICS Bulk solids Bulk solids...

Страница 5: ...80 PSIG Preparation FLO CORP s Tracer 1000 level transmitters are ready to install as is and are completely pre configured per the application data sheet or customer application information at time of...

Страница 6: ...is made of 316L Stainless Steel 1 4 diameter The Rod probe can be ordered with an optional teflon isolation sleeve and connections Both configurations have a threaded female connection on one end and...

Страница 7: ...und it will be connected to is exactly equal to the ground potential of the transmitters power If there is a ground offset you will potentially experience faulty signal outputs The grounding screw is...

Страница 8: ...877 356 5463 p 330 331 7331 f 330 331 7172 www FLO CORP com 2017 FLO CORP REVA 1116 8 Figure 3 Wiring Diagram Interconnecting Wiring to DigaCom 2000 Typical 3 Wire Connection...

Страница 9: ...877 356 5463 p 330 331 7331 f 330 331 7172 www FLO CORP com 2017 FLO CORP REVA 1116 9 External Power Wiring To Input ie PLC External Powered Wiring To DigaCom 2000 Level Monitor...

Страница 10: ...877 356 5463 p 330 331 7331 f 330 331 7172 www FLO CORP com 2017 FLO CORP REVA 1116 10 PNP Output Wiring...

Страница 11: ...ONLY BLUE Indicates the DIP switch positions through which groups of functions are selected example all functions related to the analog current output or the switching output GRAY Indicates the DIP sw...

Страница 12: ...w seconds while the disturbance signal scan is being performed Once the scan is completed successfully the LED will return to blinking alternately green and red If this is the only function you want t...

Страница 13: ...the tank to the level of the tank where you want the switch point to be activated Next set the following DIP switch to the ON 1 position 8 6 3 All other switches should be in the off position The LED...

Страница 14: ...surface of the connection thread The probe length is an important mechanical dimension which is needed to make sure the probe physically fits into the tank at the anticipated mounting location The pr...

Страница 15: ...by returning to the RUN mode Tracer still reading high Increase upper deadband to medium 7 4 This may require adjustment of 20mA set point 1 2 Tracer 1000 erratic output throughout the span of the pro...

Страница 16: ...by returning to the RUN mode Tracer still reading high Increase upper deadband to medium 7 4 This may require adjustment of 20mA set point 5 2 Tracer 1000 erratic output throughout the span of the pro...

Страница 17: ...h button Verify output by returning to the RUN mode Tracer still reading high Increase upper deadband to medium 7 4 This may require adjustment of 20mA set point 9 2 Tracer 1000 erratic output through...