7
Technical specifications
CAT
Application field
Ⅰ
Circuits not connected to mains
Ⅱ
Circuits directly connected to a low-
voltage installation
Ⅲ
Building installation
Ⅳ
Source of the low-voltage installation
Operating altitude: 2000 m (6562
ʹ
).
Jaw opening: 37 mm (1.45 in.).
Pollution degree: 2.
EMC: EN 61326-1.
Shock vibration: Random vibration per MIL-PRF-28800f Class 2 (5–55 Hz, 3
g
maximum).
7.2
Electrical specifications
Accuracy is ±(% r number of digits (dgt)) at 23
℃
±5
℃
(73.4
℉
±9
℉
),
<80% RH.
Table 7.1
Voltage (TRMS)
Function
Range
Accuracy (of reading)
1
DCV
99.99 V
±(0.7% + 2 dgt)
999.9 V
ACV
0.05–99.99 V
±(1.0% + 5 dgt)
999.9 V
50–500 Hz
VFD
ACV
0.05–99.99 V
50–60 Hz ± (1% + 5
dgt)
999.9 V
1. DCV <1000 dgt, add 6 dgt to the accuracy. ACV <1000 dgt, add 3 dgt to the accuracy.