5
Operation
Figure 5.6
Phase rotation
1.
Set the function switch to the
position.
2.
Enter Phase rotation mode by pressing the
button repeatedly until the
indicator is displayed.
3.
Connect the red test lead to the presumed phase line 1 and the black test
lead to the presumed phase line 3.
4.
One of the following results is displayed:
•
OL V
flashes if the voltage is >1000 V.
•
Lo V
flashes if the voltage is <30 V.
•
outF
flashes if the frequency is >65 Hz or <45 Hz.
•
If normal,
L1
is displayed for about 3 seconds. Then
L2
is displayed and
the meter beeps twice.
5.
Move the red test lead to the presumed phase line 2 immediately, before
"L2" extinguishes from the display.
#T559825; r. AI/33557/33557; en-US
26