41
10. Temperature
regulation
10.1. Select method of regulation
10.1.1.
Select temperature regulation method
All temperature regulation functions are selected under the
menu option:
Extract air regulation
Limits the supply air temperature in connection with pure
room or extract air regulation so that sudden fluctuations
are avoided when temperatures are too high or too low.
Activate the function in the menu option:
RESTART
Set parameters in the menu option:
RESTART
Summer/Winter compensation
Summer compensation: Adjustment of temperature setpoint
(in relation to regulation, supply air, room air or extract air)
in accordance with regulation for high outdoor air temperature
in summer.
Winter compensation: Adjustment of temperature setpoint
(in relation to regulation, supply air, room air or extract air)
in accordance with regulation for low outdoor air temperature
in winter.
Activate the function in the menu option:
RESTART
and for supply air regulation in the menu option:
RESTART
Set parameters in the menu options:
Main index > Unit > Temp control > Setpoints > Summer
comp.
Main index > Unit > Temp control > Tmp Setpoints >
Winter comp.
Combined room/extract air regulation with supply air
regulation in winter
Setpoint compensation with winter operation for:
Tmp control mode = Room SuWi (cascade regulation of
room and supply air in summer, pure supply air regulation
in winter).
or
Tmp control mode = Extract air SuWi (cascade regulation of
extract and supply air in summer, pure supply air regulation in
winter).
The comfort setpoint is used for cascade regulation in
summer (summer/winter switching).
In the winter, these room setpoints must be adapted to
supply air regulation.
Precondition:
One of the regulation types Room SuWi and Extract air
SuWi must be selected according to the Summer/Winter
compensation regulation method.
Supply air compensation must then be selected in the menu
option:
Main index > Configuration > Configuration 2 > Supply
air temp.
Set parameters in the menu option:
Main index > Unit> Temp control > Min/Max supply air
regulation
10.1.2.
Select additional functions for temperature
regulation
There are a number of different additional functions that
can be combined with the temperature regulation method
selected. All are in the menu option:
Main index > Configuration > Configuration 2
OBS!
Room regulation requires the installation
of special room sensors!
Main index > Configuration > Configuration 1
Main index > Configuration > Configuration 1 > Tmp
control mode = RmSplyC Su or ExSplyC Su
Main index > Configuration > Configuration 1 >
Tmp control mode = Room or Exhaust
Main index > Unit> Temp control >
Min/Max supply air regulation
Main index > Configuration > Configuration 2 >
SuWi comp.temp = Yes