30
Parameter
Value
Function
Heating
No
No heating circuit.
Yes
Heating register without preheating. Analogue heating valve output.
Yes+Preh.
Heating register with preheating. Analogue heating valve output.
Electric heating
Electric heating register and type of regulation.
No
No electric heating register available.
Analogue
Electric heating register with regulation via one analogue output.
1Step
1-step electric heating register with regulation via one analogue and one digital output.
2Step
2-step electric heating register with regulation via one analogue and two digital outputs.
3Step
3-step electric heating register with binary regulation via one analogue and two digital outputs.
Cooling
Select cooling register and type of regulation.
No
No cooling register.
Water
One analogue output for cooling valve output
DX 1step
One analogue and one digital output for 1-step regulation of DX cooling unit.
DX 2step
One analogue and two digital outputs for 2-step regulation of DX cooling unit.
DX 3step
One analogue and two digital (binary) outputs for 3-step regulation of DX cooling unit.
Extra heating
No
No extra heating register.
Yes
Extra heating register without preheating. Analogue heating valve output.
Yes+Preh.
Extra heating register with preheating. Analogue heating valve output.
Extra electric
heating
Extra electric heating register and type of regulation.
No
No extra electric heating register available.
Analogue
Extra electric heating register with regulation via one analogue output.
1Step
Extra 1-step electric heating register with regulation via one analogue and one digital output.
2Step
Extra 2-step electric heating register with regulation via one analogue and two digital outputs.
3Step
Extra 3-step electric heating register with binary regulation via one analogue and two digital
outputs.
Extra cooling
Extra cooling register and type of regulation.
No
No extra cooling register.
Water
One analogue output for extra cooling valve output
DX 1step
One analogue and one digital output for 1-step regulation of extra DX cooling unit.
DX 2step
One analogue and two digital outputs for 2-step regulation of extra DX cooling unit.
DX 3step
One analogue and two digital (binary) outputs for 3-step regulation of extra DX cooling unit.
Fire damper
Fire damper.
No
No fire damper.
Yes
One digital output and input each for fire damper regulation.
Yes+FollUnit
One digital output and input each for fire damper regulation. The fire damper is opened when the
unit starts and closed when the unit stops.
Configuration 1
With this parameter, the system is activated after parameter settings have been set, i.e. when
Configuration 1, Configuration 2 and Config.In/Outputs have been set (value Ready).
Not ready
The system is locked and cannot be started.
Ready
The system is unlocked after the parameter settings have been set (value Ready for Configuration
2 and Config.In/Outputs), i.e. the system can be started.
Restart
Passive
The system must be restarted after parameter settings have been set in Configuration 1. Changed
settings in Configuration 2 are implemented.
After restart, the value is changed automatically from Execute to Passive.
Execute