10
The following actions are possible at the different levels:
Level 1: No restrictions, no password required.
•
Read rights to all menus except system parameters,
configuration and detail menus.
•
Read rights to alarm lists and alarm history.
Level 2: End user, password 1000.
•
All rights as for level 1, plus:
•
Read rights to all menus except configuration menus.
•
Write rights to the most important setpoints (Setpoints/
Settings > Setpoints).
•
Alarms and alarm history can be acknowledged and reset.
Level 3: System administrator, password 2000.
•
All rights as for level 2, plus:
•
Rights to all menus except I/O configuration and system
settings.
Level 4: OEM, password given only in consultation with the
Flexit service organisation.
•
All rights as for level 3, plus:
•
Rights to all menus and system settings.
You can change the standard password to your own
password. At least authority level 3 is required. The menu
option required is:
2.3. Adjust
setpoints
2.3.1.
Temperatures/Air flow
The menu option for adjusting temperature setpoints and air
flow is:
Temperature setpoints can be changed on lines three and
four. Air flow values can be changed on lines five to ten.
The default configuration in the unit is for constant air flow
regulation.
2.4. Select method of regulation
2.4.1.
Extract air regulation
Limits the supply air temperature in connection with pure
room or extract air regulation so that sudden fluctuations
are avoided when temperatures are too high or too low.
Setpoints/Settings
p
g
Setpoints
All settings
>
Timing program
Ec.St1
>
Setp.comf.heat
20 °C
Setp.econ.heat
18 °C
Setp.TF step 1
100 l/s
Setp.TF step 2
300 l/s
Setp.TF step 3
500 l/s
Setp.FF step 1
100 l/s
Setp.FF step 2
300 l/s
Setp.FF step 3
500 l/s
Activate the function on the menu selection:
Set parameters in the menu selection:
2.5. Operating
modes
The system can be set to run in various operating modes,
and there are two alternative menu options that will lead to
the required line on the menu:
NB!
Room regulation requires the
installation of special room sensors
Operating modes
OFF
The unit is switched off.
AUTO
The unit is running in automatic mode and
controlled according to the means of regulation
and priorities that have been set
Temp.Fan
A number of different manual operating modes in
which temperature and fan mode are combined
freely, for example Comf.St2
Main index> System overview > Password handling
Main index > Unit > Setpoints/Settings
Main index > Configuration > Configuration 1 > Tmp.
control mode = Room or Exhaust
Main index > Unit> Temp control > Min/Max supply air
regulation
RESTART
Start page > Manual operation
Main index > Unit > Operating mode > Manual operation