background image

21

7. General 

functions

7.1. Operating 

modes

There are a number of different operating modes, depending 
on the functions activated in the system. To see the current 
operating mode, go to the menu option:

Main index > Unit > Operating mode

7.1.1. 

Operating modes - Change

The system can be set to run in various operating modes, 
and there are two alternative menu options that will lead to 
the required line on the menu: 
 

Start page > Manual operation

Main index > Unit > Operating mode > Manual operation

7.1.2. 

Operating modes - Monitor

There are a number of different operating modes, depending 
on the functions activated in the system. To see the current 
operating mode, go to the menu option:

Main index > Unit > Operating mode

6.3.  Loan an application or software

Preconditions:

• 

The (uncompressed) files must be in the root folder of 
the SD memory card.

• 

The files must have the names shown in the screen below. 

Files on SD card 

 

Procedure

1. 

Insert the memory card into the regulator.

2. 

Switch off the regulator.

3. 

Press the button in the hole next to the regulator's 
status screen with a thin object so that a clicking 
sound is heard, and keep the button pressed down.

4. 

Switch on the regulator.

5. 

Wait until the LED flashes red and green.

6. 

Release the button.

7. 

Wait until the LED goes out.

8. 

Switch off the regulator.

9. 

Switch on the regulator.

6.4.  Error diagnosis - Snapshot

For troubleshooting, the status of the ventilation unit just 
before the alarm was triggered can be studied afterwards by 
means of export to an SD card. Authority level 4 is required. 

Procedure
1. 

Insert a blank SD memory card into the regulator.

2. 

Backup the error diagnosis to the memory card.

 

Main index > System overview > Save/Load > 
A-snapshot save - SD= Execute.

3. Wait 

until:

Main index > System overview > Save/Load > 
A-snapshot save - SD = Yes. 

A file has now been generated on the SD card that can be 
read from a PC.

Operating modes

OFF

The unit is switched off.

AUTO

The unit is running in automatic mode and 
controlled according to the means of regulation 
and priorities that have been set

Temp.Fan

A number of different manual operating modes in 
which temperature and fan mode are combined 
freely, for example Comf.St2

Содержание CS2000 V2

Страница 1: ...User Guide CS2000 Automatic control V2 112140E 03 2016 01...

Страница 2: ...n 10 2 5 Operating modes 10 2 6 Set the calendar and timing program 11 2 6 1 General 11 2 6 2 Week schedule 11 2 6 3 Dayschedule 11 2 6 4 Calendar exceptions and stop 12 2 7 Alarm handling 12 3 Menu t...

Страница 3: ...Con guration DX cooling 39 9 1 4 Parameters 39 10 Temperature regulation 10 1 Select method of regulation 41 10 1 1 Select temperature regulation method 41 10 1 2 Select additional functions for temp...

Страница 4: ...t text boxes are used in the document to draw the user s attention to various things This may be anything from pure information text to particularly important details to ensure that the system is not...

Страница 5: ...ing coil Modbus extender a communication card that connects the ventilation unit s components to the control unit via data communication Power supply board a circuit board that distributes the power s...

Страница 6: ...uit board that distributes the power supply to the components of the ventilation unit not the electric heating coil and control cabinet There is also a terminal block for the components required to re...

Страница 7: ...s components have the following functions Component Function P1 Connection for power supply P2 Data communication P3 Data communication P4 Connection for external pressure sensor accessory P5 Connecti...

Страница 8: ...T 16 L 17 Heating IN 18 Heating OUT 19 N 20 Not used Terminal block P12 has the following signals Block no Function 21 Cooling 0 10V AO 22 Cooling G0 23 External control 1 DI 24 External control 1 G0...

Страница 9: ...1000 The menu option for making the change is 2 2 3 Set Time Date To change the time and date go to the menu option 2 2 4 Login In order to make changes to the system it is normally necessary to log i...

Страница 10: ...4 Select method of regulation 2 4 1 Extract air regulation Limits the supply air temperature in connection with pure room or extract air regulation so that sudden uctuations are avoided when temperat...

Страница 11: ...Copy times for the timing program from Monday to Tuesday Friday Passive no copying Copying starts Return to the display screen Tuesday Same function as for Monday Sunday Same function as for Monday E...

Страница 12: ...ute in the menu Alternatively the alarm can be reset with the menu option Then select Alarm Reset and Execute EXAMPLE Val x Date Only the time for start is relevant Start Date 01 01 09 Result 1 Januar...

Страница 13: ...emp Outs air damper cmd Extr air damper cmd Actual fan step Act sply fan stpt Act sply outp value Sply fan outp sign Supply air ow Act exh fan stpt Act exh fan value Exh fan outp signal Exhaust air ow...

Страница 14: ...e Alarm snapshot Diagnostic Password handling Daylight saving time HMI Versions Plant info Target Diag object handler Con guration Con guration by Con guration 1 Con guration 2 Con g IO s Check con g...

Страница 15: ...ed Op hours settings Temp control Act controlled tmp Tmp setpoints Heat recovery Loop controllers Supply fan Exhaust fan Heat recovery Operating hours Supply fan Reset Exhaust fan Reset Fan settings M...

Страница 16: ...Flow2 K Value Zero point Cal Pressure Temp sensor 1 Temp sensor 2 Temp sensor 3 Act Fan Output 1 Fan 1 Speed Fan 1 Alarm Act Fan Output 2 Fan 2 speed Fan 2 alarm Act Rotor Output Act Heater Output Rot...

Страница 17: ...t required Sett service load Sett factory load Sett service save Sett factory save A snapshot save SD Archive save SD Archive Trace save SD BSP load Versions Application info Flexit STD_AHU_v207 dato...

Страница 18: ...conv Fan steps type Fan alarm Fan fdbk Fan deviation alarm Fan comp room tmp Fan comp air qual Fan comp outs tmp Fan htg clg Fan Eng Unit Tmp stpt selection Deviation alarm tmp Su Wi comp tmp Hrec fro...

Страница 19: ...em settings You can change the standard password to your own password At least authority level 3 is required The menu option required is 5 General settings 5 1 Regulator Parameter Value Function Imper...

Страница 20: ...grated 0 31 The contrast of the backlighting Message time integrated 2 15 s Time for displaying an error message for example when a setpoint outside the valid range is entered Alarm acknowl level 1 2...

Страница 21: ...regulator 3 Press the button in the hole next to the regulator s status screen with a thin object so that a clicking sound is heard and keep the button pressed down 4 Switch on the regulator 5 Wait un...

Страница 22: ...t step 1 for analogue outputs System in comfort operation in step 1 uses setpoint step 1 for analogue outputs Parameter Value Function Manual operation Comf St2 Econ St3 Comf St3 System in economy ope...

Страница 23: ...turn overrides the normal timing program only in operating mode Up to 10 periods or exception days can be speci ed for each calendar Parameter Value Function From BMS Off Econ St1 Comf St1 Econ St2 Co...

Страница 24: ...creen Tuesday Same function as for Monday Sunday Same function as for Monday Exception Shows current command when the current day is an exception day Go to the day switching schedule for exception day...

Страница 25: ...December are exception days every year Time End date 01 01 00 will not work because 1 January comes before 23 December Start Date 23 12 09 End date 01 01 10 23 December 2009 up to and including 1 Jan...

Страница 26: ...tion Configuration Configuration via HMI Configuration 1 Done Configuration 2 Done Config In outputs Done IO config control Duplicated OK Not configured OK NB It is important for this setting to be co...

Страница 27: ...Both re alarms Filter alarm No No lter alarm Comb Supply air and extract air lter with common alarm input Supply air Input only for supply air lter alarm Extract air Input only for extract air lter al...

Страница 28: ...output One One output for example for priority alarms Two Two outputs for priority and non priority alarms External setpoint No No analogue input for connection of external setpoint or compensation f...

Страница 29: ...fans regulated in ow regulated systems Supply air fan slave One digital and analogue output each and three analogue inputs for frequency regulated fans in pressure regulated systems where the supply...

Страница 30: ...tion via one analogue output 1Step Extra 1 step electric heating register with regulation via one analogue and one digital output 2Step Extra 2 step electric heating register with regulation via one a...

Страница 31: ...available If the extract air sensor holds the values the temperature is used for start No The function is not available Heating The function is available only for heating Cooling The function is avail...

Страница 32: ...and DO2 TRUE Fan alarm Inputs for fan alarm e g thermojunction Logical 1 alarm No No alarm Comb Digital input for common alarm Supply air Digital input for supply air fan alarm Extract air Digital in...

Страница 33: ...Main setpoint Room temp mix Select the room temperature that is to be used for regulation if more than one temperature is available Average Average Min Lowest temperature Max Highest temperature Room...

Страница 34: ...behind the heat exchanger One analogue input for extra supply air sensor Frost guard heating No No frost protection Sensor Frost protection via sensor One analogue input for regulated frost protectio...

Страница 35: ...temperature maintenance and operation and one digital input for frost guard Pump Extra heating No No pump Yes Pump without pump motion Digital pump output Yes Motion Pump with pump motion One digital...

Страница 36: ...itions but only one signal The syntax must be correct 1 0 1 closed closes opens open Digital input Aux input No No aux input Input Extra digital input for display only Alarm Extra digital input with a...

Страница 37: ...ration page for all digital inputs without alarm function Digital alarm Go to the hardware con guration page for all digital inputs with alarm function Other Go to the hardware con guration page for a...

Страница 38: ...ion No cooling function activated Cold water register activated One step DX cooling activated Two step DX cooling activated Three step DX cooling activated 3 9 Cooling 9 1 Cooling It is possible to ch...

Страница 39: ...on activated Cold water register activated One step DX cooling activated Two step DX cooling activated Three step DX cooling activated 9 1 4 Parameters 1 Cooling parameters Main index Unit Temp contro...

Страница 40: ...00 Shows the current cooling regulator value 0 18000 300 s 0 18000 0 s Passive Active Passive Cooling Boost 5 00 I time 300 s D time 0 s Out of operation Passive 1 Cooling parameters Main index Unit T...

Страница 41: ...ration for Tmp control mode Room SuWi cascade regulation of room and supply air in summer pure supply air regulation in winter or Tmp control mode Extract air SuWi cascade regulation of extract and su...

Страница 42: ...oo much This is regulated via a separate setpoint for heating and cooling Heating and cooling can be activated separately The function can be implemented using an extract air sensor if there is no roo...

Страница 43: ...peration Osstp block The function blocks the air damper or extract air fan when the system is started optimally or via temperature delta 11 Fan regulation 11 1 Select method of regulation 11 1 1 Selec...

Страница 44: ...fan is ow regulated accordingly Set parameters in the menu option Main index Unit Setpoints Settings 11 1 1 5 Extract air fan slave The extract air fan is driven dependent on the supply air fan Pa l...

Страница 45: ...control 1 G0 25 External control 2 DI 26 External control 2 G0 27 Fire smoke DI 28 Fire smoke G0 29 Air quality 0 10 AI 30 Air quality G0 31 Heating 0 10V AO 32 Heating 24V 33 Heating G0 34 Fire dampe...

Страница 46: ...on 14 Relay contact NO closes if cooling is required 15 Relay contact NO closes if cooling is required 21 Cooling 0 10V signal 22 Cooling G0 signal The cooling function must be activated in the contro...

Страница 47: ...ation 1 Fire alarm Then select Alarm It is possible to connect various types of switch sensor that have pulse or xed positions The contact function can also be changed By default the control unit is s...

Страница 48: ...Flexit AS Televeien 15 N 1870 rje www flexit no...

Отзывы: