5 Selection of the Measuring Point
UMFLUXUS_F7V4-6-2EN, 2017-10-01
21
5
Selection of the Measuring Point
The correct selection of the measuring point is crucial for achieving reliable measurement results and a high measurement
accuracy.
A measurement on a pipe is possible if
• the ultrasound propagates with a sufficiently high amplitude (see section 5.1)
• the flow profile is fully developed (see section 5.2)
The correct selection of the measuring point and thus, the correct transducer positioning guarantees that the sound signal
will be received under optimum conditions and evaluated correctly.
Due to the variety of applications and the different factors that influence the measurement, there is no standard solution for
the transducer positioning. The correct position of the transducers is influenced by the following factors:
• diameter, material, lining, wall thickness and shape of the pipe
• medium
• gas bubbles in the medium
Avoid measuring points in the vicinity of deformations and defects of the pipe and in the vicinity of welds.
Avoid locations with deposit formation in the pipe.
The ambient temperature at the measuring point has to be within the operating temperature range of the transducers (see
Technical Specifications).
Select the location of the transmitter within cable reach of the measuring point.
The ambient temperature at the location has to be within the operating temperature range of the transmitter (see Techni-
cal Specifications).
If the measuring point is within an explosive atmosphere, the danger zone and gases that may be present have to be de-
termined.The transducers and the transmitter have to be appropriate for these conditions.
5.1
Acoustic Penetration
The pipe has to be acoustically penetrable at the measuring point. The acoustic penetration is reached when pipe and me-
dium do not attenuate the sound signal so strongly that it is completely absorbed before reaching the second transducer.
The attenuation in the pipe and in the medium depends on:
• kinematic viscosity of the medium
• proportion of gas bubbles and solids in the medium
• deposits on the inner pipe wall
• pipe material
The following requirements have to be met at the measuring point:
• the pipe is always filled completely
• no material deposits in the pipe
• no bubbles accumulate
Observe the notes in the following table.
Attention!
Observe the Safety Instructions for the Use in Explosive Atmosphere (see document SIFLUXUS).
Note!
Even bubble-free media can form gas bubbles when the medium expands, e.g., before pumps and
after great cross-section extensions.